background image

 

9 of 32 

© 2015 Watts Water Technologies

Phase 2 - Electrical Rough-in

To prevent the risk of personal injury and/or death, make sure power is not 

applied to the product until it is fully installed and ready for final testing. All 

work must be done with power turned off to the circuit being worked on.

STEP 2.1:
Circuit Breaker (Overcurrent Protection)

TapeMat(s) must be protected against overload by a circuit breaker. GFCI type (ground fault 

circuit interrupter) or AFCI type (arc-fault circuit interrupter) breakers may be used if desired, 

but are not necessary when using SunStat controls with integral GFCI
The rating of the breaker (see 

Table 5)

 is determined by the amp draw of the heating mats.  

Add the amp ratings of all mats to be connected to the SunStat control (see Table 2 or the 

Nameplate Label on the mat).  If the total is less than 12 amps, use a 15 or 20 A breaker 

(preference is 15 A). If the total is between 12 and 15 amps, use a 20 A breaker. If the total 

is over 15 A, another circuit will be required with its own breaker and SunStat control.

 Circuit Breakers and Supply Wire

Mat(s)

Supply Wire

Breaker

VAC

total amps

(AWG)*

qty type**

rating

120

up to 12 amps

14

1

SP

15 or 20 A

120 up to 15 amps

12

1

SP

20 A

240 up to 12 amps

14

1

DP

15 or 20 A

240 up to 15 amps

12

1

DP

20 A

*  Recommended only. Follow local codes for wire gauge size.
** SP= single-pole, DP=double-pole

Table 5

STEP 2.2:
Install Electrical Boxes

SunStat Thermostat:

 Install an extra-deep electrical box for the SunStat thermostat. Follow the instructions included 

with the SunStat for complete information on location and wiring. The thermostat must be 

located at least 4 feet (1.2 meters) away from shower openings to avoid being exposed to 

water or touched by a person while in the shower area.

SunStat Relay:

Install an extra-deep electrical box for any SunStat Relay(s). The SunStat Relay is used when 

more than 15 amps must be controlled by one SunStat Thermostat. Follow the instructions 

included with the SunStat Relay for complete information on location and wiring.

Junction Boxes:

 If a mat is to be located so its Power lead is not long enough to reach the SunStat Control or 

SunStat Relay directly, a junction box must be installed. Do not attempt to make a connection 

to other wiring without a junction box. Use a standard junction box with a cover, mounting 

it below the subfloor, in the attic, in the wall, or in another location easily accessible after all 

coverings are complete. If the SunStat sensor wire is not long enough to reach the SunStat 

Control directly, it may be extended.  A junction box may be required by local code to make this 

connection.  Follow the installation instructions included with the SunStat Control for details.
For construction with an existing wall or where the wall is covered, cut the necessary openings 

to mount the electrical boxes listed above. Wait to install the boxes until all wiring is fed into 

these locations to make it easier to pull the wire.

It may be possible to tap into 

an existing circuit as long as 

there is adequate capacity for 

the mat(s) and any additional ap-

pliance, such as a hair dryer or 

vacuum cleaner. Avoid circuits 

which have lighting, motors, 

exhaust fans, or hot tub pumps 

due to possible interference.

Summary of Contents for TapeMat C12 series

Page 1: ...are local codes may require this product and or the thermostatic control to be installed or connected by an electrician Please leave this manual with the end user Includes Custom TapeMat and ShowerMat...

Page 2: ...6 Application Indoor floor heating only X on the nameplate label indicates CUL Listing for this application Suitable for installation in a shower area see Step 3 10 for restrictions W on the nameplate...

Page 3: ...or or moderate injury This symbol identifies practices actions or failure to act which could result in property damage or damage to the equipment Table of Contents Important Safety Information 3 Phase...

Page 4: ...g NEVER forget to install the floor sensor included with the thermostat NEVER install TapeMat in any walls or over walls or partitions that extend to the ceiling NEVER install mats under cabinets or o...

Page 5: ...product appears to be damaged the factory must be called before proceeding with the installation Before installing TapeMat make sure to fully inspect the products and carefully plan the site Items Nee...

Page 6: ...40 2 x 20 12002024 4 0 25 32 45 2 x 22 6 12002224 4 5 22 28 50 2 x 25 12002524 5 0 20 26 60 2 x 30 12003024 6 0 17 21 70 2 x 35 12003524 7 0 14 18 80 2 x 40 12004024 8 0 12 16 90 2 x 45 12004524 9 0 1...

Page 7: ...9 C 8 000 ohms Table 3 Floor Sensor Resistance Values STEP 1 3 Use a digital multi meter set to the 200 or 2000 2k range to measure the resistance between the conductors of the mat power leads Record...

