background image

MSE Series Electric Boilers – Installation and Service Manual 

 

 

 

17

PROBLEM 

CAUSE 

SOLUTION / CHECK 

 

  Flow Switch is open 

  Check for closed circuit between FS-5 

and FS-6 and 24V (AC) across FS-6 
and C-1. 

 

 Element fault. 

RISK OF ELECTROCUTION! – MAIN 
POWER TO ELEMENTS MUST BE 
DISCONNECTED!  Next, disconnect 
element wires from main contactor(s) 
and check for continuity.  If no 
continuity, replace element. If 
continuity, the contactor is defective. 
(To confirm contactor defect, check for 
continuity across main contactor when 
closed.) 

Pump runs constantly when there is no 
call for heat. 

  Internal control fault. 

 Replace controller. 

  Pump ceased or burnt out. 

  Repair or replace. 

  Pump wiring fault. 

  Check and repair wiring. 

  Pump fuse blown. 

 Check pump fuse and replace if 

necessary. 

Pump will not run. 

  Internal control fault. 

 Replace controller. 

Controller does not operate normally. 

  Internal control fault. 

 Replace controller. 

  Relief valve not reseating properly. 

 Quickly lift and release manual 

discharge lever on relief valve to assist 
proper reseating.  If this fails, replace 
pressure relief valve. 

Pressure relief valve discharges water. 

  Pressure reducing valve set too high. 

 Reduce setting of pressure reducing 

valve. 

  Element or sensor threads leaking. 

 Turn off all electricity to the boiler.  

Remove wires from element terminals 
and tighten elements (with correct 
socket wrench).  Turn off water, drain, 
remove and apply sealant if necessary. 

Water leaking from electric boiler. 

  Plumbing connections leaking. 

 

  Tighten incoming pipes and pressure 

relief valve.  Turn off water, drain and 
remove and apply sealant if necessary.  
(Be sure to turn off electricity before 
draining or elements will burn out.) 

7.2 SENSOR 

CHECK 

1. 

SHUT OFF MAIN POWER TO THE ELEMENT HEATING CIRCUIT BEFORE TROUBLESHOOTING!

   

2.  Confirm correct sensor wiring. Refer to the wiring diagram sticker on the back of the boiler front 

casing panel. 

3.  Make sure there is no power applied to the controller before measuring resistance.  

4.  To test for a defective sensor, measure the resistance directly at the sensor location. The resistance 

should be roughly 12000 ohms at room temperature (68

°

F). For other temperatures and their 

corresponding resistance readings, refer to the 

BC-1 Controller Manual

5.  If the meter reads a very high resistance, there may be a broken wire, a poor wiring connection or a 

defective sensor. If the resistance is very low, the wiring may be shorted, there may be moisture in 
the sensor or the sensor may be defective. 

 
 

 

Summary of Contents for Mini-Star 12MSE

Page 1: ...djacent to the boiler for reference Ensure boiler is full of water before turning on electricity Elements will burn out immediately without water in the boiler A boiler installed above radiation level...

Page 2: ...28 8 14 4 11 5 15MSE 15 51 185 72 1 62 5 41 6 36 0 18 0 14 4 18MSE 18 61 422 86 5 75 0 54 6 47 3 23 7 18 9 20MSE 20 68 240 96 2 84 3 63 6 55 1 27 6 22 0 24MSE 24 81 895 115 100 66 5 57 7 28 8 23 1 27...

Page 3: ...Rise C Table 2 Water Temperature Rise vs Flow Rate in GPM LPM Model KW 10 F 5 6 C 20 F 11 C 30 F 17 C 40 F 22 C 6MSE 6 4 2 16 2 1 8 1 4 5 1 0 4 9MSE 9 6 2 23 3 1 12 2 1 8 1 6 6 12MSE 12 8 3 31 4 2 16...

Page 4: ...tends the life of the components and increases energy efficiency With the addition of an Outdoor Sensor to the BC 1 controller Outdoor Reset can be used to increase or decrease outlet water temperatur...

Page 5: ...ters i e standard stud spacing on the top side of the hangers The lag screws must be suitably anchored to safely support the weight of the boiler including water content piping and wiring 2 5 PIPING T...

Page 6: ...m water It can allow oxygen to enter the system and cause serious corrosion problems As well minerals dissolved in the water supply will precipitate when heated thus preferentially depositing in the b...

Page 7: ...ng and check the related codes to properly size conductors switches and overcurrent protection Several openings are provided on the right and bottom of the casing for different voltage connections For...

Page 8: ...let Sensor Connect inlet water temperature sensor to terminals BI and CM common The Boiler Inlet Sensor is attached by cable tie to the boiler inlet pipe OS CM Outdoor Sensor Optional Outdoor Sensor f...

Page 9: ...uce flow rate and cause thermal shock Figure 2 also illustrates the connections to the air purger not supplied by manufacturer and expansion tank in the line from the boiler to the radiation units Add...

Page 10: ...automatic on off switching power supply to the boiler pump or a pump contactor The load current of this output is limited by the pump fuse selected boiler supplied with 3 A fuse and must not exceed 5...

Page 11: ...ss and hold simultaneously all three buttons for 1 second The display then advances to the Adjust menu and the ADJUST segment is turned on in the display The display will automatically revert back to...

Page 12: ...ic Boiler Mode 1 parallel piping setpoint heating Mode 3 parallel piping dedicated DHW generation only Mode 4 parallel piping outdoor reset with optional DHW override BOIL TARGET 180 F Minimum boiler...

Page 13: ...is changing derivative it will determine when to switch a stage on or off This feature prevents short cycling which can quickly wear out contactors and cause rapid temperature fluctuations The heating...

Page 14: ...t override setting A1 Pump 1 Pump 2 r a m k e t 3 0 0 y a l e R 4 2 V 0 2 1 V c a l a n r e t x E I I s s a l C r e m r o f s n a r T N L C R L1 L2 P1 P2 C HT ST R FS FS 1 2 3 4 5 6 T1 Figure 7 Wiring...

Page 15: ...er c Elements will burn out if the boiler is not filled with water when electrical power is turned on Do not connect thermostat wires until system has been filled with water Water should be drained ou...

Page 16: ...BC 1 display is blank Internal control fault Replace controller E01 Controller unable to read from its EEPROM Verify all the settings in the adjust menu are correct Shr Controller is unable to read fr...

Page 17: ...set too high Reduce setting of pressure reducing valve Element or sensor threads leaking Turn off all electricity to the boiler Remove wires from element terminals and tighten elements with correct s...

Page 18: ...ngineering Company distributor call us if you need help locating a distributor near your area If you require any technical assistance or have any comments about our product please write or phone us at...

Page 19: ...MSE Series Electric Boilers Installation and Service Manual 19 Notes Section 9...

Page 20: ...4 2 4 Wall mounting 5 2 5 Piping 5 2 6 System Operating Requirements 6 3 Wiring 7 3 1 Electrical Wiring 7 4 Startup Instructions 9 4 1 Warning 9 4 2 Startup 9 5 BC 1 Controller Information 10 5 1 Con...

Reviews: