Reference sensor of the collector fi eld cooling function.
Settings range: S1-S8, VFS1-2, active storage, RC / Default: none
6.7.4 Field Cooling Sensor
SunMaxx Solar | 5098 NY 206 Bainbridge NY 13733 | 1.877.786.6299 1.877.270.7875 fax | www.sunmaxxsolar.com
RELA
Y FUNC
TIONS
CAUTION
This function does not activate the solar pump to cool the collector. Therefore, please refer to the collector protection.
6.8 ANTI LEGIONELLA
This function is used to heat up the system during selected periods to eliminate legionella bacteria.
Settings range: S1-S8, VFS1-2, Active storage/ Default setting: none
This temperature has to be detected for the time set in AL residence time at the AL sensors for a successful heat up.
Settings range: 60°C to 99°C (140°F to 210°F) / Default setting: 70°C (158°F)
6.8.1 AL T Set
This determines the time span for which the AL T set temperature must be detected for a successfull AL heat up.
Settings range: 1-120 min / Default setting: 60 min
6.8.2 AL Residence Time
This displays the date and time of the last successful heat up.
No settings
6.8.3 Last AL Heat
This temperature is used to measure the AL temperature.
Settings range: S1-S8, VFS1-2, Active storage/ Default setting: none
6.8.4 AL Sensor 1
Optional AL sensor
When a second sensor is connected, both sensors must reach and hold the setpoint temperature for the residence time for a successful heat up.
Settings range: S1-S8, VFS1-2, Active storage/ Default setting: none
6.8.5 AL Sensor 2