background image

MSE Series Electric Boilers – Installation and Service Manual 

 

 

 

9

b.    Power Supply to Heaters 

The supply cable has to be sized based on the amperage in Table 1 and the cables used. 

Connect only specified line voltage and phase power to main terminal block on the control panel. 
Strip wire ends before inserting into terminal block. Tighten terminal screw clamps. Attach ground 
wire to ground terminal block on the control panel. 

 

Startup Instructions 

Section 4 

4.1 WARNING 

WARNING 

The following instructions are intended as a guide for a Qualified Service Technician.  Before 

switching the power on, fill the system with water and vent air. Check for and repair any leaks 
in the water piping. 

4.2 STARTUP

 

a.    Fill System

 

Figure 2 shows the suggested set-up for a make-up water supply using a pressure regulator (supplied 
with “PS” package).  Do not apply full line make-up water pressure to the system.  Fill the system to 
approximately 12 psi (cold water) if the expansion tank is pressurized at 12 psi.  The expansion tank 
should be sized to provide the system with enough volume for thermal expansion and contraction while 
maintaining operating pressures within safe and reasonable limits.  There should be no significant 
pressure fluctuations in systems having both an effective automatic fill valve and a properly sized 
expansion tank or expansion tank arrangement.  The standard pressure relief valve supplied with the 
boiler is rated at 30 psi, or as required by order, but the maximum working pressure cannot exceed 90 psi 
for the electric boiler.  Once the system is filled with water, all trapped air must be removed to avoid air 
locks, which can reduce flow rate and cause thermal shock.  Figure 2 also illustrates the connections to 
the air purger (not supplied by manufacturer) and expansion tank in the line from the boiler to the 
radiation units.  Additional air purgers should be installed at high points in the system to assist in 
removing air which can accumulate from the water supply line.  All high points must be vented. 

b.    Startup Procedure 

Perform the following procedure as a check for proper boiler and system operation: 
1.  Press and hold three keys found below the LCD screen of the controller until “Adjust” is displayed 

(Figure 5). In adjust mode, enter the desired settings for your heating application (see BC-1 Boiler 
Controller Manual for more information). (Note: This boiler is also equipped with a non-adjustable, 
high-limit temperature device set at 239

°

F as safety limit control.  The high limit temperature device 

has an automatic reset function.) 

2.  Turn up all room thermostats above room temperature.  
3.  When power is supplied to the controller, the LCD displays “- - -“.   When the thermostat calls for 

heat, the pump will be energized immediately and the pump indicator,  , will display on the LCD. 
The “- - -“ screen is replaced with the boiler target temperature. Next, the three stages are energized 
along with the stage indicator, 

, in sequence and based on the user settings. Once the boiler 

water temperature reaches the setpoint, the controller will regulate the boiler water temperature using 
the three stages. The number of stages that switch on is based on the heating demand and user 
settings.  After all room thermostats are satisfied, the controller de-energizes the three stages, in 
sequence, and then switches off the pump.  

4.  Current must be checked by a qualified electrician at the feeder panel and compared to the values 

shown in Table 1.  

5.  Turn thermostats to the desired room temperature. 

Summary of Contents for Mini-Star 12MSE

Page 1: ...djacent to the boiler for reference Ensure boiler is full of water before turning on electricity Elements will burn out immediately without water in the boiler A boiler installed above radiation level...

Page 2: ...28 8 14 4 11 5 15MSE 15 51 185 72 1 62 5 41 6 36 0 18 0 14 4 18MSE 18 61 422 86 5 75 0 54 6 47 3 23 7 18 9 20MSE 20 68 240 96 2 84 3 63 6 55 1 27 6 22 0 24MSE 24 81 895 115 100 66 5 57 7 28 8 23 1 27...

Page 3: ...Rise C Table 2 Water Temperature Rise vs Flow Rate in GPM LPM Model KW 10 F 5 6 C 20 F 11 C 30 F 17 C 40 F 22 C 6MSE 6 4 2 16 2 1 8 1 4 5 1 0 4 9MSE 9 6 2 23 3 1 12 2 1 8 1 6 6 12MSE 12 8 3 31 4 2 16...

Page 4: ...tends the life of the components and increases energy efficiency With the addition of an Outdoor Sensor to the BC 1 controller Outdoor Reset can be used to increase or decrease outlet water temperatur...

Page 5: ...ters i e standard stud spacing on the top side of the hangers The lag screws must be suitably anchored to safely support the weight of the boiler including water content piping and wiring 2 5 PIPING T...

Page 6: ...m water It can allow oxygen to enter the system and cause serious corrosion problems As well minerals dissolved in the water supply will precipitate when heated thus preferentially depositing in the b...

Page 7: ...ng and check the related codes to properly size conductors switches and overcurrent protection Several openings are provided on the right and bottom of the casing for different voltage connections For...

Page 8: ...let Sensor Connect inlet water temperature sensor to terminals BI and CM common The Boiler Inlet Sensor is attached by cable tie to the boiler inlet pipe OS CM Outdoor Sensor Optional Outdoor Sensor f...

Page 9: ...uce flow rate and cause thermal shock Figure 2 also illustrates the connections to the air purger not supplied by manufacturer and expansion tank in the line from the boiler to the radiation units Add...

Page 10: ...automatic on off switching power supply to the boiler pump or a pump contactor The load current of this output is limited by the pump fuse selected boiler supplied with 3 A fuse and must not exceed 5...

Page 11: ...ss and hold simultaneously all three buttons for 1 second The display then advances to the Adjust menu and the ADJUST segment is turned on in the display The display will automatically revert back to...

Page 12: ...ic Boiler Mode 1 parallel piping setpoint heating Mode 3 parallel piping dedicated DHW generation only Mode 4 parallel piping outdoor reset with optional DHW override BOIL TARGET 180 F Minimum boiler...

Page 13: ...is changing derivative it will determine when to switch a stage on or off This feature prevents short cycling which can quickly wear out contactors and cause rapid temperature fluctuations The heating...

Page 14: ...t override setting A1 Pump 1 Pump 2 r a m k e t 3 0 0 y a l e R 4 2 V 0 2 1 V c a l a n r e t x E I I s s a l C r e m r o f s n a r T N L C R L1 L2 P1 P2 C HT ST R FS FS 1 2 3 4 5 6 T1 Figure 7 Wiring...

Page 15: ...er c Elements will burn out if the boiler is not filled with water when electrical power is turned on Do not connect thermostat wires until system has been filled with water Water should be drained ou...

Page 16: ...BC 1 display is blank Internal control fault Replace controller E01 Controller unable to read from its EEPROM Verify all the settings in the adjust menu are correct Shr Controller is unable to read fr...

Page 17: ...set too high Reduce setting of pressure reducing valve Element or sensor threads leaking Turn off all electricity to the boiler Remove wires from element terminals and tighten elements with correct s...

Page 18: ...ngineering Company distributor call us if you need help locating a distributor near your area If you require any technical assistance or have any comments about our product please write or phone us at...

Page 19: ...MSE Series Electric Boilers Installation and Service Manual 19 Notes Section 9...

Page 20: ...4 2 4 Wall mounting 5 2 5 Piping 5 2 6 System Operating Requirements 6 3 Wiring 7 3 1 Electrical Wiring 7 4 Startup Instructions 9 4 1 Warning 9 4 2 Startup 9 5 BC 1 Controller Information 10 5 1 Con...

Reviews: