background image

Installation Instructions For FBP-2-40H

IMPORTANT SAFEGUARDS

WHEN USING ELECTRICAL EQUIPMENT, BASIC SAFETY PRECAUTIONS SHOULD ALWAYS
BE OBSERVED INCLUDING THE FOLLOWING:

1.

READ AND FOLLOW ALL SAFETY INSTRUCTIONS

2.

Do not use outdoors.

3.

Do not mount near gas or electric heaters.

4.

Equipment should be mounted in locations and at heights where it will not readily be subjected to tampering by unauthorized
personnel.

5.

The use of accessory equipment not recommended by Sure-Lites may cause an unsafe condition.

6.

Do not use this equipment for other than its intended purpose.

7.

SAVE THESE INSTRUCTIONS

Step 1.

To prevent high voltage from being present on the output leads (red and yellow), do not join the battery connector until installation is complete and
AC power is supplied to the emergency ballast.

Step 2.

This product is for use with 17W through 215W single and bipin fluorescent lamps, including standard, energy saving, HO, VHO, circline, U-shaped
and rapid-start long compact and 18W through 28W 4-pin compact fluorescent lamp(s) without integral starters.

Step 3.

Make sure all connections are in accordance with the National Electrical Code and any local regulations.

Step 4.

To reduce the risk of electrical shock, disconnect both normal and emergency power supplies and battery connector of the emergency ballast
before servicing.

Step 5.

This emergency ballast is for factory or field installation in either the ballast channel or on top of the fixture..

Step 6.

This product is for use in indoor fixtures except air handling heated air outlets, and wet, damp or hazardous location fixtures.

Step 7.

An unswitched AC power source is required. (120 or 277 volts).

Step 8.

Do not attempt to service the battery. A sealed, no-maintenance battery is used that is not field replaceable. Contact the manufacturer for
information on service.

Step 9.

Servicing should be performed by qualified service personnel.

SURE-LITES

SURE-LITES   

1121 Highway 74 South  Peachtree City, GA 30269

5/98

024000085

LISTED

®

CONTAINS NICKEL-CADMIUM
RECHARGEABLE BATTERY.
MUST BE RECYCLED OR 
DISPOSED OF PROPERLY.

ADDITIONAL WIRING DIAGRAMS-2 LAMP EMERGENCY OPERATION

NOTE:

WIRING DIAGRAMS (THIS SIDE) ONLY FOR EMERGENCY BALLASTS RATED FOR 2-LAMP EMERGENCY OPERATION. 

CHECK UNIT LABEL TO DETERMINE NUMBER OF LAMPS THAT CAN BE OPERATED IN EMERGENCY. DETERMINE 
APPROPRIATE DIAGRAM USING NUMBER AND COLORS OF AC BALLAST LEAD WIRES.

FOR MODELS WITH BROWN LAMP CONNECTOR WIRES, SEE SPECIFIC MODEL'S INSTRUCTION FOR WHEN TO CONNECT

3B.  2-LAMP RAPID START 

RED

WHITE

BATTERY CONNECTOR

INDICATOR LIGHT

ORANGE

BLACK

BLUE

BLUE

BLU/WHT

WHITE

277V
120V

COM

TO UNSWITCHED AC
USE PROPER TAP
CAP UNUSED LEAD

EMERGENCY
  BALLAST

  

AC  BALLAST

WHITE

BLACK

LINE

BLUE

RED

RED

YELL/BLK

YELLOW

YELLOW

YELLOW

RED

LAMP 2  (EMERGENCY)

  (EMERGENCY)

  (EMERGENCY)

  (EMERGENCY)

  (EMERGENCY)

LAMP 1

4B.  2-LAMP LEAD-LAG INSTANT START SLIMLINE 

RED

WHITE

BATTERY CONNECTOR

INDICATOR LIGHT

ORANGE

BLACK

BLUE

BLUE

BLU/WHT

WHITE

277V
120V

COM

TO UNSWITCHED AC
USE PROPER TAP
CAP UNUSED LEAD

EMERGENCY
  BALLAST

  

AC  BALLAST

WHITE

BLACK

LINE

RED

YELL/BLK

YELLOW

RED

LAMP 2  (EMERGENCY)

LAMP 1

7B.  3-LAMP INSTANT START 

 

BLUE

BLUE

BLUE

BLU/WHT

BLUE

    

AC  BALLAST

WHITE

BLACK

LINE

YELL/BLK

YELLOW

RED

RED

    YELLOW

LAMP 1

RED

WHITE

BATTERY CONNECTOR

INDICATOR LIGHT

ORANGE

BLACK

WHITE

277V
120V

COM

TO UNSWITCHED AC
USE PROPER TAP
CAP UNUSED LEAD

EMERGENCY
  BALLAST

LAMP 2

LAMP 3 (EMERGENCY)

(EMERGENCY)

11B.  4-LAMP INSTANT START 

 

RED

BLUE

RED

BLUE

BLU/WHT

    

AC  BALLAST

WHITE

BLACK

LINE

YELL/BLK

YELLOW

YELLOW

YELLOW

RED

BLUE

LAMP 2

LAMP 1

LAMP 3

RED

WHITE

BATTERY CONNECTOR

INDICATOR LIGHT

ORANGE

BLACK

WHITE

277V
120V

COM

TO UNSWITCHED AC
USE PROPER TAP
CAP UNUSED LEAD

EMERGENCY
  BALLAST

LAMP 4 (EMERGENCY)

AC BALLASTS

        VALMONT
          E432PI120
          E432PI277

11D.  4-LAMP INSTANT START (3 Lamps Used)

 

RED

CAP

BLUE

BLUE

BLUE

BLU/WHT

    

AC  BALLAST

WHITE

BLACK

LINE

YELL/BLK

YELLOW

YELLOW

YELLOW

RED

RED

LAMP 2

LAMP 1

RED

WHITE

BATTERY CONNECTOR

INDICATOR LIGHT

ORANGE

BLACK

WHITE

277V
120V

COM

TO UNSWITCHED AC
USE PROPER TAP
CAP UNUSED LEAD

EMERGENCY
  BALLAST

LAMP 3 (EMERGENCY)

AC BALLASTS

        VALMONT
          E432PI120
          E432PI277

]

 or

14B.  4-LAMP INSTANT START 

 

BLUE

RED

RED

BLUE

BLUE

BLU/WHT

    

AC  BALLAST

WHITE

BLACK

LINE

YELL/BLK

YELLOW

YELLOW

YELLOW

RED

LAMP 2

LAMP 1

LAMP 3

RED

WHITE

BATTERY CONNECTOR

INDICATOR LIGHT

MAGNETEK

MAGNETEK

ORANGE

BLACK

WHITE

277V
120V

COM

TO UNSWITCHED AC
USE PROPER TAP
CAP UNUSED LEAD

EMERGENCY
  BALLAST

LAMP 4 (EMERGENCY)

(EMERGENCY)

14D.  4-LAMP INSTANT START (3 Lamps Used)

 

BLUE

BLUE

RED

BLUE

BLU/WHT

    

AC  BALLAST

WHITE

BLACK

LINE

YELL/BLK

YELLOW

YELLOW

YELLOW

RED

RED

CAP

LAMP 2

LAMP 1

RED

WHITE

BATTERY CONNECTOR

INDICATOR LIGHT

ORANGE

BLACK

WHITE

277V
120V

COM

TO UNSWITCHED AC
USE PROPER TAP
CAP UNUSED LEAD

EMERGENCY
  BALLAST

LAMP 3 (EMERGENCY)

(EMERGENCY)

AC BALLASTS

        ADVANCE

               EBT

UNIVERSAL, TRIAD

          REL-4P32-RH-TP         SS82-277-4/32ISLH            B432I120
          REL-4P32-TP

    B432I277

          VEL-4P32-RH-TP       OSRAM
          VEL-4P32-TP                QT-4x32/120IS
        

                   QT-4x32/277IS

AC BALLASTS

        ADVANCE

               EBT

UNIVERSAL, TRIAD

          REL-4P32-RH-TP         SS82-277-4/32ISLH            B432I120
          REL-4P32-TP

    B432I277

          VEL-4P32-RH-TP       OSRAM
          VEL-4P32-TP                QT-4x32/120IS
        

                   QT-4x32/277IS

36B.  2-LAMP INSTANT START 

 

BLUE

BLUE

BLUE

BLU/WHT

    

AC  BALLAST

WHITE

BLACK

LINE

YELL/BLK

YELLOW

RED

RED

LAMP 1

RED

WHITE

BATTERY CONNECTOR

INDICATOR LIGHT

ORANGE

BLACK

WHITE

277V
120V

COM

TO UNSWITCHED AC
USE PROPER TAP
CAP UNUSED LEAD

EMERGENCY
  BALLAST

LAMP 2 (EMERGENCY)

(EMERGENCY)

51B.  4-LAMP RAPID START 

 

RED

RED

BLU/WHT

BLU/WHT

BLUE

BLU/WHT

    

AC  BALLAST

WHITE

BLACK

LINE

YELL/BLK

YELLOW

YELLOW

YELLOW

RED

BLUE

BLUE

BROWN

BROWN

LAMP 2

LAMP 1

LAMP 3

RED

WHITE

BATTERY CONNECTOR

INDICATOR LIGHT

ORANGE

BLACK

WHITE

277V
120V

COM

TO UNSWITCHED AC
USE PROPER TAP
CAP UNUSED LEAD

EMERGENCY
  BALLAST

LAMP 4 (EMERGENCY)

(EMERGENCY)