background image

Installation 

900079-02J, 05/2019

Innovative Hearth Products
DRL3000 Linear Direct-Vent Gas Fireplaces

47

INSTALLATION ACCESSORIES

Listed Secure Vent

®

 Components

Catalog Number

Model

Description

H1968

SV4.5HT-2

Horizontal Square 

Termination with 

Firestop/Spacer 

(H2246), and 

Adaptor (74L61)

94L10

SV4.5HTSS

Rigid, Horizontal, 

Small Square 

Termination with 

Firestop/Spacer 

(H2246) and 

Adaptor (74L61) 

(see 750204M)

H5817

SV4.5-20SSWSK

Rigid, Horizontal, 

Small Square 

Termination, with 

20” Slip Section*, 

Wall Shield and 

Firestop (see 

750247M & 

750204M)

H2152

SV4.5CGV-1

Vertical Termination 

Cap, High Wind

H8914

SV4.5TK90HT2

Horizontal 

Termination Kit 

HT-2 with 90° 

elbow

H8915

SV4.5TK90SS

Horizontal 

Termination Kit 

Small Square with 

90° elbow

Vent Sections (Rigid)

77L70

SV4.5L6

6” (152 mm) 

77L71

SV4.5L12

12” (305 mm) 

77L72

SV4.5L24

24” (610 mm) 

77L73

SV4.5L36

36” (914 mm) 

77L74

SV4.5L48

48” (1219 mm) 

77L75

SV4.5LA

Telescopic Length 

Slip Section (2–7-

1/2” rigid)

77L76

SV4.5E45

45° Elbow

77L77

SV4.5E90

90° Elbow

Catalog Number

Model

Description

The following flashing comes packaged with a storm collar

77L78

SV4.5F

Flat Roof Flashing

77L79

SV4.5FA

1/12 to 7/12 

Adjustable Flashing

77L80

SV4.5FB

7/12 to 12/12 

Adjustable Flashing

77L81

SV4.5SC6

Storm Collar (6 pack)

H6183

SV4.5HF5

Firestop Spacer, 5”, 

rigid

H6184

SF4.5HF5

Firestop Spacer, 5”, 

flex

H2246

SV4.5HF-10

Firestop/Spacer-

Horizontal, rigid (3-1-1 

spacing),  10 Pack

H2247

SV4.5VF-10

Firestop/Spacer-

Vertical, rigid (1-1-1 

spacing),  10 Pack

96K92

SV4.5SP

Support Plate

17M52

SV4.5HGS-1

Termination Guard, 

Square (1 pack) (see 

750109M)

17M53

SV4.5HGS-12

Termination Guard, 

Horizontal Square (12 

pack) (see 750109M)

87L02

SV4.5HGS

Termination Guard 

for Horizontal Square 

Termination (Deluxe)(1 

pack) (see 750055M)

H5820

SV4.5HTSK

Termination Shroud 

(Guard) for Horizontal 

Square Termination (1 

pack) (see 750246M)

* The 20” slip section can be field cut to desired size (new length must allow a minimum of 

1-3/4” overlap within pipe). Deburr cut edges as necessary.

IMPORTANT NOTE: The installation accessories shown in this section are part 

of the safety agency listing for the product models represented in this manual.

Summary of Contents for DRL3000

Page 1: ...nisseur de gaz depuis un voisin Suivez les instructions du fournisseur Si vous ne pouvez rejoindre le fournisseur de gaz appelez le service des incindies L installationetl entretiendoiventêtreassuréspar un installateur ou un service d entretien qualifié ou par le fournisseur de gaz INSTALLER Leave this manual with the appliance CONSUMER Retain this manual for future reference Installateur Laissez ...

Page 2: ...L VIDRIO CALIENTE CAUSARÁ QUEMADURAS USTED NUNCA DEBE TOCAR EL VIDRIO CALIENTE LOS NIÑOS NUNCA DEBE TOCAR EL VIDRIO L écran pare étincelles fourni avec ce foyer réduit le risque de brûlure en cas de contact accidentel avec la vitre chaude et doit être installé pour la protection Des enfants et Des personnes à risques Vea el volante adjunto para la representación de color adecuado See attached colo...

Page 3: ...aduras graves si se toca Mantenga a los niños alejados de la chimenea en funcionamiento Supervise en forma cercana a los niños en cualquier cuarto donde haya una chimenea funcionando para impedir el contacto con el vidrio Mantenga la ropa mobiliario gasolina y otros líquidos inflamables alejados de la chimenea Aún después de haber apagado el gas las superficies de la chimenea permanecen extremadam...

Page 4: ...nt subir des brûlures s ils viennent en contact avec la surface chaude Il est recommandé d installer une barrière physique si des personnes à risques habitent la maison Pour empêcher l accès à un foyer ou à un poêle installez une barrière de sécurité cette mesure empêchera les tout petits les jeunes enfants et toute autre personne à ris que d avoir accès à la pièce et aux surfaces chaudes 7 Tout é...

Page 5: ...ation 12 Vent Termination Clearances 13 Minimum Clearances to Combustibles 15 Wall Finishes Surrounds Mantels 16 Installation Preparation 16 Installation Installation Sequence 17 Construct the Fireplace Framing 17 Prepare the Fireplace Top Spacers 19 Route the Gas Supply Line into the Fireplace 19 Vent System Preparation 20 Install the Vent System 24 Complete the Field Wiring 35 Connect the Gas Li...

Page 6: ...s operating controls is dangerous Improper installation or use of this appliance can cause serious injury or death from fire burns explosion or carbon monoxide poisoning CARBON MONOXIDE POISONING Early signs of carbon monoxide poisoning are similar to the flu with headaches dizziness and or nausea If you have these signs obtain fresh air immediately Turn off the gas supply to the appliance and hav...

Page 7: ...ided will result in an improperly installed and operating appliance voiding its warranty Do not attempt to alter or modify the construction of the appliance or its components Any modification or alteration may void the warranty certification and listings of this unit CAUTION Hot while in operation Do not touch Severe Burns may result Keep children clothing furniture gasoline and other liquids havi...

Page 8: ...ectronic fireplaces are designed with an electronic intermittent pilot ignition system Electrical power 110 Vac line voltage is recommended to operate the fireplace however AA batteries not provided can be used for full time operation or as a backup in case of a power outage Batteries will operate the flame ON OFF function only Electrical power is required to operate the optional blower A remote c...

Page 9: ...are listed for installation in bedrooms aftermarket mobile homes and manufactured homes The installation must conform to local codes or in the absence of local codes with the National Fuel Gas Code ANSI Z223 1 NFPA 54 latest edition or the Natural Gas and Propane Installation Code CAN CGA B149 1 The fireplace when installed must be electrically grounded and wired in accordance with local codes or ...

Page 10: ...l cause damage to valve components Verify that the tanks have step down regulators to reduce the pressure to safe levels Using a propane tank smaller than 100 lbs may create pressure loss and insufficient fuel delivery which can cause sooting severe delayed ignition or other malfunctions see NPFA 58 Any damage as a result of insufficient tank size or other improper installation is NOT covered unde...

Page 11: ...llation and repair must be done by a plumber or gas fitter licensed in the Commonwealth of Massachusetts The flexible gas line connector used shall not exceed 36 914 mm in length The individual manual shutoff must be a T handle type valve Massachusetts Horizontal Vent Requirements In the Commonwealth of Massachusetts horizontal terminations installed less than seven 7 ft above the finished grade m...

Page 12: ...e location the aesthetic and functional use of the fireplace are primary concerns However vent system routing to the exterior and access to the fuel supply are also important The fireplace may be located on or near conventional construction materials See Construct the Fireplace Framing on Page 17 for more information Due to high temperatures the fireplace should be located out of traffic and away ...

