6.12 ERROR MESSAGE
The relay is switched on, when one or more protective funtion is active or a message is shown.
This function can be inverted, so that the relay is alway on and switches off when a protective function or a message is shown.
Settings range: On, Inverted, Off / Default setting: Off
Collector alarm
Collector protection
System protection
Frost protection
Recooling
Antilegionella protection
Message
This menu is used to confi gure the system pressure montoring via direct sensor. As soon as the set limits are exceeded, the relay is switched on.
6.13.1 Pressure Monitor
6.13 PRESSURE MONITOR
The relay is switched on, when one or more protective funtion is active or a message is shown.
The relay is switched on when the pressure drops below set minimum or exceeds the set maximum pressure.
Settings range: On, Off / Default setting: Off
Type of pressure sensor
This menu is used to determine the type of pressure sensor used.
Please note: If e.g. VFS1 is connected, RPS1 option is not shown.
Settings range: Off; 0-0,6 bar; 0-1 bar; 0-1,6 bar; 0-2,5 bar; 0-4 bar; 0-6 bar; 0-10 bar
Default setting: Off
6.13.1.1 RPS1 / RPS2
Minimum pressure. If this value is undershot, an error message is displayed and the relay is switched on (Hysteresis 0.5 bar).
Settings range: Off; 0,0 to 1,6 bar
Default setting:
6.13.1.2 Pmin
Maximum pressure. If this value is exceeded, an error message is displayed and the relay is switched on (Hysteresis 0.5 bar).
Settings range: Off; 0,0 to 10 bar
Default setting: 1,6 bar
6.13.1.3 Pmax