INSTALLATION
WARNING: TO PREVENT HIGH VOLTAGE ON RED & YELLOW OUTPUT LEADS PRIOR TO
INSTALLATION, BATTERY CONNECTOR MUST BE OPEN. JOIN BATTERY CONNECTOR
AFTER INSTALLATION, AND AFTER AC POWER IS TURNED ON.
NOTE:
Make sure that the necessary branch circuit wiring is available. An unswitched source
of power is required. The emergency ballast must be fed from the same branch circuit
as the AC ballast.
1. Disconnect AC power from the fixture. Remove the ballast channel cover and install the
emergency ballast either in the ballast channel (See Illustrations 1 & 2) or on top of the fixture*
(See Illustration 3).
2. Select the appropiate wiring diagram to connect the emergency ballast to the AC ballast and
lamp. Make sure all connections are in accordance with the National Electrical Code and any local
regulations.
3. Install the test switch through the ballast channel cover of a troffer or through the side of a strip fixture.
Drill a 1/2" hole and install the switch as shown (See Illustrations 1 & 2). Wire the test switch so that it
removes AC power from both the emergency ballast and the AC ballast at the same time (See Illustration 4).
4. Refer to Illustration 5 and install the charging indicator light so that it will be visible after the fixture is installed.
NOTE:
After installing the charging indicator light and test switch, mark each with the appropiate
label. If a detached charging indicator light is used, connect by matching wire colors and
install as shown in Illustration 5.
5. In a readily visible location, attach the label “CAUTION-This Unit Has More Than One Power Connection
Point. To Reduce The Risk Of Electric Shock, Disconnect Both The Branch Circuit-Breakers Or Fuses and
Emergency Power Supplies Before Servicing.”
Emergency
Ballast
Charging
Indicator
Light
Test
Switch
Ballast
Channel
Cover
Emergency
Ballast
Charging
Indicator
Light
Test
Switch
Wire Bundle
Cover
*
Wire Bundle
Cover
*
Drill 1/8"
Hole For
Mounting
Screws
Emergency
Ballast
1/2" Std.
Knockout
7/8" Hole
W/ Bushing
ILLUSTRATION 1
ILLUSTRATION 2
ILLUSTRATION 3
ILLUSTRATION 4
HOT
COM
BLACK
WHITE
WHITE
AC
BALLAST
Emergency
Ballast
120V
OR
ORANGE 277V
(CAP UNUSED LEAD)
BLACK
TEST
SWITCH
RED
RED
UNSWITCHED FIXTURE
SWITCHED FIXTURE
BLACK
BLACK
HOT
COM
BLACK
WHITE
WHITE
AC
BALLAST
Emergency
Ballast
120V
OR
ORANGE 277V
(CAP UNUSED LEAD)
BLACK
TEST
SWITCH
WALL
SWITCH
RED
RED
BLACK
BLACK
*For installation on top of the fixture, wire bundle covers may be required by state or local codes. These covers are
available from the manufacturer as an accessory kit and must be ordered separately. Call your local distributor or the
factory for complete information.
ADDITIONAL WIRING DIAGRAMS-1 LAMP EMERGENCY OPERATION
DETERMINE APPROPRIATE DIAGRAM USING NUMBER AND COLORS OF AC BALLAST LEAD WIRES
FOR MODELS WITH BROWN LAMP CONNECTOR WIRES, SEE SPECIFIC MODEL'S INSTRUCTION FOR WHEN TO CONNECT
NOTE: These wiring diagrams are suitable for electronic AC ballast.
2A. 1-LAMP RAPID START
RED
WHITE
BATTERY CONNECTOR
INDICATOR LIGHT
ORANGE
BLACK
BLUE
BLUE
BLU/WHT
WHITE
277V
120V
COM
TO UNSWITCHED AC
USE PROPER TAP
CAP UNUSED LEAD
EMERGENCY
BALLAST
