6.11 SOLID FUEL BOILER
The relay is used to control an additional solid fuel boiler.
Settings range: On, Off
Maximum temperature at target sensor to enable difference function
If the temperature at the target sensor exceeds this value, difference function is disabled.
Settings range: 0 °C to 99°C (32 °F to 210°F) / Default setting: 60°C (140°F)
6.10.5 DF Tmax
Maximum temperature in the storage. If this is exceeded, the relay is switched off.
Settings range: OFF to 100°C (212°F) / Default setting: 70°C (158°F)
6.11.1 SF Tmax
Minimum temperature in the solid fuel boiler to switch on the pump. If the temperature at the boiler sensor is below this temperature, the relay
is disabled.
Settings range: 0 °C to 100°C (32 °F to 212°F) / Default setting: 70°C (158°F)
6.11.2 SF Tmin
Switch on and Switch off condition for the temperature difference between boiler and storage.
Switch on difference Δ T SF
Settings range: 5 to 20 K / Default setting: 8
Switch off temperature difference Δ T SF
Settings range: 0 K to Switch Δ T SF / Default setting: 7
6.11.3 ΔT SF
This determines the sensor, that is used as boiler sensor.
Settings range: S1-S8, VFS1-2, Active storage/ Default setting: none
6.11.4 Boiler Sensor
This determines the sensor, that is used as storage sensor.
Settings range: S1-S8, VFS1-2, Active storage/ Default setting: none
6.11.5 Storage Sensor