Page 13: ...t 1 83 m 16 12 to 18 12 7 0 ft 2 13 m 18 12 to 20 12 7 5 ft 2 29 m 20 12 to 21 12 8 0 ft 2 44 m 12 X Roof pitch is X 12 2 ft minimum 2 ft minimum Lowest discharge opening H H minimum height from roof to lowest discharge opening of vent Horizontal overhang Vertical wall Vent termination Storm collar Concentric vent pipe Flashing 1 26 mm minimum clearance to combustibles Horizontal Vent Termination ...

Page 14: ... minimum G Clearance to inside corner 2 51 mm minimum 2 51 mm minimum H Clearance to each inside of center line extended above meter regulator assembly 36 910 mm within a height of 15 ft above the meter regulator assembly 36 910 mm within a height of 15 ft above the meter regulator assembly I Clearance to service regulator vent outlet 36 910 mm 36 910 mm J Clearance to nonmechanical air supply inl...

Page 15: ...ide of the unit and any screw heads adjacent to it Hearth Extension A hearth extension is not required with this fireplace Any hearth extension used is for appearance only and does not have to conform to standard hearth extension installation requirements Shelf Height The venting attached to the top vent should be routed in a way to minimize obstructions to the space above the fireplace Do not ins...

Page 16: ...ea Safe Zone Combustible walls shown in dark gray Combustible mantel legs may project beyond either side of the fireplace opening as long as they are kept within the shaded area illustrated here At 8 1 4 side wall clearance a combustible wall can project 12 5 127 mm At 14 minimum side wall clearance a combustible wall can project to any length 12 305 mm 17 431 mm 14 356 mm 12 305 10 254 8 203 6 15...

Page 17: ... Remote Control System Page 45 14 Verify Proper Fireplace Operation Page 38 Finishing 15 Install the Glass Media Page 57 16 Install the Baffle Page 39 17 Install the Glass Door and Barrier Page 58 18 Adjust the Air Shutter to Ensure Proper Flame Appearance Page 39 19 Install the Finishing Materials Page 41 20 Attach the Safety in Operation Warning Labels Page 45 1 Construct the Fireplace Framing 1...

Page 18: ...sh with surrounding finish material see for dimensions Table 10 Fireplace Framing Dimensions Inches millimeters Model A B C D E F 42 57 1448 21 534 37 940 44 3 8 1127 35 5 8 905 65 1651 54 69 1753 21 534 40 7 8 1039 48 1 4 1226 39 1 2 1004 65 1651 with 1 2 recess for flush framing Top Jack Stud Header positioned horizontally see Pages 41 42 NOTE Illustration provided for dimensions Fireplace must ...

Page 19: ...formation on Accessing the Control Compartment NOTE If gas shutoff valve on the fireplace is desired surround kit must be used Refer the gas line routing included in the surround instructions NOTE All codes require a shutoff valve mounted in the supply line Figure 31 Page 38 illustrates the method for connecting the gas supply The flex line method is acceptable in the U S however Canadian requirem...

Page 20: ...may not service multiple appliances and must never be connected to a flue serving a separate solid fuel burning appliance NOTE The vent pipe is tested to be run inside an enclosed wall such as a chase There is no requirement for inspection openings in the enclosing wall at any of the joints in the vent pipe 6 Install the Vent Restrictor if necessary 1 Use the vent run descriptions in Figure 11 to ...

Page 21: ...oof and using the vent restrictor install the vent restrictor in the top vent of the fireplace outlet If installing more than 6 ft of vertical venting install the restrictor Figure 12 from inside or outside the unit in the inner fireplace collar The vent restrictor is held in place by friction Vent Restrictor with Horizontal Terminations When horizontally terminating a vent system with a vertical ...

Page 22: ...14 Connecting vent components Figure 15 Connected vent components Figure 16 Elbow Dimensions Dimple Locking Incline Channel Arrow Appliance Collar or Vent Section Dimple Locking Incline Channel Arrow SV4 5E90 90 Elbow 8 1 8 in 206 mm Swivel Joint 360 swivel 4 13 16 in 122 mm SV4 5E45 45 Elbow Swivel Joint 360 swivel 4 13 16 122 mm 8 1 8 206 mm Swivel Joint 360 Swivel Joint 360 SV4 5E45 45 elbow SV...

Page 23: ...10 12 79 5 6 625 0 1 0 2 0 3 492 41 1 0 1 0 10 12 81 6 75 0 0 0 1 1 2 499 5 41 625 0 0 0 1 10 11 91 5 7 625 0 0 2 0 1 3 504 42 1 0 0 1 10 12 93 7 75 0 0 0 0 2 2 511 5 42 625 0 0 0 0 11 11 97 5 8 125 1 0 0 0 2 3 520 5 43 375 0 2 0 1 11 14 103 5 8 625 0 0 0 3 0 3 531 44 25 0 2 2 0 11 15 108 9 1 0 0 3 0 4 538 5 44 875 1 0 0 2 11 14 117 9 75 1 0 5 0 0 6 549 45 75 1 0 2 1 11 15 118 5 9 875 1 1 0 3 0 5 ...

Page 24: ...ugh the roof The minimum vent height above the roof and or adjacent walls is specified in ANSI Z223 1 In Canada the current CAN CGA B149 1 installation code by major building codes Always consult your local codes for specific requirements A general guide to follow is the gas vent rule Table 6 The following figures and their associated vertical vent tables illustrate the various configurations that...

Page 25: ...op spacer If there is living space above the ceiling level the firestop spacer must be installed on the bottom side of the ceiling If attic space is above the ceiling the firestop spacer must be installed on the top side of the joist Route the vent sections through the framed opening and secure the firestop spacer with 8d nails or other appropriate fasteners at each corner Remember to maintain 1 2...

Page 26: ...ent sections through the roof structure Install the roof flashing over the vent section and position such that the vent column rises vertically use carpenters level Nail along perimeter to secure flashing or adjust roofing to overlap the flashing edges at top and sides only and trim where necessary Seal the top and both sides of the flashing with waterproof caulking The flashing must overlap the r...

Page 27: ...same rise to run ratios as shown in the venting figures for 90 elbows must be followed if 45 elbows are used NOTE An elbow is acceptable as 1 ft of vertical rise except where an elbow is the only vertical component in the system WARNING Do NOT join separate sections of concentric flexible vent pipe Figure 22 Top Vent Straight Vertical Firestop Spacer u See Clearance to combustibles on Page 24 Secu...

Page 28: ...top spacer must be used anywhere vent pipe passes through a combustible floor or ceiling Horizontal firestop spacer must be used anywhere vent pipe passes through a combustible wall Install the provided vent restrictor if required A 90 elbow may NOT be attached directly to the appliance collar A minimum 6 pipe section must be used between the fireplace collar and a 90 elbow Total H Max 20 ft 6 096...

Page 29: ... vertical venting every 8 ft 2 4 m above fireplace vent outlet Horizontal inclined run Place horizontal support brackets every 5 ft 1 524 m Fireplace Straight vent sections Horizontal firestop spacer u Horizontal termination Figure 23 Typical Horizontal Vent Installation 1 Analyze the vent route and determine the number of vent sections and elbows required See Effective Vent Length on Pages 22 23 ...

Page 30: ... If not previously measured locate the center of the vent at the exterior wall Prepare the opening Assemble the vent system until the terminus of the last section is within 5 127 mm to 8 1 2 216 mm inboard of the exterior surface to which the termination is to be attached Figure 24 If the terminus of the last section is not within this distance use the telescopic vent section SV4 5LA as the last v...

Page 31: ...tal Termination Venting Connection and Exterior Wall Recessing Use silicone caulk to seal the top and sides of the termination up to the underlayment stucco or masonry wall surface Caulk Typical Horizontal Termination Caulk For thicknesses greater than 9 1 4 235 mm see Table 21 Firestop Spacer SV4 5HF shown on the exterior side of the wall It may also be installed on the interior side Typical Term...

Page 32: ...er must be used any time vent pipe passes through a combustible floor or ceiling SV4 5HF Secure Vent SF4 5HF Secure Flex firestop spacer must be used any time vent pipe passes through a combustible wall WARNING Do not join separate sections of concentric flexible vent together Table 22 Top Vent One 90 Elbow Maximum total H Minimum total V feet meters feet meters 2 0 610 1 0 305 4 5 1 372 3 0 914 6...

Page 33: ...section must be used between the fireplace collar and a 90 elbow V H H1 Horizontal Termination Vertical Firestop Spacer u Horizontal Firestop Spacer u Table 24 Top Vent Three 90 Elbows Maximum total H Minimum total V feet meters feet meters 2 0 610 1 0 305 4 5 1 372 3 0 914 6 1 829 4 1 220 7 5 2 286 5 1 524 9 2 743 6 1 729 15 4 572 10 3 048 Total H 15 ft 4 572 m maximum Total H Total V 60 ft 18 3 ...

Page 34: ...nner flex vent over the adaptor collar at least 1 3 4 NOTE Ensure the flex vent is free from damage or tears e Slide the gear clamp down and tighten it fully to secure the flexible vent to the adaptor inner collar approximately 3 4 from the end of the flex f Install three 3 sheet metal screws 120 apart through the flexible vent and into the adaptor collar just below the gear clamp to provide addit...

Page 35: ...e Flex termination and adaptor collars are a different circumference than Secure Vent collars Secure Flex vent has a longer center tube to improve ease of installation 8 Complete the Field Wiring CAUTION The ground supply lead must be connected to the wire attached to the green ground screw located on the outlet box see wiring diagrams Failure to do so will result in a potential safety hazard The ...

Page 36: ...ASSEMBLY B BLACK BR BROWN GY GRAY PU PURPLE R RED BL BLUE G GREEN O ORANGE W WHITE Y YELLOW WIRING COLOR CODE B B B R R W W B B B B BL BL G G O Y Y R R Y W G G O SCHEMATIC REPRESENTATION ONLY 2 Remove the electrical inlet cover plate from the side of the unit by removing the plate securing screws 3 Remove the cover plate knockout then feed the power supply wire through the knockout opening and int...

Page 37: ...e 58 3 The battery holder is attached via cable to the CPI IPI bracket on the left hand side Figure 50 Pull the cable until the battery holder is visible Turn the battery holder such that it will clear the unit and can be removed from the unit the black and red wires will still be connected to the unit 4 Place the four 4 provided AA batteries into the holder Align the end of the batteries the the ...

Page 38: ... prevent moisture and debris in the gas line from damaging the valve Test Factory and Field Connections for Gas Leaks WARNING Never use an open flame to check for leaks Turn on gas supply and test for gas leaks using a gas leak test solution also known as bubble leak solution NOTE Using a soapy water solution is an effective leak test solution but it is not recommended because the soap residue tha...

Page 39: ...h Any damage due to sooting resulting from improperly setting the air shutter is not covered under the warranty The air shutter door and nearby appliance surfaces are hot Exercise caution to avoid injury while adjusting flame appearance Flame Appearance and Sooting The flame should be blue at the base and yellow orange in the body of the flame When the fireplace is first lit the entire flame may b...

Page 40: ...tment Amount of Primary Air Flame Color Air Shutter Adjustment If air shutter is closed too far Flame will be orange Air shutter gap should be increased PULL lever toward front of fireplace If air shutter is open too far Flame will be blue Air shutter gap should be decreased PUSH lever toward back of fireplace Air shutter adjustment lever below glass door 1 Move the adjustment lever Figure 34 down...

Page 41: ...t top non combustible board with the 3 middle holes at the bottom and conter sink holes facing out and reinstall the three 3 screws using the countersink holes in the board Fasten the board to the side jack studs with one 1 screw on each side using the center holes in the board Using 100 silicone applying the silicone with small Hershey kisses spaced out evenly on the first non combustible board A...

Page 42: ...tion 900079 02J 05 2019 Innovative Hearth Products DRL3000 Linear Direct Vent Gas Fireplaces 42 Framing Diagrams 1 through 7 see Instruction 2 Page 41 1 2 3 4 5 6 7 Side and top horizontally mounted jack studs ...

Page 43: ...Noncombustible Material with Cleanface Finish Profile View Figure 39 Noncombustible Material with Surround Profile View For surround finish cut top fiberboard to height of installed top spacers Combustible material NOT ALLOWED BELOW THIS POINT on face of unit Wall Stud Insulation and combustible material NOT ALLOWED in shaded clearance zones around vent components Combustible wall finish material ...

Page 44: ...mbustible fiberboard may be faced with any NON combustible finish material appropriate for use brick tile stone high temperature paint etc For painted wall finish use two 2 coats of quality primer and high temperature paint on provided fiberboard 4 Secure nailing flanges to wall framing NOTE If skimming the non combustible board to match drywall use Sheetrock brand Durabond 90 setting type joint c...

Page 45: ... the 4 provided AA batteries into the receiver battery bay Figure 43 Correctly align polarity Burner ON OFF Figure 43 Remote and Wall Receiver Battery Compartments Figure 44 Remote Control Transmitter 20 Attach the Safety in Operation Warning Labels 1 Attach the furnished safety instruction labels at all fireplace operation and control points Page 46 NOTE The installer MUST ensure these warnings a...

Page 46: ... du foyer en le faisant basculerdeMarcheàArrêt etvice versa Nettoyez soigneusement la plaque murale de l interrupteur ou le thermostat mural pour éliminer la poussière et les traces de graisse ou d huile Collez l étiquette sur la surface de la plaque de l interrupteur mural qui contrôle le foyer Figure A ou du thermostat mural Figure B Choisissez la langue qui est principalement parlée dans la rés...

Page 47: ...77L77 SV4 5E90 90 Elbow Catalog Number Model Description The following flashing comes packaged with a storm collar 77L78 SV4 5F Flat Roof Flashing 77L79 SV4 5FA 1 12 to 7 12 Adjustable Flashing 77L80 SV4 5FB 7 12 to 12 12 Adjustable Flashing 77L81 SV4 5SC6 Storm Collar 6 pack H6183 SV4 5HF5 Firestop Spacer 5 rigid H6184 SF4 5HF5 Firestop Spacer 5 flex H2246 SV4 5HF 10 Firestop Spacer Horizontal ri...

Page 48: ... 7 5 191 mm for flex 6 pack F3191 SV4 5AdaptorKit Secure Flex Adaptor Kit Includes rigid to flex adaptor and flex to rigid adaptor flex not included Catalog Number Model Description 94L04 SFKIT12SS Small Square Termination for flex with 12 305 mm of compressed flex vent see 750204M 94L05 SFKIT18SS Small Square Termination for flex with 18 457 mm of compressed flex vent see 750204M 94L06 SFKIT24SS ...

Page 49: ...es dommages matériels des blessures ou la mort Le tecnicien agréé est responsable de l installation de cette trousse L installation n est pas adéquate ni complète tant que le bon fonctionnement de l appareil converti n a pas été vérifié selon les instructions du fabricant fournies avec la trousse Le fournisseur de service qualifié ayant réalisé l installation assume les responsabilités liées à la ...

Page 50: ...ure 45 7 Remove the control compartment access door and gasket Figure 49 Figure 45 Removing the Burner and Accessing the Control Compartment Figure 46 Removing the Air Shutter Adjustment Rod Control Compartment Access Panel and Gasket Right Burner Bracket Remove two screws to remove burner assembly Burner Assembly Right Burner Bracket Venturi Burner Orifice Air Shutter Adjustment Rod 8 Refer to th...

Page 51: ...Ensure the air shutter clears the pilot bracket 18 Turn ON the gas supply to the fireplace and relight the appliance Page 65 With the main burner ON use a gas leak test solution to test the new pressure regulator assembly and all gas line joints for leaks Page 38 19 Attach the conversion information label to the rating plate 20 Locate the valve test ports Figure 1 Using a manometer test the inlet ...

Page 52: ...spection par un technicien professionnel avant d être utilisé et au moins une fois l an par la suite Des nettoyages plus fréquents peuvent être nécessaires si les tapis la literie et cetera produisent une quantité importante de pous sière Il est essentiel que les compartiments abritant les commandes les brûleurs et les conduits de circulation d air de l appareil soient tenus propres NOTE Do not us...

Page 53: ...opera la chimenea encendiéndola y apagándola Limpiebienlaplacadelinterruptoroeltermostatode paredparaquitarelpolvoyaceite Peguelaetiqueta enlasuperficiedelaplacadelinterruptorquecontrola la chimenea Figura A o en el termostato de pared Figura B Seleccione el idioma que más se habla en la casa 2 Si se usa un control remoto para controlar la chimenea encuentre el transmisor y límpielo bien para quit...

Page 54: ...s not flowing to the pilot and burner the service shutoff valve located in the fireplace control compartment may need to be opened Contact your dealer or distributor for more information To access the service shutoff valve remove the glass door burner floor panels and control compartment access panel in the fireplace floor In units with the surround installed the gas shut off valve is locate below...

Page 55: ...ce the remote control transmitter where children cannot reach it Wall Switch Receiver Low Battery Power Detection Battery life depends on several factors including battery quality and number of fireplace ignitions When the batteries are low or depleted the fireplace can only be operated manually ON OFF When the depleted batteries are replaced the receiver will resume normal operation Remote Contro...

Page 56: ...lot that will help prevent glass door condensation and cycle startup switch to continuous mode NOTE Continuous mode is indicated by a pilot that comes ON and remains lit when the fireplace is OFF Figure 50 Control Compartment ON OFF CPI IPI switch ON standing OFF intermittent Main gas shutoff valve Installing the Firebox Liners NOTE It is not necessary to remove the firebox liner panels for most m...

Page 57: ...eproductionofcarbonmonoxide CO aTOXICgasthatiscolorlessandodorless This appliance is NOT designed to burn wood Any attempt to burn wood in this fireplace may be a safety hazard cause irreparable damage the appliance and void the warranty 1 Install the glass media in the recessed area between the front and rear floors NOTE 42 fireplaces require a full bag of glass media 54 fireplaces require two 2 ...

Page 58: ...manufacturer Do not attempt to replace broken cracked or chipped glass separately Do not attempt to touch the front enclosure glass with your hands while the fireplace is in use WARNING Do not operate appliance with the glass front removed cracked or broken AVERTISSEMENT Ne pas utiliser l appareil si le panneau frontal en verre n est pas en place est craqué ou brisé WARNING Any safety screen guard...

Page 59: ...Proper door alignment and sealing are important to the operation and performance of the fireplace Ensure the door seal is contacting the frame and that no air leaks are present 3 Align the screw holes below the glass door with the holes in the fireplace and secure using the three 3 provided screws Figure 52 4 For cleanface installations install the modesty panel 5 Install barrier Removing the glas...

Page 60: ...g system components However more frequent periodic inspections and cleanings should be performed by the homeowner NOTE Prior to the first use of the fireplace and each burn season and periodically during the burn season inspect the horizontal termination for debris such as bird nests leaves paper or branches Remove any items from the surfaces of the termination prior to use Also be aware of shrubs...

Page 61: ...ng the glass media Carefully follow the placement instructions Page 56 This will ensure a proper flame and safe combustion NOTE Improper positioning of media can create carbon build up and will alter the performance of the fireplace Replacing the media If the media needs replacement use only the proper replacement media from manufacturer Page 63 Cleaning the burner Carefully remove the media Vacuu...

Page 62: ...ffle inspect the vent system at the top and at the base within the firebox for signs of blockage or obstruction Look for any signs of dislocation of the vent components Fireplace Inspection Qualified Service Technician Perform the appropriate fireplace inspection procedure detailed in this manual Page 38 Replacing Batteries Homeowner Qualified Services Technician For electronic gas valve models Re...

