background image

14 

 

Table 3: Electric furnace SUP, ECM ½ HP motor, air flow tables

 

 

 

AC / HP SIZE

Adjustment

BLUE wire position

A/C size 

(TONS)

CFM ?

AC/HP CFM ADJUST

BLACK wire position = (NOM)

CFM ?

AC/HP CFM ADJUST

BLACK wire position = (LO)

CFM ?

AC/HP CFM ADJUST

BLACK wire position = (HI)

36

3,0

1200

1080

1320

30

2,5

1000

900

1100

24

2,0

800

720

880

18

1,5

600

540

660

AC / HP SIZE

Selection

BLUE wire position

A/C size 

(TONS)

CFM  ?

CONTINUOUS FAN

YELLOW wire position = (LO)

CFM  ?

CONTINUOUS FAN

YELLOW wire position = (MED)

CFM  ?

CONTINUOUS FAN

YELLOW wire position = (HI)

36

3,0

600

960

1200

30

2,5

500

800

1000

24

2,0

400

640

800

18

1,5

300

480

600

HEAT KW/CFM

adjustment

RED wire position

POWER 

(Kw)

CFM

First stage

24 VAC on W1*

CFM

Second stage

24 VAC on W1 and/or W2*

20

20

500

1000

18

18

450

900

15

15

400

800

ON / OFF DELAY

Adjustment

WHITE wire position

ON-Delay

Time

OFF-Delay

% CFM - Time

0 / 90

0 sec.

100% - 90 sec.

30 / 90

30 sec.

100% - 90 sec.

0 / 0 

0 sec.

0 sec.

ENH

30 sec.

70 % - 150 sec.

No adjustment

required

ON-Delay

Time

OFF-Delay

% CFM - Time

-

0 sec.

50% -  60 sec.

ELECTRIC HEATING MODE

24 VAC (R) input on W1 and/or W2 only

* Remove the Jumper 

J2

 when a 2 stages thermostat is used

ON & OFF DELAY FOR COOLING AND HEAT PUMP HEATING MODE

DELAY PROFILE FOR ELECTRIC HEATING MODE

COOLING OR HEAT PUMP HEATING MODE (WITH HP-EFF SELECTED ?)

24 VAC (R) input on G, Y/Y2 and O (for cooling)

? In Cooling - Dehumidification mode (with Jumper 

J1

 remove), with no 24 VAC input to DH, the CFMs are reduced by 15%.

? The CFMs shown are reduced by 20% if there is 24 VAC input to Y1 only (Y/Y2 not powered)
? SYSTEM TYPE select to HP-EFF corresponds to 400 CFM/TONS - HP-COMFORT corresponds to 350 CFM/TONS

CONTINUOUS FAN

24 VAC (R) input on G only

? CFM's when AC/HP CFM ADJUST at NOM position. CFM's 10% lower or higher if AC/HP CFM ADJUST at LO or HI position.

Summary of Contents for SUP10-A240V12

Page 1: ...ial Boulevard Sherbrooke Quebec Canada J1L 1V8 Caution Do not tamper with the unit or its controls Call a qualified service technician INSTALLER SERVICE TECHNICIAN USE THE INFORMATION IN THIS MANUAL F...

Page 2: ...ng mode dehumidification 9 3 3 5 Electric heat heating mode 1 stage 9 3 3 6 Electric heat heating mode 2 stage 9 3 3 7 Heat pump heating mode single stage 9 3 3 8 Heat pump heating mode two stage 9 3...

Page 3: ...e Ask the technician installing your furnace to show and explain to you the following items i The main disconnect switch or circuit breaker ii The air filter and how to change it check monthly and cl...

Page 4: ...nstallation The return duct may be installed to the back to the bottom on the left side or on the right side of the unit The supply duct shall be installed on the top of the unit Care should be taken...

Page 5: ...installation must be performed with copper wire ONLY in order to comply with the Canadian electrical code The usage of an aluminum or copper wire is acceptable on models 25kW and lower Move all wires...

Page 6: ...er the vertical sections of the supply and return air duct with soundproofing material c Use baffles in short radius elbows d Use flexible hangers to suspend the ducts The SUPREME furnace is equipped...

Page 7: ...irflow and zero 0 ON delay programmed into the ECM motor that cannot be overridden Four 4 motor operation delay profiles are provided to customize and enhance system operation Refer to Figure 10 and F...

Page 8: ...heat pump When using a heat pump a thermostat with dial fuel option or a fossil fuel kit is required that prevents the operation of the electric elements and the heat pump at the same time Refer to t...

Page 9: ...ng mode 1 stage Thermostat closes circuit R to W1 or W2 Furnace delivers the selected electric heat airflow and maximum heating capacity is powered starting the heating elements in sequence with a del...

Page 10: ...igned to engage during the improper functioning of the blower or when the filter was improperly maintained 3 4 2 High limit verification After operating the furnace for at least 15 minutes restrict th...

Page 11: ...ler name and address START UP RESULTS Voltage Total current consumed by the elements Supply air temperature Return air temperature Supply air duct static pressure Return air duct static pressure Total...

Page 12: ...N Fan ON after delays at selected Cooling CFM OFF Compressor OFF Fan OFF after selected cooling delays ON Compressor ON Fan ON after delays at 80 of the selected Cooling CFM OFF Compressor OFF Fan OFF...

Page 13: ...2 6 0 5 2 6 0 5 2 6 0 5 2 6 0 5 2 6 0 Heating Elements Consumption 240V 208V Amp 41 4 35 9 62 1 53 8 75 8 65 7 82 8 71 8 96 5 83 6 103 5 89 7 82 8 71 8 96 5 83 6 103 5 89 7 113 6 98 5 124 3 107 7 Tota...

Page 14: ...Adjustment WHITE wire position ON Delay Time OFF Delay CFM Time 0 90 0 sec 100 90 sec 30 90 30 sec 100 90 sec 0 0 0 sec 0 sec ENH 30 sec 70 150 sec No adjustment required ON Delay Time OFF Delay CFM...

Page 15: ...575 1150 ON OFF DELAY Adjustment WHITE wire position ON Delay Time OFF Delay CFM Time 0 90 0 sec 100 90 sec 30 90 30 sec 100 90 sec 0 0 0 sec 0 sec ENH 30 sec 70 150 sec No adjustment required ON Del...

Page 16: ...16 Figure 15 Furnace dimensions...

Page 17: ...17 Figure 16 Electrical diagram SUPREME Advantage ECM...

Page 18: ...18 Figure 17 Parts list SUPREME Advantage ECM...

Page 19: ...3 25kw 26 B04282 Electrical sequencer kit Supreme 18 20kw 27 B04283 Electrical sequencer kit Supreme 15kw 28 B04284 Electrical sequencer kit Supreme 10kw 29 B04275 Plastic top door 30 X50042 Label log...

Reviews: