Installation
900079-02J, 05/2019
Innovative Hearth Products
DRL3000 Linear Direct-Vent Gas Fireplaces
24
Clearance to combustibles
Maintain the minimum clearance to combustibles (e.g., framing, attic, ceiling insulation, etc.).
For all vertical runs:
• 1” (26 mm) from all sides
NOTE:
Attic insulation shield (H3907) must be installed when blown or loose-fill insulation is used, and is
recommended for all attic installations.
For all horizontal/inclined runs:
• 3” (77 mm) from the top
• 1” (26 mm) from the sides
• 1” (26 mm) from the bottom
7.
Install the Vent System
Install the Vertical Termination Vent System
These instructions should be used as a guideline and do not supersede local codes in any way. Install venting with
the most restrictive requirements as outlined in these instructions, local codes, these instructions, the current
National Fuel Gas Code (ANSI-Z223.1) in the USA or the current standards of CAN/CGA-B149.1 in Canada.
Ensure clearances are in accordance with local installation codes and the requirements of the gas supplier.
Dégagement conforme aux codes d’installa tion locaux et aux exigences du foumisseunde gaz.
Vertical vent systems terminate through the roof. The minimum vent height above the roof and/or adjacent walls
is specified in ANSI Z223.1 (In Canada, the current CAN/CGA-B149.1 installation code) by major building codes.
Always consult your local codes for specific requirements. A general guide to follow is the gas vent rule
(
Table 6
)
.
The following figures and their associated vertical vent tables illustrate the various configurations that are possible
for use with these fireplaces. Secure Vent
®
pipe is shown in these figures; Secure Flex
®
pipe may also be used.
A table summarizes each configuration’s minimum and maximum vertical and horizontal length parameters for a
variety of applications.
1.
Refer to
Figures 17 and 22
,
Tables 19
, and
20
on
Pages 27-28
to select the type of vertical installation desired.
Elbows are available in 90° and 45° configurations. Refer to
Figure 16
on
Page 22
for the SV4.5E45 and
SV4.5E90 elbow dimensional specifications.
Vertical (Straight) Installation
1. Determine the number of straight vent sections required
—See
Effective Vent Length on
Pages 22-23
for more
information. Plan the vent lengths so that a joint does not occur at the intersection of ceiling or roof joists.
Figure 17 - Vertical (Straight) Installation
Vertical
firestop/spacer
See
Table 8
Secure Vent
®
vent sections
Max. 60 ft
(18 m)
Min. 6 ft
(1.8 m)
Vertical termination
Flashing and
storm collar