Refer to the unit wiring diagram and select the pin for the heater 
size being used (Refer to Figure 10 and Figure 16). 
 
The  airflow  must  be  large  enough  for  safe  and  continuous 
operation. (Refer to Table 3 and 4 for airflow delivery CFM). 

2.6.2-  AC/HP size 

Select System Size Installed 

The factory setting for air conditioner or heat pump size is the 
largest outdoor unit that can be used with the furnace.  Installer 
needs to select air conditioner or heat pump size to ensure that 
airflow  delivered  falls  within  proper  range  for  the  size  unit 
installed. 
 
The  select  pins  are  marked  036,  030,  024,  018  for  furnace 
equipped  with  ½  HP  ECM  motor  and  060,  048,  042,  036  for 
furnace  equipped  with  1.0  HP  ECM  motor.    Refer  to  the  unit 
wiring diagram and select the pin for the outdoor unit size being 
used (Refer to Figure 10 and Figure 16). 

2.6.3-  System type 

Select System Type Installed AC or HP 

The type of system must be selected: 
1. 

AC 

– Air Conditioner provides approximately 400 CFM per 

ton  for  greater  efficiency  and  humidity  control  with  the 
AC/HP  CFM  ADJUST  set  to  the  nominal  (NOM)  tap.    To 
achieve more or less than 400 CFM per ton, move tap to 
(HI)  or  (LO)  position  respectively.    Refer  to  appropriate 
airflow tables for exact CFM setting. 

2. 

HP-COMFORT

 

– 

Heat 

Pump 

Comfort 

provides 

approximately  350  CFM  per  ton  for  higher  than  normal 
heating air delivery temperature.

 

3. 

HP-EFF

 – Heat Pump Efficiency provides same airflow for 

heating  and  cooling  modes  to  increase  overall  HP 
efficiency; approximately 400 CFM per ton with the AC/HP 
CFM ADJUST set to the nominal (NOM) tap.

 

The factory setting is AC (Refer to Figure 10 and Figure 16). 

2.6.4-  AC/HP CFM adjust 

Select Medium, Low, or High Airflow 

To provide airflow at rates described above, the AC/HP ADJUST 
select  is  factory  set  to  the  nominal  (NOM)  tap.    The  adjust 
selections HI/LO will regulate airflow supplied for all operational 
modes. 
 
HI provides 10% airflow over nominal unit size selected and LO 
provides 10% airflow below nominal unit size selected. 
 
Setting options are provided to adjust airflow supplied to meet 
individual  installation  needs  for  such  things  as  noise,  comfort, 
and humidity removal.  (Refer to Figure 10 and Figure 16) 

2.6.5-  ON/OFF delay 

Select desired time delay profile 

 

NOTE:

  Delay  selections  are  active  in  cooling  and  heat  pump 

heating  modes  only.    Electric  heating  modes  have  a  one  (1) 
minute  OFF  delay  at  50%  airflow  and  zero  (0)  ON  delay 
programmed into the ECM motor that cannot be overridden. 

 

Four  (4)  motor  operation  delay  profiles  are  provided  to 
customize and enhance system operation. (Refer to Figure 10 
and Figure 16). 

Selection options are: 
1. 

0/90:

  No  ON  delay  and  90  second  OFF  delay  at  100% 

airflow (factory setting). 

2. 

30/90:

 30 second ON delay with no airflow and 90 second 

OFF delay at 100% airflow profile.  Used when it is desirable 
to  allow  system  coils  time  to  heat-up/cool-down  in 
conjunction with the airflow.

 

3. 

0/0:

  No  delay  option.    Used  for  servicing  unit  or  when  a 

thermostat is utilized to perform delay functions.

 

4. 

ENH:

 enhanced selection provides a 30 second ON delay 

with no airflow followed by 150 seconds at 70% airflow, and 
no OFF delay for added comfort.  This profile will minimize 
cold  blow  in  heat  pump  operation  and  could  enhance 
system efficiency.

 

2.6.6-  Continuous fan 

NOTE:

 If installed with a two-stage outdoor unit, do not select HI 

speed continuous fan.  If HI is selected, low stage compression 
will  also  run  HI  fan  speed  possibly  resulting  in  insufficient 
dehumidification. 

 

Select  desired  fan  speed  when  thermostat  is  set  on 
continuous fan. (Refer to Figure 10 and Figure 16) 

1. 

LO speed

 – factory setting, 50% cooling mode airflow. 

2. 

MED speed

 – move connector to MED, 80% cooling mode 

airflow.

 

3. 

HI  speed

  –  move  connector  to  HI,  100%  cooling  mode 

airflow.

 

2.6.7-  Low-voltage circuit 

Fusing and Reference 

The  low-voltage  circuit  is  fused  by  a  board-mounted  5-amp 
automotive fuse placed in series with the transformer SEC2 and 
the R circuit.  The C circuit of the transformer is referenced to 
chassis ground through a printed circuit run at SEC1 connected 
to metal standoff marked with ground symbol. 

2.6.8-  Basic furnace configuration 

The following basic configuration of the furnace will provide ARI 
rated performance of an air conditioner: 
1. 

HEAT  KW/CFM

  –  Select  the  heater  range  for  the  size 

electric heater installed. 

2. 

AC/HP SIZE

 – Select system size installed. 

3. 

SYSTEM TYPE

 – Select system type AC 

4. 

AC/HP CFM ADJUST

 – Select NOM. 

5. 

ON/OFF DELAY

 – Select 0/90 profile. 

6. 

CONTINUOUS  FAN

  –  Select  desired  fan  speed  when 

thermostat is set to continuous fan. 

 
The following basic configuration of the furnace will provide ARI 
rated performance of a heat pump: 

1. 

HEAT  KW/CFM

  –  Select  the  heater  range  for  the  size 

electric heater installed. 

2. 

AC/HP SIZE

 – Select system size installed. 

3. 

SYSTEM TYPE

 – Select system type HP-EFF 

4. 

AC/HP CFM ADJUST

 – Select NOM. 

5. 

ON/OFF DELAY

 – Select 0/90 profile. 

6. 

CONTINUOUS  FAN

  –  Select  desired  fan  speed  when 

thermostat is set to continuous fan. 

Summary of Contents for SUP10-A240V12

Page 1: ...ial Boulevard Sherbrooke Quebec Canada J1L 1V8 Caution Do not tamper with the unit or its controls Call a qualified service technician INSTALLER SERVICE TECHNICIAN USE THE INFORMATION IN THIS MANUAL F...

Page 2: ...ng mode dehumidification 9 3 3 5 Electric heat heating mode 1 stage 9 3 3 6 Electric heat heating mode 2 stage 9 3 3 7 Heat pump heating mode single stage 9 3 3 8 Heat pump heating mode two stage 9 3...

Page 3: ...e Ask the technician installing your furnace to show and explain to you the following items i The main disconnect switch or circuit breaker ii The air filter and how to change it check monthly and cl...

Page 4: ...nstallation The return duct may be installed to the back to the bottom on the left side or on the right side of the unit The supply duct shall be installed on the top of the unit Care should be taken...

Page 5: ...installation must be performed with copper wire ONLY in order to comply with the Canadian electrical code The usage of an aluminum or copper wire is acceptable on models 25kW and lower Move all wires...

Page 6: ...er the vertical sections of the supply and return air duct with soundproofing material c Use baffles in short radius elbows d Use flexible hangers to suspend the ducts The SUPREME furnace is equipped...

Page 7: ...irflow and zero 0 ON delay programmed into the ECM motor that cannot be overridden Four 4 motor operation delay profiles are provided to customize and enhance system operation Refer to Figure 10 and F...

Page 8: ...heat pump When using a heat pump a thermostat with dial fuel option or a fossil fuel kit is required that prevents the operation of the electric elements and the heat pump at the same time Refer to t...

Page 9: ...ng mode 1 stage Thermostat closes circuit R to W1 or W2 Furnace delivers the selected electric heat airflow and maximum heating capacity is powered starting the heating elements in sequence with a del...

Page 10: ...igned to engage during the improper functioning of the blower or when the filter was improperly maintained 3 4 2 High limit verification After operating the furnace for at least 15 minutes restrict th...

Page 11: ...ler name and address START UP RESULTS Voltage Total current consumed by the elements Supply air temperature Return air temperature Supply air duct static pressure Return air duct static pressure Total...

Page 12: ...N Fan ON after delays at selected Cooling CFM OFF Compressor OFF Fan OFF after selected cooling delays ON Compressor ON Fan ON after delays at 80 of the selected Cooling CFM OFF Compressor OFF Fan OFF...

Page 13: ...2 6 0 5 2 6 0 5 2 6 0 5 2 6 0 5 2 6 0 Heating Elements Consumption 240V 208V Amp 41 4 35 9 62 1 53 8 75 8 65 7 82 8 71 8 96 5 83 6 103 5 89 7 82 8 71 8 96 5 83 6 103 5 89 7 113 6 98 5 124 3 107 7 Tota...

Page 14: ...Adjustment WHITE wire position ON Delay Time OFF Delay CFM Time 0 90 0 sec 100 90 sec 30 90 30 sec 100 90 sec 0 0 0 sec 0 sec ENH 30 sec 70 150 sec No adjustment required ON Delay Time OFF Delay CFM...

Page 15: ...575 1150 ON OFF DELAY Adjustment WHITE wire position ON Delay Time OFF Delay CFM Time 0 90 0 sec 100 90 sec 30 90 30 sec 100 90 sec 0 0 0 sec 0 sec ENH 30 sec 70 150 sec No adjustment required ON Del...

Page 16: ...16 Figure 15 Furnace dimensions...

Page 17: ...17 Figure 16 Electrical diagram SUPREME Advantage ECM...

Page 18: ...18 Figure 17 Parts list SUPREME Advantage ECM...

Page 19: ...3 25kw 26 B04282 Electrical sequencer kit Supreme 18 20kw 27 B04283 Electrical sequencer kit Supreme 15kw 28 B04284 Electrical sequencer kit Supreme 10kw 29 B04275 Plastic top door 30 X50042 Label log...

Reviews: