37
INSTALLATION and OPERATION MANUAL
INSTALLATION and OPERATION MANUAL
INSTALLATION and OPERATION MANUAL
INSTALLATION and OPERATION MANUAL
11.3. Technical parameters
Table 7
Pell 25
Pell 40
Pell 70
Pell 90
Pell 150
Nominal heat output
kW
25
40
70
90
150
Min./Max. heat output
kW
5÷25
10÷40
15÷70
30÷90
50÷150
Average
power
consumption
Firing-Up mode
Operate mode
Self-cleaning mode
W
W
W
~ 400
~
60÷70
~ 1300
~ 400
~
60÷70
~ 1300
~ 400
~
70÷110
~ 1300
~ 400
~
70÷110
~ 1300
~ 400
~
70÷110
~ 1300
Electric power supply
V/Hz
~
230/50
~
230/50
~
230/50
~
230/50
~
230/ 50
Overall
dimensions
Height H
Width L / Depth D
mm
mm
575
615/245
575
700/300
575
750/350
575
750/350
650
750/350
Minimal recommended
size of boi ler combustion
chamber
Height
Width
Depth
mm
mm
mm
250
250
390
350
450
550
350
450
600
500
500
450
500
500
800
Required chimney draught
Pa
25
27
30
32
40
Boiler mounting kit
P
P
P
P
P
Heat-output adjustment
P
P
P
P
P
Combustion Efficiency
Emitted heat
%
%
96
92
96
92
96
92
96
92
96
92
Weight of burner
kg
26
30
37
51
55
Burner body
Length
Width
Height
A, mm
B, mm
C, mm
390
245
360
390
245
360
390
245
360
390
245
360
390
330
410
Combustion
chamber housing
Diameter
Length
D, mm
E, mm
140
220
170
300
170
340
170
340
210
340
Feeder chute
Diameter
Length
G,mm
I,mm
60
250
60
250
60
250
60
250
60
250
Automatic cleaning system
P
P
P
P
P
P
Built-in CPU control unit
U
P
P
P
P
P
Burner flame, length* F, mm
750
1000
1500
1600
2000
Pellet auger
Diameter
Length M, mm
75
1500
75
1500
75
1500
75
1500
75
1500
Flexible connection
Diameter
Length N, mm
60
700
60
700
60
700
60
700
60
700
Weight of auger
kg
6
6
6
6
6