AC BALLAST
WHITE
BLACK
LINE
BLUE
RED
RED
YELL/BLK
YELLOW
RED
LAMP (EMERGENCY)
3A. 2-LAMP RAPID START
RED
WHITE
BATTERY CONNECTOR
INDICATOR LIGHT
ORANGE
BLACK
BLUE
BLUE
BLU/WHT
WHITE
277V
120V
COM
TO UNSWITCHED AC
USE PROPER TAP
CAP UNUSED LEAD
EMERGENCY
BALLAST
AC BALLAST
WHITE
BLACK
LINE
BLUE
RED
RED
YELL/BLK
YELLOW
YELLOW
RED
LAMP 2 (EMERGENCY)
LAMP 1
7A. 3-LAMP INSTANT START
BLUE
BLUE
BLUE
BLUE
BLU/WHT
AC BALLAST
WHITE
BLACK
LINE
YELL/BLK
YELLOW
RED
RED
LAMP 2
LAMP 1
RED
or
WHITE
BATTERY CONNECTOR
INDICATOR LIGHT
ORANGE
BLACK
WHITE
277V
120V
COM
TO UNSWITCHED AC
USE PROPER TAP
CAP UNUSED LEAD
EMERGENCY
BALLAST
LAMP 3 (EMERGENCY)
YELL
11A. 4-LAMP INSTANT START
RED
BLUE
RED
BLUE
BLU/WHT
AC BALLAST
WHITE
BLACK
LINE
YELL/BLK
YELLOW
YELLOW
YELLOW
RED
BLUE
LAMP 2
LAMP 1
LAMP 3
RED
WHITE
BATTERY CONNECTOR
INDICATOR LIGHT
ORANGE
BLACK
WHITE
277V
120V
COM
TO UNSWITCHED AC
USE PROPER TAP
CAP UNUSED LEAD
EMERGENCY
BALLAST
LAMP 4 (EMERGENCY)
AC BALLASTS
VALMONT
E432PI120
E432PI277
11C. 4-LAMP INSTANT START (3 Lamps Used)
RED
CAP
BLUE
RED
BLUE
BLU/WHT
AC BALLAST
WHITE
BLACK
LINE
YELL/BLK
YELLOW
YELLOW
YELLOW
RED
BLUE
LAMP 2
LAMP 1
RED
WHITE
BATTERY CONNECTOR
INDICATOR LIGHT
ORANGE
BLACK
WHITE
277V
120V
COM
TO UNSWITCHED AC
USE PROPER TAP
CAP UNUSED LEAD
EMERGENCY
BALLAST
LAMP 3 (EMERGENCY)
AC BALLASTS
VALMONT
E432PI120
E432PI277
]
14A. 4-LAMP INSTANT START
BLUE
BLUE
RED
BLUE
BLU/WHT
AC BALLAST
WHITE
BLACK
LINE
YELL/BLK
YELLOW
YELLOW
YELLOW
RED
RED
LAMP 2
LAMP 1
LAMP 3
RED
WHITE
BATTERY CONNECTOR
INDICATOR LIGHT
ORANGE
BLACK
WHITE
277V
120V
COM
TO UNSWITCHED AC
USE PROPER TAP
CAP UNUSED LEAD
EMERGENCY
BALLAST
LAMP 4 (EMERGENCY)
AC BALLASTS
ADVANCE
EBT
UNIVERSAL, TRIAD
REL-4P32-RH-TP SS82-277-4/32ISLH B432I120
REL-4P32-TP
B432I277
VEL-4P32-RH-TP OSRAM
VEL-4P32-TP QT-4x32/120IS
QT-4x32/277IS
AC BALLASTS
ADVANCE
EBT
UNIVERSAL, TRIAD
REL-4P32-RH-TP SS82-277-4/32ISLH B432I120
REL-4P32-TP
B432I277
VEL-4P32-RH-TP OSRAM
VEL-4P32-TP QT-4x32/120IS
QT-4x32/277IS
14C. 4-LAMP INSTANT START (3 Lamps Used)
BLUE
CAP
BLUE
RED
BLUE
BLU/WHT
AC BALLAST
WHITE
BLACK
LINE
YELL/BLK
YELLOW
YELLOW
YELLOW
RED
RED
LAMP 2
LAMP 1
RED
WHITE
BATTERY CONNECTOR
INDICATOR LIGHT
ORANGE
BLACK
WHITE
277V
120V
COM
TO UNSWITCHED AC
USE PROPER TAP
CAP UNUSED LEAD
EMERGENCY
BALLAST
LAMP 3 (EMERGENCY)
]
36A. 2-LAMP INSTANT START
BLUE
BLUE
BLUE
BLU/WHT
AC BALLAST
WHITE
BLACK
LINE
YELL/BLK
YELLOW
RED
RED
LAMP 1
RED
WHITE
BATTERY CONNECTOR
INDICATOR LIGHT
ORANGE
BLACK
WHITE
277V
120V
COM
TO UNSWITCHED AC
USE PROPER TAP
CAP UNUSED LEAD
EMERGENCY
BALLAST
LAMP 2 (EMERGENCY)
51A. 4-LAMP INSTANT START
RED
RED
BLU/WHT
BLU/WHT
BLUE
BLU/WHT
AC BALLAST
WHITE
BLACK
LINE
YELL/BLK
YELLOW
YELLOW
YELLOW
RED
BLUE
BLUE
BROWN
BROWN
LAMP 2
LAMP 1
LAMP 3
RED
WHITE
BATTERY CONNECTOR
INDICATOR LIGHT
ORANGE
BLACK
WHITE
277V
120V
COM
TO UNSWITCHED AC
USE PROPER TAP
CAP UNUSED LEAD
EMERGENCY
BALLAST
LAMP 4 (EMERGENCY)
52A. 1-LAMP INSTANT START
BLUE
BLUE
BLU/WHT
AC BALLAST
WHITE
BLACK
LINE
YELL/BLK
YELLOW
RED
RED
RED
WHITE
BATTERY CONNECTOR
INDICATOR LIGHT
ORANGE
BLACK
WHITE
277V
120V
COM
TO UNSWITCHED AC
USE PROPER TAP
CAP UNUSED LEAD
EMERGENCY
BALLAST
LAMP (EMERGENCY)