Page 63: ...ainted surfaces may be accomplished with the touch up paint kit Catalog No Model No Description F3373 Black touch up paint satin firebox interior F1882 SCTPSAB Black touch up paint powder coat exterior Termination Guard Kits The vent termination guards may be used to cover the vent termination on the exterior of the home to minimize exposure to the hot surface of the termination Catalog Model Desc...

Page 64: ... mounted Thermostatic or manual ON OFF operation Connects to wall switch wire H8864 Model WS S TSTAT ON OFF and Timer Control Kits Feature a timed ON OFF mode as well as manual ON OFF operation Cost Effective Solution Catalog Number Manual ON OFF operation Works with millivolt and low voltage electronic ignition controls Kit includes remote and receiver F2236 Model RCKit4001 RC S 1 Manual or up to...

Page 65: ...water Electronic Gas Control Valve SIT Electronic Pilot Assembly 3 Turn off all electric power to the appliance if service is to be performed Note The control may have a battery backup remove batteries if installed 4 Close the main line gas shut off valve 1 STOP Read the safety information above on this label 2 Read the Care and Operation manual including the section on Remote Control System if ap...

Page 66: ...voir une batterie de secours installer les batteries au besoin 8 Placez l interrupteur du récepteur en position REMOTE ou l interrupteur mural en position ON 9 Si applicable Appuyez sur le bouton ON OFF pour sélectionner ON 10 Si applicable Ajustez le thermostat sur la télécommande à l ajustement désiré 11 Si l appareil ne se met pas en marche suivez les instructions intitulées Comment couper l ad...

Page 67: ...of air call a service technician if required e Unit is not receiving power Replace unit battery backup 3 The main Burner comes on but then goes out a Fireplace has not established proper draft Switch CPI IPI switch to pilot ON mode wait two 2 minutes then relight b Gas is not reaching the fireplace Check the gas supply and gas shutoff valves c Loose wires to the valve or ignition module Check cont...

Page 68: ...9189 1 Wall Switch Receiver Kit H8564 1 H8564 1 3 DFC Wire Harness H8601 1 H8601 1 4 Ground Wire H7278 1 H7278 1 5 DFC Ignition Board J7906 1 J7906 1 6 Natural Gas Valve H8562 1 H8562 1 7 Propane Gas Valve H8594 1 H8594 1 8 Natural Gas Pilot Assembly H7268 1 H7268 1 9 Propane Pilot Assembly H7269 1 H7269 1 10 Glass Door Latch H8433 1 H8433 1 Flex Gas Connector Assembly 93L32 1 93L32 1 Orifice Conn...

Page 69: ...placement Parts Homeowner Replacement Parts Description 42 54 Catalog Number Qty Catalog Number Qty Remote Control Transmitter Kit F2236 1 F2236 1 11 Glass Door H8799 1 H8431 1 12 Top Baffle H8787 1 H8583 1 13 Blower Assembly FBK 250 optional 80L86 1 80L86 1 14 Clean Trim Assembly with Barrier J7552 1 J7551 1 15 Barrier J7427 1 J7426 1 WARNING Never use substitute materials Use of non approved par...

Page 70: ...__________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ____...

Page 71: ... natural or propane gas only Burning conventional fuels such as wood coal or any other solid fuel will cause damage to the Product will produce excessive temperatures and could result in a fire hazard c damages caused by failing to provide proper maintenance and service in accordance with the instructions provided with the Product d damages repairs or inefficiency resulting from faulty installatio...

Page 72: ...al number Date fireplace was Installed Type of gas fireplace uses Dealer name Innovative Hearth Products reserves the right to make changes at any time without notice in design materials specifications prices and also to discontinue colors styles and products Consult your local distributor for fireplace code information Printed in U S A 2014 Innovative Hearth Products P N 900079 02 Rev J 05 2019 1...

Reviews: