Installation
900079-02J, 05/2019
Innovative Hearth Products
DRL3000 Linear Direct-Vent Gas Fireplaces
30
6. Install the firestop/spacer at the ceiling
—When using Secure Vent
®
, use SV4.5VF firestop/spacer at ceiling
joists; when using Secure Flex
®
, use SF4.5VF firestop/spacer. If there is living space above the ceiling level,
the firestop/ spacer must be installed on the bottom side of the ceiling. If attic space is above the ceiling, the
firestop/spacer must be installed on the top side of the joist. Route the vent sections through the framed opening
and secure the firestop/spacer with 8d nails or other appropriate fasteners at each corner.
Maintain 1” (26 mm) clearance to combustibles, framing members, and attic or ceiling insulation when running
vertical chimney sections.
NOTE:
Attic insulation shield (H3907) must be installed when blown or loose-fill insulation is used, and is
recommended for all attic installations.
7. Support the vertical run sections
—On the vertical run, support the venting system every 8 ft (2.4 m) above the
fireplace vent outlet with field provided support straps (Plumber’s tape). Attach the straps to the vent pipe and
secure to the framing members with nails or screws
(
Figure 23
)
.
NOTE:
Proper venting support is very important. Never use the fireplace to support the weight of the venting.
8. Change vent direction
—At transition from or to a horizontal/inclined run, install SV4.5E45 or SV4.5E90 elbows
in the same manner as the straight vent sections. The elbows feature a twist section to allow them to be routed
about the center axis of their initial collar section to align with the required direction of the next vent run element.
Twist elbow sections in a clockwise direction only so as to avoid the possibility of unlocking any of the previously
connected vent sections
(
Figure 16
)
.
9. Continue installation of horizontal/inclined sections
—Continue with the installation of the straight vent
sections in horizontal/inclined run. Install support straps every 5 ft. (1.52 m) along horizontal/inclined vent runs
using conventional plumber’s tape in a direction away from the fireplace or catalog number 96K93
(
Figure 23
)
.
Maintain the horizontal/inclined run in a straight (no dips), slightly elevated plane. The recommended incline is
approximately 1/4” per 1 ft (20 mm per 1 m) horizontal, in a direction away from the fireplace. Smaller rise per
foot run ratios are acceptable all the way to at or near level. Use a carpenter’s level to measure from a constant
surface and adjust the support straps as necessary.
Maintain the required clearances to combustibles
(
Page 34
)
.
10. Assemble the vent run to the exterior wall
—If not previously measured, locate the center of the vent at the
exterior wall. Prepare the opening. Assemble the vent system until the terminus of the last section is within 5”
(127 mm) to 8-1/2” (216 mm) inboard of the exterior surface to which the termination is to be attached
(
Figure
24
)
. If the terminus of the last section is not within this distance, use the telescopic vent section SV4.5LA, as the
last vent section.
Table 21
lists the additional venting components needed (in addition to the termination and
adaptor) for a range of wall thicknesses.
11. Attach the termination adaptor
—Attach the adaptor (SV4.5RCH, provided with the termination) to the vent
section or telescoping vent section, elbow or fireplace collar
(
Figure 24
)
.
NOTE:
If blown insulation is to be used, the through-wall shield kit (H5816) MUST be installed.
12. Install the firestop/spacer at the exterior wall
—Install SV4.5HF (Secure Vent
®
), SF4.5HF (Secure Flex
®
)
firestop/spacer over the opening at the exterior side of the framing, long side up, with the 3” spacer clearance at
the top
(
Figure 24
)
and nail into place.
NOTE:
The firestop/spacer may also be installed over the opening at the interior side of the framing.
13. Install the termination (
SV4.5HT-2 and SV4.5HTSS (42” models only)
)
—From outside the exterior wall,
slide the collars of the termination onto the adaptor (the outer over the outer and the inner inside the inner)
until the termination seats against the exterior wall surface to which it will be attached. Orient the housing of
the termination with the arrow pointed upwards. Secure the termination to the exterior wall. The horizontal
termination must not be recessed into the exterior wall or siding by more than the 1-1/4” (32 mm)
(
Figure 25
)
.
NOTE:
If the venting exits the building below grade, or close to grade, see
Installation Accessories on
Page 48
for available snorkel terminations. The termination must be above grade and above the expected level of
snow accumulation.
NOTE:
The vent termination is hot while in operation and for a period of time following the use of the fireplace. To
prevent contact with hot surfaces, use a horizontal termination guard; available for purchase at your local dealer.
The horizontal terminations have been designed to perform in a wide range of weather conditions. They meet or
exceed industry standards.
When selecting the locations of your horizontal terminations,
do not place the termination where water from
eaves and adjoining rooflines may create a heavy flow of cascading water onto the termination cap
. If the cap
must be placed where the possibility of cascading water exists, it is the responsibility of the builder to direct the
water away from the termination cap by using gutters or other means.
Carefully follow the installation instructions for the termination, including the use of silicone caulking where
required.