Page 8: ...0VAC Sensor wire AFTER MAT AND SENSOR ARE FASTENED TO FLOOR OHMS Mat black to white black to blue for 240VAC Mat black to ground Mat white to ground blue to ground for 240VAC Sensor wire AFTER FLOOR C...

Page 9: ...ons included with the SunStat for complete information on location and wiring The thermostat must be located at least 4 feet 1 2 meters away from shower openings to avoid being exposed to water or tou...

Page 10: ...m plate up to the electrical box For multiple power leads multiple mats install 3 4 conduit Thermostat Sensor The SunStat Control sensor can be installed with or without electrical conduit depending o...

Page 11: ...to reach the control location it may be possible to cut the mat mesh and pull loose the length of heating wire needed It is acceptable to run the power lead several feet in the floor area and embed i...

Page 12: ...6 from a toilet wax ring It may be installed closer to walls if necessary but make sure the heating wire will not be located underneath finish trim Install in line with vanity and counter areas Instal...

Page 13: ...Roll over Installing in front of cabinets and toilets Install mat right up to the face of the cabinet as shown above Mat can be installed under tile to within 6 from the wax ring and can slightly unde...

Page 14: ...tar DO NOT staple or apply tape over the heating wire Damage can result DO NOT use nails duct tape other types of tape or other unapproved fasteners to hold the heating wire or mesh in place Damage ca...

Page 15: ...t 1 into the mat area halfway between the heating wires and secure it using hot glue Do not cross the heating wires It may be necessary to chisel a small section of the subfloor to accommodate the sen...

Page 16: ...run the heating wire through a non masonry curb causing it to overheat 7 Embed mats in mortar and install only under tile stone brick or other masonry surface per this instruction manual 8 Never begin...

Page 17: ...see their web site at www tile assn com When installing floor coverings other than tile or stone follow industry and or manufacturer s recommendations Ensure the mat is first covered with a layer of s...

Page 18: ...ick according to manufacturer s specifications Fully embed the heating wire and splices so that no portion of these show Install floor covering after the mortar has cured Special Precautions Isolation...

Page 19: ...rack isolation membrane Insulating barrier TapeMat Thin set or self leveling mortar bed Insulation per International Residential Code Chapter 11 Insulation per International Residential Code Chapter 1...

Page 20: ...ing and heating panels contained below the floor Do not penetrate floor with nails screws or similar devices Nappe de chauffage de sol Avertissement Rique de choc lectrique C blage lectrique et nappes...

Page 21: ...istance between two heating wires Electrical box Single gang Mud Ring if required Electrical conduit Sensor wire Mat power lead Mat Mesh Thin set thick set thin slab or self leveling mortar bed Tile s...

Page 22: ...IOM WR TapeMat 1526 22 of 32 Appendix 90 Turn 90 Flip Roll over Turn 180 or Back to Back Turn Fill in Technique Types of turns...

Page 23: ...23 of 32 2015 Watts Water Technologies Step by step layout for a typical bathroom 1 2 3 4 5 6 7 8...

Page 24: ...One mat Toilet Shower Bath Tub Closet Vanity Control Install 4 6 from walls Install mats right up to the face of the cabinet The heat only conducts about 1 1 2 from the wire Install mats 6 away from...

Page 25: ...Three mats Small bath layout One mat Front Entryway Doorway Doorway Control Sink Bath Tub Install mats right up to the face of the vanity The heat transfers only about 1 1 2 from the wire Control Inst...

Page 26: ...ring approximately 20 from back wall Fill in triangular areas by removing wire from mat and securing with hot glue Toilet Control Do not begin the mat inside the shower area The controls should NEVER...

Page 27: ...local inspector or the authority having jurisdiction Never install the mat in shower walls or any other walls Shower installation detail Locate power lead and factory connection to heating wire at lea...

Page 28: ...m any electrical work unless qualified to do so Work should be done with great care and with power turned off to the circuit being worked on Follow all local building and electrical codes The thermost...

Page 29: ...If it trips again check for a short circuit in the mat as detailed earlier in this manual If mat is damaged record resistance between all wires and contact the manufacturer If mat is not damaged repla...

Page 30: ...to the control Also see Sensor is loose or broken above Loose connection s on line side and or load side of control Remove and reinstall the wire nuts at each connection Make sure the wire nuts are t...

Page 31: ...eding with the installation or proposed repair THECOMPANIESDISCLAIMANYWARRANTYNOTPROVIDEDHEREIN INCLUDING ANY IMPLIED WARRANTY OF MERCHANTABILITY OR IMPLIED WARRANTY OF FITNESS FOR A PARTICULAR PURPOS...

Page 32: ...RQA 8 4 0 2 1 3 1 1 3 3 1 5 SunTouch Customer Support USA Toll free 888 432 8932 USA Fax 417 831 4067 Canada Toll free 888 208 8927 Canada Fax 905 332 7068 Latin America Tel 52 81 1001 8600 Latin Amer...

Reviews: