16
When this signal is high, motor rotation will be clockwise.
Rotation will be counterclockwise when this signal is low.
Clockwise and counterclockwise directions are properly
oriented when viewing the motor from the end opposite the
mounting flange.
AWO
All Windings Off Input
When this signal is low, AC and DC current to the motor will be
zero.
Caution: There will be no holding torque when the
AWO signal is low.
RDCE
Reduce Current Input
The motor current will be 50% of the selected value when this
signal is low.
Caution: Holding torque will also be reduced
when this signal is low.
NOTE: If you are using the drive with an SS2000I or SS2000I-V
control, the READY input and the OPTO input on the control must
be jumpered together.
4.7.3 Level Requirements
OPTO
Voltage ...................4.5 to 6.0 volts dc
Current ...................16 mA per signal used
Other Signals
Voltage
Low.................. 0.8 Vdc
0.0 Vdc
High ................. OPTO
OPTO - 1 volt
Current
Low.................. 16 mA
High ................. 0.2 mA
4.7.4 Timing Requirements
PULSE
Max. Frequency .....500 kHz
Max. Rise And
Fall Times...............1 microsecond
Min. Pulse Width ....1 microsecond
Other Signals
Response Time ...... 50 microseconds
Summary of Contents for SLO-SYN SS2000MD7
Page 1: ...INSTALLATION INSTRUCTIONS for SLO SYN MODELS SS2000MD7 SS2000MD7 128 TRANSLATOR DRIVE ...
Page 17: ...17 Suggested Methods For Control Interface Figure 4 2 ...
Page 20: ...20 M062 LE09 MOTOR 3 AMPERES SERIES CONNECTION M062 LE09 MOTOR 6 AMPERES PARALLEL CONNECTION ...
Page 21: ...21 M063 LE09 MOTOR 3 AMPERES SERIES CONNECTION M063 LE09 MOTOR 6 AMPERES PARALLEL CONNECTION ...
Page 25: ...25 ...
Page 26: ...26 ...
Page 27: ...27 ...
Page 28: ...28 ...