iControl Manual                                                                                           

 

 

10 

 

 
state prior to the shutdown event; “Last Known State” will return the outlet to its state prior to 
the shutdown event. 
 

ICE

 sets the enabling or disabling of the ICE function. This is available only for outlets 1 and 2. 

 

Security 
 

This page is used to set passwords for each of the three access levels: Viewer, User, and Admin.  
Press “Save” to save your selections.  

*Defaults are Viewer/viewer, User/user, Admin/admin.

 

 
Front Panel Reset Button 

 
The reset button is located towards the left side of the front panel, and is accessible by a small 
item such as a paperclip. The reset button performs 2 functions:  System Reboot and System 
Restore to Factory Defaults. 
 

System Reboot 

 
To reboot the iControl firmware, press and hold the front panel reset button until the LEDs turn 
off (approximately 1 second), then release. The system will then reboot. 
 

System Restore to Factory Defaults 

 

*Warning: removes all configuration information, including network setup, email setup, outlets 
setup, sequences, and schedules. 

 

Method 1 

 
To restore the iControl firmware to its factory default state, press and hold the front panel reset 
button until the LEDs turn off (approximately 1 second), continue holding until the LEDs all turn 
on again (approximately 4 seconds after they turn off), then release. The system will reboot with 
factory default settings restored. 
 

Method 2 

If Method 1 does not work, or if the iControl firmware appears to be “stuck” or “hung”, try 
Method 2 for restoring the factory default settings. Disconnect the iControl hardware from the ac 
power source. While pressing and holding the front panel reset button, connect the hardware to 
the ac power source. Wait until the LEDs all turn on and then off, then release the reset button. 
The system will reboot with factory default settings restored.

 

Summary of Contents for iControl SX1115-iP

Page 1: ...USER MANUAL SurgeX SX1115 iP SX1120 iP Web Enabled Power Conditioning Management System V1 0 19...

Page 2: ...T UP 3 INSTALLATION 3 120 VOLT CONNECTIONS 3 TCP IP TELNET CONNECTION 4 TEMPERATURE SENSOR 4 LED INDICATORS 4 WEB SERVER 4 HOME PAGE 4 ACTIONS PAGE 5 SEQUENCES PAGE 7 SCHEDULES PAGE 7 SETUP PAGE 8 FRO...

Page 3: ...tacles 1 and 2 SurgeX ICE eliminates problems associated with inrush currents from large loads such as amplifiers With SurgeX ICE it is not necessary to take inrush currents into account when designin...

Page 4: ...ssing and holding the front panel reset button until the LEDs turn off approximately 1 second or by cycling power to the unit 7 Disconnect the network cables 8 Restore your computer s original IP sett...

Page 5: ...on is as follows SELF TEST Green When illuminated the surge suppression circuitry is functioning correctly POWER Red When illuminated the iControl is connected to a live wall or floor outlet OVER UNDE...

Page 6: ...es button Status displays the current outlet state On or Off Press Refresh after making changes to reload the web page with the current outlet states displayed Current Draw displays the true RMS curre...

Page 7: ...he Surge Protection Status maintains a Failed state after pressing Clear Shutdown the iControl will need to be returned to SurgeX for analysis and repair or replacement Press Clear Shutdown on the Set...

Page 8: ...ear in the Actions Page when a sequence is selected as an action There can be up to 20 steps in a single sequence Select the time delay from the Delay Time column Select the outlet from the Item To Ch...

Page 9: ...ate and time settings Automatic specifies that the iControl should automatically synchronize its time with an internet time server You may enter the address of a time server in the text box or leave t...

Page 10: ...ted as hyperlinks on the upper left side of all the web pages Click Add to open the Add a Favorite page Enter the other unit s name and IP address and press Save Network This page allows the configura...

Page 11: ...ely 1 second then release The system will then reboot System Restore to Factory Defaults Warning removes all configuration information including network setup email setup outlets setup sequences and s...

Page 12: ...gy Unlimited due to current limiting Endurance C62 41 1991 category B3 pulses 1 KV 500 000 3 KV 10 000 6 KV 1000 Undervoltage Shutdown Adjustable from 90 Volts to 105 Volts Overvoltage Shutdown Adjust...

Reviews: