14
4.5 CURRENT SETTINGS
The proper current setting for each motor is shown on the individual
torque vs. speed curves. Use this current level to obtain the torque
shown. The access hole for the switches which set the motor current
level is located on the back of the unit (see Figure 4.1). Switches 1
through 6 are used to select the current level. Select the desired
operating current by setting the appropriate switch to position 1 (ON).
The OFF position is labeled "0". Only one switch should be ON. If two or
more switches are ON, the one which selects the highest current level
will be the active switch. The switch settings are as follows:
Position
(amperes)
Current
None
1.0
1
2.0
2
3.0
3
4.0*
4
5.0*
5
6.0*
6
7.0*
*Heat sinking is recommended at current settings of 4 amperes or
higher. The drive case temperature MUST NOT exceed 70ºC.
4.6 STEP RESOLUTION
The number of pulses per revolution is selected using positions 7 and 8
of the switch described in Section 4.5. The following chart shows the
correct switch settings for each available step resolution.
Switch Position
Step
Resolution
Pulses Per
Revolution
7
8
MD7
MD7-
128
MD7
MD7-
128
0
0
1/2
Full
400
200
1
0
1/10
1/16
2,000
3200
0
1
1/25
1/64
5,000
12,800
1
1
1/100
1/128
20,000
25,600
Summary of Contents for SLO-SYN SS2000MD7
Page 1: ...INSTALLATION INSTRUCTIONS for SLO SYN MODELS SS2000MD7 SS2000MD7 128 TRANSLATOR DRIVE ...
Page 17: ...17 Suggested Methods For Control Interface Figure 4 2 ...
Page 20: ...20 M062 LE09 MOTOR 3 AMPERES SERIES CONNECTION M062 LE09 MOTOR 6 AMPERES PARALLEL CONNECTION ...
Page 21: ...21 M063 LE09 MOTOR 3 AMPERES SERIES CONNECTION M063 LE09 MOTOR 6 AMPERES PARALLEL CONNECTION ...
Page 25: ...25 ...
Page 26: ...26 ...
Page 27: ...27 ...
Page 28: ...28 ...