7.  ERROR CODES

Electronic control fault table

DISPLAY FAILURE DESCRIPTION

REASON

SOLUTION

Non

Standby

Non

Normal boot

P01

Inlet Temp. Sensor Fault

The temp. Sensor is broken or 
short circuit

Check or change the temp. 
Sensor

P02

Outlet Temp.Sensor Fault

The temp. Sensor is broken or 
short circuit

Check or change the temp. 
Sensor

P04

Coil Temp.Sensor Fault

The temp. Sensor is broken or 
short circuit

Check or change the temp. 
Sensor

P05

Amibent Temp.Sensor Fault

The temp. Sensor is broken or 
short circuit

Check or change the temp. 
Sensor

P07

Suction Temp.Sensor Fault

The temp. Sensor is broken or 
short circuit

Check or change the temp. 
Sensor

P081

Discharge Temp. Sensor Fault

The temp. Sensor is broken or 
short circuit

Check or change the temp. 
Sensor

E01

High Pressure Prot.

The high-pressure switch is 
broken

Check the pressure switch and 
cold circuit

E02

Low Pressure Prot.

Low pressure1 protection

Check the pressure switch and 
cold circuit

E03

Flow Switch Prot.

No water/little water in water 
system

Check the pipe water flow and 

water pump

E07

Anti-freezing Prot

Water flow is not enough

Check the pipe water flow 

and whether water system is 
jammed or not

E19

Primary Anti-freezing Prot.

The ambient temp. is low

E29

Secondary Anti-freezing Prot.

The ambient temp. is low

E06

Inlet and outlet temp. too big

Water flow is not enough and 

low differential pressure

Check the pipe water flow 

and whether water system is 
jammed or not

Non

Low temperature protection

The environmental temp. is low

E051

Comp. Overcurrent Prot.

The compressor is overload

Check whether the system 
of the compressor running 
normally

P082

Exhaust Air over Temp Prot.

The compressor is overload

Check whether the system 
of the compressor running 
normally

Heatseeker NovaS Heat Pump 

Installation & User Manual

23

Summary of Contents for Heatseeker NovaS

Page 1: ...HeatseekerVortexE Inverter Heat Pump Installation User Manual 1 INSTALLATION USER MANUAL H E AT S E E K E R...

Page 2: ...me Solar Pty Ltd ABN 88 007 400 213 New South Wales 19 24 Anzac Avenue Smeaton Grange NSW 2567 P 02 4648 4766 solar nsw supremeheating com au Queensland Unit 4 7 9 De Barnett Street Coomera QLD 4209 P...

Page 3: ...tallation and maintenance 13 5 1 Notice before installation 13 5 2 Installation instructions 14 5 3 Trial after installation 21 6 Trouble shooting guide 22 7 Error codes 23 ANCILLARY PRODUCTS 8 NovaSw...

Page 4: ...he following components 1 2 OPERATING CONDITIONS AND RANGE ITEMS RANGE Operating Range Air temperature 7 C 43 C Temperature Setting Heating 9 C 40 C The heat pump will have ideal performance in the op...

Page 5: ...3 1 The heat pump can only be used with pool water It can NEVER be used to heat or cool other flammable or turbid liquid 1 3 2 When moving the heat pump do not lift the water union This will damage th...

Page 6: ...not store or use combustible gas or liquids such as thinners paints or fuels near the heat pump 1 3 6 If you detect any abnormal noises odours smoke or leaks from the heat pump immediately switch off...

Page 7: ...he main power supply switch should be out of the reach of children 1 3 8 Please disconnect the heat pump from the power supply during electrical storms Heatseeker NovaS Heat Pump Installation User Man...

Page 8: ...current operation and return to the last level of operation Up key Used to page up and increase variable value Down key Used to page down and decrease variable value Setting key Used to enter the set...

Page 9: ...ature the light is on Water inlet symbol When the main display area displays the water inlet temperature the light is on Setting symbol When the parameter is adjustable it is on Fault symbol In case o...

Page 10: ...ill return to the main interface without any changes saved If there is no operation for 5 seconds the system will automatically memorise user s setting and return to the main interface 4 Setting of ti...

Page 11: ...ress to set minutes Press or to adjust hours Press or to adjust minutes 7 Keyboard lock To avoid misoperation the controller can be locked after completing the settings Hold for 5 seconds Repeat to un...

Page 12: ...ticide on the surfaces around the unit to prevent ant and insect ingress 2 3 2 Winterizing Sub Zero Climates In climates where the winter season reaches sub zero temperatures please disconnect from po...

Page 13: ...Pool Volume Warm Climate Litres 30 000 40 000 50 000 60 000 Advised Flow Rate L min 53 66 86 100 Inlet Outlet mm 50 Compressor Twin rotary Mitsubishi DC Inverter Heat Exchanger Spiral titanium tube i...

Page 14: ...ng the heat pump please ensure the unit remains in an upright position at all times 4 2 When moving the heat pump do not lift the water union This will damage the titanium heat exchanger Heatseeker No...

Page 15: ...professional Unqualified installations may result in damage to the heat pump and or safety risks to the user 5 1 NOTICE BEFORE INSTALLATION 5 1 1 Plumbing connections must be made with solid PVC pipe...

Page 16: ...5m from and to the heat pump 30m in total unless the ground is wet or the groundwater level is high A rough estimate of the heat loss per 30m is 0 6 kWh 2 000 BTU for every 5 C difference between the...

Page 17: ...system and the heat pump to prevent chemicals returning to the heat pump Failure to observe this instruction will void the warranty Independent System In line System FROM POOL TO POOL 3 WAY VALVE NON...

Page 18: ...Adjusting the Bypass A B HEAT PUMP BACK FILTER FILTER PUMP FROM POOL TO POOL 3 WAY VALVE CHLORINATOR NON RETURN VALVE OUT IN Heatseeker NovaS Heat Pump Installation User Manual 16...

Page 19: ...s Once the message clears the default display is the current water temperature Starting sequence will now begin ATTENTION Bypass Installation Operation without a bypass or with improper bypass adjustm...

Page 20: ...HEATPUMP DIMENSIONS 5 2 2 Heatseeker NovaS 9kW 5 2 3 Heatseeker NovaS 13kW Heatseeker NovaS Heat Pump Installation User Manual 18...

Page 21: ...pump is running condensation will occur and drain from the bottom of the unit This is completely normal However consideration should be made for how to drain the condensation away Drainage nozzle and...

Page 22: ...5 The layout of power cable and signal cable should be orderly and not affect each other ATTENTION Switch on after finishing all wiring construction and re checking 1 Wiring Diagram A For power suppl...

Page 23: ...l 1 The user is advised to start the water pump before the heat pump and turn off the heat pump before the water pump for long life circle 2 The user should start the water pump and check for any leak...

Page 24: ...pply outside acceptable operating range Engage electrician to confirm power supply refer to technical specifications E06 Excessive temperature differential between inlet and outlet water insufficient...

Page 25: ...switch is broken Check the pressure switch and cold circuit E02 Low Pressure Prot Low pressure1 protection Check the pressure switch and cold circuit E03 Flow Switch Prot No water little water in wat...

Page 26: ...nnection between DC fan motor module and fan motor is in bad contact 1 Change a new fan motor 2 Check the wire connection and make sure they are in good contact E081 Communication Fault speed control...

Page 27: ...ough F17 Inv Input Out Phase The input voltage lost phase Check and measure the voltage adjustment F18 IPM Sampling Cur IPM sampling electricity is fault Check and adjust the current measurement F19 I...

Page 28: ...started for 2 minutes to sample the water temperature If after 2 minutes the temperature of the water is below above the required set point temperature depending if in heating or cooling mode the cir...

Page 29: ...hat the power cable is 1 8m long and should be plugged directly into a general power outlet not into an extension lead 8 4 2 Pump The circulation pump plugs into the 240V outlet beneath the NovaSwitch...

Page 30: ...time sometimes is not sufficient to maintain the water at the desired temperature depending on the seasons This is the reason why the heat pump is equipped with the sample function that will manage t...

Page 31: ...nd should be plugged directly into a general power outlet not into an extension lead 9 4 2 Pump The filtration pump plugs into the 240V outlet beneath the NovaLink Marked pump on the controller face 9...

Page 32: ...te upgrade of the main device by WIFI module baseplate MCU 10 3 Technical Parameters OPERATING VOLTAGE DC8V 12V Recommended value 12V OPERATING CURRENT Max recurrent peak 1A average standby current 50...

Page 33: ...10 5 Functional Description 10 6 Account Login Heatseeker NovaS Heat Pump Installation User Manual 31...

Page 34: ...e figure Enter your registered email address and password and click 3 to jump to the device list 3 Forgot Password When you forget your password click 4 Fig 2 and jump to the password forgotten interf...

Page 35: ...d click 6 to confrim click 7 to turn the page 2 Click 8 to enter the WIFI password for the current connection click 9 to confirm 3 Jump to system settings connect specified WIFI click 10 to select the...

Page 36: ...page to configure the network click 14 to turn next page Fig 13 click 15 to bond device Fig 14 5 Click OK Fig 15 to allow the App to use the camera for scanning the WH barcode on the heat pump unit F...

Page 37: ...10 9 Device Management Heatseeker NovaS Heat Pump Installation User Manual 35...

Page 38: ...Heatseeker NovaS Heat Pump Installation User Manual 36...

Page 39: ...e Product 4 The Automatic Controller included in the Product carries a in the case of an AquaGen 5 Series of Automatic Controllers including Sensors a three 3 year limited warranty For spare parts and...

Page 40: ...services supplied again What Supreme Solar Pty Ltd will do 10 For defects relating to installation of the Product Supreme Solar Pty Ltd will in its absolute discretion a repair the Product or pay for...

Page 41: ...f such purchase b Product Supreme Solar Pty Ltd solar pool heating system c Governing law paragraph 16 Victoria Australia Consumer guarantee 18 This warranty is provided in addition to consumer guaran...

Page 42: ...NOTES Heatseeker NovaS Heat Pump Installation User Manual 40...

Page 43: ...Heatseeker NovaS Heat Pump Installation User Manual 41...

Page 44: ...HeatseekerVortexE Inverter Heat Pump Installation User Manual 42 HeatseekerVortexE Inverter Heat Pump Installation User Manual 42 supremeheating com au 1300 787 978...

Reviews: