background image

iControl Manual                                                                                           

 

 

11 

 

 

Specifications

 

 

Load Rating:  

15/20 Amps at 120 Volts (SX1115iP/SX1120iP) 

 

Power Requirement (no load): 

 5 Watts  

 

Surge Let-through Voltage (6000 Volt surge):

  0 Volts 

 
UL 1449 Adjunct Classification Test Results:  

1000 surges, 6000 Volts, 3000 Amps, B3 pulse; measured 

suppressed voltage, 170 Volts; no failures 

 
Federal Guidelines: 

Grade A, Class 1, Mode 1 (CID A-A-55818)

 

 

EMI/RFI Filter, Normal Mode (50 Ohm load):

 40 dB @ 100 KHz, 50dB @ 300 KHz, 50 dB @ 3 MHz, 50 dB @ 

30 MHz 
 

EMI/RFI Filter, Common Mode (50 Ohm load):

 18dB @ 300 KHz, 30 dB @ 1 MHz, 50 dB @ 5 MHz, 50 dB @ 

20 MHz 

 
Maximum Applied Surge Voltage:

  6000 Volts * 

 

Maximum Applied Surge Current:

  Unlimited (due to current limiting) * 

 
Maximum Applied Surge Energy:

  Unlimited (due to current limiting) * 

 

Endurance (C62.41-1991 category B3 pulses):

 1 KV > 500,000; 3 KV > 10,000; 6 KV > 1000 

 

Undervoltage Shutdown:  

Adjustable from 90 Volts to 105 Volts 

 

Overvoltage Shutdown:

  Adjustable from 135 Volts to 150 Volts 

 

Maximum Load Inrush Energy During Power Up (ICE on Outlets 1 & 2 only): 

1000 Joules 

 

Network Port: 

10/100 Base T Ethernet connection on Female RJ-45 supporting TCP/IP, HTTP, DHCP, TFTP, 

telnet and NTP protocols. 

 

 
Dimensions:

  19” W x 10.5” D x 1.75” H (Single Rack Space) 

 

Weight:  

12.5 lb. 

 

Temperature Range: 

 5C to 35C 

 

Humidity Range: 

 5% to 95% R.H. Non-condensing 

 

Agency Listings:

  ETL and cETL (UL 1449, 2nd Edition; CSA C22.2 No.8-M1986, R2000) 

 
* 1.2 x 50 microsecond industry standard combination wave surge as per IEEE C62.41 

 
 
 

*CAUTION:  Do not install this device if there is not at least 10 meters (30 feet) or more 
between the electrical outlet and the electrical service panel. 

Summary of Contents for iControl SX1115-iP

Page 1: ...USER MANUAL SurgeX SX1115 iP SX1120 iP Web Enabled Power Conditioning Management System V1 0 19...

Page 2: ...T UP 3 INSTALLATION 3 120 VOLT CONNECTIONS 3 TCP IP TELNET CONNECTION 4 TEMPERATURE SENSOR 4 LED INDICATORS 4 WEB SERVER 4 HOME PAGE 4 ACTIONS PAGE 5 SEQUENCES PAGE 7 SCHEDULES PAGE 7 SETUP PAGE 8 FRO...

Page 3: ...tacles 1 and 2 SurgeX ICE eliminates problems associated with inrush currents from large loads such as amplifiers With SurgeX ICE it is not necessary to take inrush currents into account when designin...

Page 4: ...ssing and holding the front panel reset button until the LEDs turn off approximately 1 second or by cycling power to the unit 7 Disconnect the network cables 8 Restore your computer s original IP sett...

Page 5: ...on is as follows SELF TEST Green When illuminated the surge suppression circuitry is functioning correctly POWER Red When illuminated the iControl is connected to a live wall or floor outlet OVER UNDE...

Page 6: ...es button Status displays the current outlet state On or Off Press Refresh after making changes to reload the web page with the current outlet states displayed Current Draw displays the true RMS curre...

Page 7: ...he Surge Protection Status maintains a Failed state after pressing Clear Shutdown the iControl will need to be returned to SurgeX for analysis and repair or replacement Press Clear Shutdown on the Set...

Page 8: ...ear in the Actions Page when a sequence is selected as an action There can be up to 20 steps in a single sequence Select the time delay from the Delay Time column Select the outlet from the Item To Ch...

Page 9: ...ate and time settings Automatic specifies that the iControl should automatically synchronize its time with an internet time server You may enter the address of a time server in the text box or leave t...

Page 10: ...ted as hyperlinks on the upper left side of all the web pages Click Add to open the Add a Favorite page Enter the other unit s name and IP address and press Save Network This page allows the configura...

Page 11: ...ely 1 second then release The system will then reboot System Restore to Factory Defaults Warning removes all configuration information including network setup email setup outlets setup sequences and s...

Page 12: ...gy Unlimited due to current limiting Endurance C62 41 1991 category B3 pulses 1 KV 500 000 3 KV 10 000 6 KV 1000 Undervoltage Shutdown Adjustable from 90 Volts to 105 Volts Overvoltage Shutdown Adjust...