START UP PROCEDURE 

Before starting the machine, make sure the machine is level within 1/8 inch in all directions, the bin 
or dispenser leg height can be adjusted by rotating the leg foot. 

Check the water level in the water trough. It should be approximately ½ inch above the top of the 
water pump impeller housing. The water level can be adjusted by bending the float arm. 

Move the ICE-OFF-WASH switch to the ICE position. The switch is located in the control box. 
Remove the ice machine front panel or remove the lower grill on the under counter models to 
access the control box. 

Check for proper water flow over the evaporator(s).  There should be an even flow of water over 
the evaporator(s). 

Check the water regulating valve (water cooled machine) for proper adjustment by measuring the 
discharge pressure which should be adjusted to maintain 250 psi (17.01 bar / 1.723 MPa). Adjust 
the water regulating valve as required. Water exiting the condenser should be between 100°F 
(38°C) and 110°F (43°C). 

As ice begins to form on the evaporators, check the freeze pattern of the ice. Ice should form 
evenly across the evaporator. 

Bridge Thickness and Timer Adjustment 

Once the unit has gone through 1 or 2 harvest cycles, verify that the ice production is per the 
chart below.

 

Model 

Batch Weight 

UIM-240FA, UIM-300FA 

3.2 – 3.5 

As a reference, when ice drops off the evaporator(s) during harvest, check the bridge thickness of 
the ice slab. The bridge should be approximately 3/16 of an inch on Undercounter, UIM-240FA and 
UIM-300FA units. The bridge should be approximately 1/8 of an inch on all other units. If the batch 
weight or bridge thickness is incorrect, the timer will need to be adjusted. 

Both the Ice Batch Weight and Bridge Thickness are controlled by the freeze timer located in the 
control box. To check the timer setting, add the seconds of each dipswitch turned to the “ON” 
position. The number beside the each dipswitch represents seconds. To increase the Batch Weight 
and bridge thickness, increase the timer setting. To decrease the Batch Weight and bridge 
thickness, decrease the timer setting. The freeze timer can be adjusted by sliding one or more 
switches to either the “ON” or “OFF” position to obtain the desired setting. 

© Supera    

September 2015           

 

9

Summary of Contents for UIM-240FA

Page 1: ...MANUAL This manual contains important information regarding your Supera unit Please read this manual thoroughly prior to equipment set up operation and maintenance Failure to comply with regular maint...

Page 2: ...one 866 953 3288 E mail Service SuperaCo com Any service communication must include Model Serial Number A detailed explanation of the issue Keep this manual for future reference The Supera Service Par...

Page 3: ...al evidence of loss or damage must be fully described and noted on your freight bill or express receipt and signed by the carrier s agent The claim should be filed on a form available from the carrier...

Page 4: ...vidually to a floor drain The use of condensate pumps for draining water is not recommended by Supera Supera assumes no responsibility for improperly installed equipment Note The purge drain fitting i...

Page 5: ...of an electrical fire Adjustments Level the machine within 1 8 inch in all directions Check the bin control for proper adjustment Check the water in the water trough for proper level Check the ice bri...

Page 6: ...tion All water supply lines must be installed per local codes Use 1 4 inch O D minimum on air cooled machines On water cooled machines 3 8 inch O D minimum tubing must be run to the condenser The wate...

Page 7: ...OFF WASH Switch is located in the control box Remove the grill screws to access the control box Note This unit does not have a splash curtain This model utilizes a thermostatic bin control in place o...

Page 8: ...This unit does not have a splash curtain This model utilizes a thermostatic bin control in place of a mechanical bin switch ON OFF WASH Switch is located in the control box Remove the grill screws to...

Page 9: ...now supplied to the water purge valve hot gas valve and the harvest motor The water purge valve opens and allows the water pump to purge the water remaining in the water trough removing impurities and...

Page 10: ...vaporators check the freeze pattern of the ice Ice should form evenly across the evaporator Bridge Thickness and Timer Adjustment Once the unit has gone through 1 or 2 harvest cycles verify that the i...

Page 11: ...e capillary tube thermo well the bin thermostat opens and the machine will shut off Bin Control Adjustment All Models Except Undercounter Models Check the bin switch for proper adjustment by swinging...

Page 12: ...the brass thermal well for 3 4 minutes It is imperative that enough ice be used for the 4 Slowly turn the adjustment screw counter clockwise until the machine shuts off If the screw is turned too qui...

Page 13: ...n 2 Check ice bridge thickness 3 Check water level in trough 4 Clean the condenser air cooled machines to insure unobstructed air flow 5 Check for leaks of any kind Water Refrigerant Oil Etc 6 Check t...

Page 14: ...move the splash curtain and inspect the evaporator and water spillway to ensure all mineral residue has been removed 8 If necessary wipe the evaporator spillway and other water transport surfaces with...

Page 15: ...urface of stainless steel that protects it from corrosion 3 Don t use cleaners that use chlorine or chlorides Don t use chlorine bleach or products like Comet to clean the steel Chlorides break down t...

Page 16: ...rvest or wait for cycle completion 3 Place the ICE OFF WASH switch to the OFF position The switch is located in the control box 4 Disconnect the tubing between the water pump discharge and water distr...

Page 17: ...Service History Model Number Serial Number Date Installed...

Page 18: ...d Under This Warranty SUPERA LLC s sole obligation under this warranty is limited to either repair or replacement of parts subject to the additional limitations below This warranty neither assumes nor...

Page 19: ...Supera Customer Care Toll Free Service Line 1 866 953 3288 For additional product and warranty information please visit our website at www SuperaCo com...

Reviews: