Room reference temperature in day mode. If this temperature is exceeded at the room temperature sensor at the set times, the relay is switched
off.
Settings range: 10° C to 30° C (50° F to 86° F)
6.17.1 Room Set Day
Room reference temperature in night mode. If this temperature is exceeded at the room temperature sensor at the set times, the relay is
switched off.
Settings range: 10° C to 30° C (50° F to 86° F)
6.17.2 Room Set Night
This menu determines the sensor for the room temperature.
Settings range: S2 to S7, RC
6.17.3 Room Sensor
Set the desired periods of time when the heat circuit day mode should be active. 3 periods can be set per day, settings can also be copied to
other days. Outside the set times the heating function is working in night mode.
Setting range: from 00:00 to 23:59 /default setting: 06:00 to 22:00
6.17.4 Periods
6.18 HEAT QUANTITY
Constant fl ow
When the heat meter mode „Flow rate“ is selected, an approximated heat quantity is calculated using the values the user has to enter. These are
type of glycol/AntiFreeze, glycol portion and fl ow rate. These values are put into correlation with the temperature data of collector sensor and
storage sensor. If necessary a correction value for ΔT can be set: Since for the heat meter the collector and the storage temperature are used, a dif
-
ference to the fl ow respectively return fl ow temperature can be compensated by changing Offset ΔT accordingly.
Example:
Displayed collector temp. 40°C (104°F), measured flow temperature 39°C (102°F), displayed storage temperature 30°C (86°F), measured return
temperature
31°C (88°F) = results in a correction value of -20% (displayed ΔT 10K, real ΔT 8K = -20% correction)
VFS
When the mode VFS is selected, the direct sensor with combined temperature and fl ow measurement is used.
CAUTION
The heat quantity measured in the mode “Flow rate” is a calculated approximation for function control of the system.
This determines the sensor that is used to measure the fl ow temperature.
Settings range: S1-S8, VFS1-2, active collector, active storage/ Default setting: S1
6.18.1 Flow Sensor (X)