background image

 

7

If  remote  sensing  is  desired,  move  the  wire  connected 
to  terminal  6  to  terminal  7  and  the  wire  connected  to 
terminal  8  to terminal  9  on  the  control module terminal 
panel.  This  will  disconnect  the  control  module  sense 
terminals  from  the  output  terminals  of  the  regulator. 
Connect  remote  sensing  wires  to  terminals  6  and  8  on 
the control modules. 
 

6.0. 

OPTIONS

 

 

6.1.  NON DESIGNATED OPTIONS 

 

6.1.1. 

Auxiliary Power Modules

 (A2) 

These modules are provided on units  where a  120 volt 
AC  source  is  required  to  operate  internal  circuitry. The 
output voltage of these modules is on terminals 1 and 2 
of  the  terminal  strip.  If  there  is  no  output  on  these 
terminals  check  the  two  fuses  mounted  on  the  same 
bracket. The output of the auxiliary power modules are 
used  to  operate  fans,  trip  or  hold  on  circuit  breakers, 
and  on  any  other  applications  where  120  volts  is 
required. 
 

6.1.2. 

Fans

 (B2) 

On  larger  units  fans  are  provided  to  help  efficiently 
remove  heat  generated  in  the  cabinet.  An  auxiliary 
power module supplies the fan operating voltage. If the 
fans  do  not  operate  insure  the  auxiliary  power  module 
output voltage is present. 
 

6.2. 

MODEL NUMBER SPECIFIED OPTIONS 

 

6.2.1. 

Circuit Breaker

 (CB1) 

An  input  circuit  breaker  provides  short  circuit  and 
overload  protection  for  the  CRA  Series  Power 
Conditioners.  Industrial  circuit  breakers  with  high 
interrupting  capacity  are  used.  These  breakers  also 
serve as an on/off switch for the regulator and any load 
attached. 
 

6.2.1.1.  Shunt Trip

 

In units where the model number designates the circuit 
breaker  as  “CS”  the  circuit  breaker  is  equipped  with  a 
shunt trip. A shunt trip causes the breaker to open when 
voltage  is  applied  to  the  shunt  trip  coil.  The  trip  coil  is 
rated  120  volt,  AC  and  is  de-energized  when  the 
breaker opens. 
 
When  alarm  contact  options  and  a  circuit  breaker  trip 
option  are  ordered  together,  the  unit  is  furnished  with 
120 volt AC, auxiliary power module (A2) and the alarm 
circuit  contacts  are  wired  to  trip  the  input  breaker. The 
Shunt  Trip  Connections  Diagram  shows  the  typical 
connections. 
 
If you do not want the alarm contacts to trip the input 
breaker, the unit can easily be re-configured to not trip 
the breaker and to perform other control functions. The 
120 volts supplied by the auxiliary power module to trip 
the shunt coil can be replaced by an external source if 
desired, but do not disconnect any other devices from 

this source. A momentary push button switch (S4) is 
provided to disable any alarm contacts from activating 
the trip coil. This allows turn on of the system so alarm 
options can reset. Hold switch in while turning on the 
circuit breaker. 
 
 

Shunt Trip Connections Diagram 

 

6.2.2. 

Manual Bypass Switch

 (S3)

 

A two-position, non-load break, manual bypass switch 
provides a nominal output voltage in the even of an 
internal component failure. In the "REGULATOR" 
position, the units regulating and transient suppression 
components are active providing a conditioned output. 
In the "BYPASS" position the regulating variable 
transformer, motor power and transient suppression 
circuits are disconnected from the isolation transformer. 
The input power is connected to the nominal input tap 
on the isolation transformer’s primary. This provides 
nominal isolated voltage to the load. The neutral or 
second input line, having no control components in 
series, is not switched. The circuit breaker and isolation 
transformer remain in line regardless of the bypass 
switch position, since they are always needed. The 
control unit’s voltmeter will continue to show the output 
voltage, as long as the range switch is not in the off 
position, but no correction is performed. 
 

6.2.3. 

Ammeters

 (M1) 

An  analog  ammeter  displays  load  current  for  each 
phase. Each meter indicates the load current within 2% 
of the meters full range. 
 
 

Summary of Contents for STABILINE CRA141S010

Page 1: ...to make engineering changes on all its products Such refinements may affect information given in the instructions Therefore USE ONLY THE INSTRUCTIONS THAT ARE PACKED WITH THE PRODUCT WARNING High volt...

Page 2: ...2...

Page 3: ...r damaged 2 0 DESCRIPTION 2 1 GENERAL CRA141S Series STABILINE Power Conditioners are fast acting fully isolated power conditioners that provide filtered and regulated power for sensitive loads These...

Page 4: ...k KVA Rated for Non Boost H KVA Rated for Boost mode S Single Control D Double Control T Triple Control NNN Load KVA Rating CB Input Circuit Breaker with no trip coil CS Input Circuit Breaker with 120...

Page 5: ...e accessible through the front panels A 3 foot 1000 mm area in front of the unit should be kept clear for installation and service 3 3 ELECTRICAL INSTALLATION All CRA Series Power Conditioners are des...

Page 6: ...refore set how much the output voltage will change before the unit will correct The accuracy is increase with clockwise rotation of the SENSITIVITY potentiometer 5 1 8 Fuses A1 F1 to A1 F4 The four fu...

Page 7: ...ns and a circuit breaker trip option are ordered together the unit is furnished with 120 volt AC auxiliary power module A2 and the alarm circuit contacts are wired to trip the input breaker The Shunt...

Page 8: ...ed factory setting The stored factory settings are shown in the table below To return stored setting to the factory default tap the ENTER key to go to the next feature then use SET and ADVANCE keys to...

Page 9: ...service electrical equipment should perform trouble shooting procedures on this unit If the conditioner fails to operate correctly the following checks will help locate and correct the problem Refer...

Page 10: ...igns of wear or damage The brush assemblies on the variable transformer section will not need replacement under normal conditions When excessive brush wear or commutator damage occurs it is usually th...

Page 11: ...11 9 0 RATING 9 1 POWER RATINGS INPUT VOLTAGE 480 VOLTS FREQUENCY 60 Hz CONNECTION 1 Phase 2 Wire plus safety ground RANGE 20 10 OUTPUT VOLTAGE 120 VOLTS CURRENT 84 Amps Max CONNECTION 1 Phase 2 Wire...

Page 12: ...mperature Operating Average ambient temperature for any 24 hour period not to exceed 30 C 86 F and maximum temperature not to exceed 40 C 104 F Average ambient temperature for any 24 hour period may b...

Page 13: ...ion Part Number A1 CONTROL MODULE 213243 010 A1 A1 CONTROL BOARD 227412 001 A1 F1 F2 F3 F4 FUSE 1A 600V 213274 001 A1 LP1 LP2 LIGHT INDICATOR GREEN 227571 001 A1 M1 VOLTMETER 212917 001 A1 S1 SWITCH R...

Page 14: ...14 11 0 SCHEMATIC For reference only use full size supplied with unit...

Page 15: ...15 12 0 FLOOR MOUNT DIMENSIONS Enclosures A through G Note All dimensions are inches millimeters...

Page 16: ...16 Enclosures A through G continues Note All dimensions are inches millimeters...

Page 17: ...17 Enclosures A through G continues Note All dimensions are inches millimeters...

Page 18: ...ffer literature technical assistance and a select range of models off the shelf for fastest possible delivery and service In addition Superior Electric Manufacturer s Representatives are available to...

Reviews: