background image

 

WARNING 

Risk of fire. 

The conductor sizing must conform to the last edition of the 
local or national codes. 

Failure to follow this rule can result in death, bodily injury 
and/or property damage. 

Power supply to the unit can be done using copper or aluminum 
wires. The wire size must be decided in accordance to the unit 
power  consumption,  the  over  current  protection  type  and 
capacity, the wire type and length, and the environment where 
the  unit  is  installed.  If  an  aluminum  wire  is  used,  other 
precautions  must  be  taken  to  insure  the  conformity  of  the 
installation. In all cases, all the factors affecting the wire gauge 
must be considered and the installation codes followed. 
 
The  exterior  of  the unit must have  an  uninterrupted ground  to 
minimize the risk of bodily harm.  A ground terminal is supplied 
with the control box for that purpose. A connector is supplied on 
the ground terminal to ground an added accessory. 
 
In the event that wires inside the unit require replacement, these 
must  be  copper  wires  only  with  same  temperature  rating  and 
sizes as originals. 

2.4.1-  Conversion from two to one supply wires for 
model over 27kW  

 

Warning

  –  When  using  one  terminal  block  on  models  over 

27kW,  the  installation  must  be  performed  with  copper  wire 
ONLY in order to comply with the Canadian electrical code. The 
usage of an aluminum or copper wire is acceptable on models 
25kW and lower. 
 
Move  all  wires  from  the  two  pole  terminal  to  the  three  pole 
terminal following the corresponding colors as shown in Figure 
4. 
The breaker and the supply conductors must be sized by adding 
the ampacities of the two terminals indicated on the nameplate. 
Refer to the electrical diagram Figure 16. 
 

Figure 4 : Conversion from two to one supply wires 

Before   

 

 

After 

 

2.5-  INSTALLATION OF THE THERMOSTAT 

A thermostat must be installed to control the temperature of the 
area  to  be  heated.    Follow  the  instructions  supplied  with  the 
thermostat. Some thermostats need to connect the C terminal 
on  the  furnace  and  thermostat.  Install  the  thermostat  on  an 
interior  wall  in  a  location  where  it  will  not  be  subject  to  direct 
sunlight,  lamps,  air  diffusers,  fireplaces,  etc.  Seal  openings  in 
walls to avoid air currents that may influence the operation of the 
thermostat. Also refer to the wiring diagrams provided with the 
heating/air conditioning unit. The connections must be made as 
indicated on Figure 5 to Figure 9. Refer to the electrical diagram 
(Figure 16

). 

Figure 5: 1-stage thermostat, electric heating only 

 

Figure 6: 2-stage thermostat, electric heating only 

 

Figure 7: 1 stage thermostat, electric heat and cooling 

application 

 

 

 

Summary of Contents for SUP10-A240V12

Page 1: ...ial Boulevard Sherbrooke Quebec Canada J1L 1V8 Caution Do not tamper with the unit or its controls Call a qualified service technician INSTALLER SERVICE TECHNICIAN USE THE INFORMATION IN THIS MANUAL F...

Page 2: ...ng mode dehumidification 9 3 3 5 Electric heat heating mode 1 stage 9 3 3 6 Electric heat heating mode 2 stage 9 3 3 7 Heat pump heating mode single stage 9 3 3 8 Heat pump heating mode two stage 9 3...

Page 3: ...e Ask the technician installing your furnace to show and explain to you the following items i The main disconnect switch or circuit breaker ii The air filter and how to change it check monthly and cl...

Page 4: ...nstallation The return duct may be installed to the back to the bottom on the left side or on the right side of the unit The supply duct shall be installed on the top of the unit Care should be taken...

Page 5: ...installation must be performed with copper wire ONLY in order to comply with the Canadian electrical code The usage of an aluminum or copper wire is acceptable on models 25kW and lower Move all wires...

Page 6: ...er the vertical sections of the supply and return air duct with soundproofing material c Use baffles in short radius elbows d Use flexible hangers to suspend the ducts The SUPREME furnace is equipped...

Page 7: ...irflow and zero 0 ON delay programmed into the ECM motor that cannot be overridden Four 4 motor operation delay profiles are provided to customize and enhance system operation Refer to Figure 10 and F...

Page 8: ...heat pump When using a heat pump a thermostat with dial fuel option or a fossil fuel kit is required that prevents the operation of the electric elements and the heat pump at the same time Refer to t...

Page 9: ...ng mode 1 stage Thermostat closes circuit R to W1 or W2 Furnace delivers the selected electric heat airflow and maximum heating capacity is powered starting the heating elements in sequence with a del...

Page 10: ...igned to engage during the improper functioning of the blower or when the filter was improperly maintained 3 4 2 High limit verification After operating the furnace for at least 15 minutes restrict th...

Page 11: ...ler name and address START UP RESULTS Voltage Total current consumed by the elements Supply air temperature Return air temperature Supply air duct static pressure Return air duct static pressure Total...

Page 12: ...N Fan ON after delays at selected Cooling CFM OFF Compressor OFF Fan OFF after selected cooling delays ON Compressor ON Fan ON after delays at 80 of the selected Cooling CFM OFF Compressor OFF Fan OFF...

Page 13: ...2 6 0 5 2 6 0 5 2 6 0 5 2 6 0 5 2 6 0 Heating Elements Consumption 240V 208V Amp 41 4 35 9 62 1 53 8 75 8 65 7 82 8 71 8 96 5 83 6 103 5 89 7 82 8 71 8 96 5 83 6 103 5 89 7 113 6 98 5 124 3 107 7 Tota...

Page 14: ...Adjustment WHITE wire position ON Delay Time OFF Delay CFM Time 0 90 0 sec 100 90 sec 30 90 30 sec 100 90 sec 0 0 0 sec 0 sec ENH 30 sec 70 150 sec No adjustment required ON Delay Time OFF Delay CFM...

Page 15: ...575 1150 ON OFF DELAY Adjustment WHITE wire position ON Delay Time OFF Delay CFM Time 0 90 0 sec 100 90 sec 30 90 30 sec 100 90 sec 0 0 0 sec 0 sec ENH 30 sec 70 150 sec No adjustment required ON Del...

Page 16: ...16 Figure 15 Furnace dimensions...

Page 17: ...17 Figure 16 Electrical diagram SUPREME Advantage ECM...

Page 18: ...18 Figure 17 Parts list SUPREME Advantage ECM...

Page 19: ...3 25kw 26 B04282 Electrical sequencer kit Supreme 18 20kw 27 B04283 Electrical sequencer kit Supreme 15kw 28 B04284 Electrical sequencer kit Supreme 10kw 29 B04275 Plastic top door 30 X50042 Label log...

Reviews: