Safety and Installation Instructions - Document 001-14158 Rev **

 

 

©May 2007 SunPower Corporation. All rights reserved. Specifications included in this manual are subject to change without notice.

 

Safety and Installation Instructions 
(United States and Canada) 

 

1.0  Introduction  

This manual provides safety and installation instructions for UL-listed 

SunPower photovoltaic (PV) modules carrying the UL logo on the product label 

(Figure 1). 

 

Figure 1    

 

 

 

1.1 Disclaimer of Liability 

The installation techniques, handling and use of this product are beyond 

company control. Therefore, SunPower does not assume responsibility for 

loss, damage or expense resulting from improper installation, handling or use. 

 

1.2 Underwriters Laboratories

 (UL) Listing Information 

This product meets or exceeds the requirements set forth by UL1703 for PV 

Modules. This UL Standard covers flat-plate PV modules and panels intended 

for installation on buildings or those intended to be freestanding. To satisfy the 

listing for this product the modules must be mounted with a rack or standoff 

structure. The UL listing does not include integration into a building surface 

because additional requirements may apply. This product is not intended for 

use where artificially concentrated sunlight is applied to the module. 

 

1.3 Limited Warranty 

Module limited warranties are described in the SunPower warranty certificates 

obtainable at 

www.sunpowercorp.com

.   

2.0 

Safety Precautions 

Before installing this device, read all safety instructions in this document. 

 

 

 

  Cover all modules in the PV array with an opaque cloth or material before 

making or breaking electrical connections. 

  All installations must be performed in compliance with the National 

Electrical Code (NEC) and any applicable local codes. 

  There are no user serviceable parts within the module. Do not attempt to 

repair any part of the module. 

  Installation should be performed only by authorized personnel.  

  Remove all metallic jewelry prior to installing this product to reduce the 

chance of accidental exposure to live circuits. 

  Use insulated tools to reduce your risk of electric shock. 

  Do not stand on, drop, scratch, or allow objects to fall on modules. 

  If the front glass is broken, or the back sheet is torn, contact with any 

module surface or module frame can cause electric shock. 

  Do not install or handle the modules when they are wet or during periods of 

high wind. 

  Contact your module supplier if maintenance is necessary. 

  Save these instructions! 

3.0  Electrical Characteristics 

The module electrical ratings are measured under Standard Test Conditions 

(STC) of 1 kW/m² irradiance with AM 1.5G spectrum and a cell temperature of 

25º C. SunPower modules deliver specific electrical characteristics (Figure 2).  

Electrical Characteristics at STC

 

Module 

Rated 

Power 

(W) 

Power 

Tol 

(%) 

Voltage 

at Rated 

Power 

(V) 

Curr at 

Rated 

Power 

(A) 

Open 

Circuit 

Voltage  

(V) 

Short 

Circuit 

Current 

(A) 

Max 

Series 

Fuse (A) 

Max Sys 

Voltage 

(V) 

Current 

Temp 

Coeff 

(mA/°C) 

Voltage 

Temp 

Coeff 

(mV/°C) 

Power 

Temp 

Coeff 

(%/°C)C) 

SPR-220-

WHT 

220 

+/- 8 

39.8 

5.53 

48.3 

5.95 

15 

600 

3.5 

-136.8 

-0.38 

SPR-215-

BLK 

215 

+/- 8 

39.8 

5.40 

48.3 

5.80 

15 

600 

3.5 

-136.8 

-0.38 

SPR-210-

WHT 

210 

+/- 5 

40.0 

5.25 

47.7 

5.75 

15 

600 

3.5 

-136.8 

-0.38 

SPR-205-

BLK 

205 

+/- 5 

40.0 

5.13 

47.8 

5.53 

15 

600 

3.5 

-136.8 

-0.38 

SPR-200-

WHT 

200 

+/- 5 

40.0 

5.0 

47.8 

5.4 

15 

600 

3.5 

-136.8 

-0.38 

 

Figure 2 

 

A photovoltaic module may produce more current and/or voltage than reported 

at STC. Sunny, cool weather and reflection from snow or water can increase 

current and power output. Therefore, the values of Isc and Voc marked on the 

module should be multiplied by a factor of 1.25 when determining component 

voltage ratings, conductor ampacities, fuse sizes, and size of controls 

connected to PV output. An additional 1.25 multiplier may be required by the 

NEC for sizing fuses and conductors as described in the NEC Section 690-8.  

 

3.1 Fire Rating 

The module is Class C fire rated.  

4.0  Electrical Connections 

Modules may be connected in series and/or parallel to achieve the desired 

electrical output as long as certain conditions are met. Please use only the 

same type of modules in a combined source circuit.  

 

4.1 Equipment Grounding 

To avoid electrical shock, ground the frame of the module or array before 

wiring the circuit using a grounding method that meets NEC requirements for 

grounding solar electrical systems. SunPower recommends the following two 

methods of grounding the module frame.   

 

1) Attach an equipment ground conductor with stainless steel hardware at one 

of the four designated 0.17  grounding holes on the module frame. If an 

equipment ground conductor larger in diameter than #10 AWG is necessary, a 

grounding lay-in lug is required. A thread-forming 10-32 stainless steel screw 

is required when using a self-drilling type screw to make the frame ground 

connection. Please refer to NEC Article 690 on grounding PV arrays for 

specific requirements. 

 

2) SunPower modules can be grounded using third-party grounding washer or 

clip systems provided they have been tested and certified to meet UL 467 

requirements for bonding/grounding systems and are installed according to the 

manufacturer’s specified instructions. 

 

4.2 System Grounding 

 

4.3 Series Connection

 

The modules may be wired in series to produce the desired voltage output. Do 

not exceed the maximum system voltage indicated in Figure 2. 

 

4.4 Parallel Connection

 

The modules may be combined in parallel to produce the desired current 

output. Each series string or module may be required to be fused prior to 

combining with other strings. Figure 2 describes the maximum fuse size 

allowed. Please refer to the NEC Article 690 for additional fusing requirements. 

Important!

  Read this instruction sheet in its entirety 

before installing, wiring, or using this product in any way. 

Failure to comply with these instructions will invalidate 

the SunPower Limited Warranty for PV Module. 

Danger!

  Module interconnects pass direct current (DC) and 

are sources of voltage when the module is under load and 

when it is exposed to light. 

Direct current can arc across 

gaps and may cause injury or death if improper 

connection or disconnection is made, or if contact is 

made with module leads that are frayed or torn.

 Do not 

connect or disconnect modules when current from the 

modules or an external source is present. 

Important!

 For optimal performance, SunPower PV modules 

must only be used in configurations where the positive 

polarity of the PV array is connected to ground. 

Failure to 

comply with this requirement will reduce the 

performance of the system and invalidate SunPower’s 

Limited Power Warranty for PV Modules.

 

 

For more information on grounding the system correctly, visit 

our website at 

www.sunpowercorp.com/inverters

 or contact 

SunPower technical support at 1-877-SUN-0123. 