2.7.11. Operation modes
Configuring mode
The BMS device can receive, check and take into account additional configuration data sent
by its main EMS/VMS device (master/slave relation).
Normal Operation mode
The device is fully operational. It means that no error is detected and that the device can
execute its Control and Monitoring tasks.
Degraded mode
The BMS device detects either an internal or external failure. If a critical error occurs during
Normal Operation mode, the mode management function goes to Degraded mode.
Shutdown mode
All BMS services are stopped.
De-energized mode
When the battery is in idle mode for a specified time the BMS shuts down all non-essential
electronics to minimize the quiescent current.
2.7.12. System components operation modes dependencies
Operating mode
Protective disconnect
device
Communication
BMS
Configuring mode
Open
Yes
Active
Normal Operation mode
Closed
Yes
Active
Degraded mode
Open
Yes
Active
De-energized mode
Open
No
Inactive
Shutdown mode
Open / Closed
No
Sleep
Table 12. System components operation modes dependencies