background image

XU115 Manual                                                                                                                                            

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

XU115-510 

UPS Fault – 

When the UPS detects a hardware fault, the Bad Battery/Overload/Fault LED will illuminate and 

the UPS will sound a constant alarm. The fault condition, in some instances, may be reset by turning the UPS 
off and then on. 

 
TROUBLESHOOTING 

 
 

Symptom 

Possible Cause 

What To Do 

UPS will not turn on 

On/Off button not pressed 

Press and release the On/Off button 
to start UPS 

UPS operates in battery mode only, 
even though there is normal AC 
present 

Input AC circuit breaker is tripped 

Reset circuit breaker by pressing 
the plunger back in. If the AC 
circuit breaker trips after UPS starts 
up, reduce the load on the UPS 

Fault LED is illuminated 

UPS has detected an internal fault 

Call for service 

The AC Mode LED is illuminated, 
but there is no output 

The UPS is being controlled via its 
communications port 

Disconnect the computer cable 
from the UPS and press the On 
button. If UPS works normally, the 
software has control of the UPS 

UPS does not provide expected 
runtime 

The batteries may be weak or at the 
end of useful service life 

Charge the batteries for 8 hours and 
retest. If the runtime is still less 
than expected, the batteries may 
need to be replaced, even though 
the Weak/Bad Battery LED is not 
illuminated. 

Bad Battery LED is illuminated 

Loose connections at the batteries, 
Weak batteries, Bad batteries 

Check battery connections, charge 
the batteries for 8 hours, replace the 
batteries. 

Overload LED is illuminated 

The load has exceeded the UPS’s 
capacity 

Check the specifications (See 
Specifications section). Remove 
part of the load 

The AC Mode LED is blinking 
once every second and the audible 
alarm is silent 

The UPS is operating in the Boost 
Mode 

The UPS is performing its intended 
function 

The AC Mode LED is blinking 
twice every second and the audible 
alarm is silent 

The UPS is operating in the Buck 
Mode 

The UPS is performing its intended 
function 

 

Summary of Contents for XU115

Page 1: ...XU115 510 USER MANUAL SurgeX XU115 Line Interactive 1000VA UPS with Automatic Voltage Regulation Surge Eliminator Power Conditioner...

Page 2: ...ING YOUR EQUIPMENT 2 USB COMMUNICATIONS PORT CONNECTION 3 PHONE FAX MODEM NETWORK PROTECTION CONNECTION 3 OPERATION 3 CHARGING THE BATTERY 3 TURNING THE UNIT ON OFF 3 USB COMMUNICATIONS PORT 3 POWER M...

Page 3: ...tion To reduce the risk of fire connect only to a circuit provided with 20 amperes maximum branch circuit over current protection in accordance with the National Electric Code ANSI NFPA 70 Plug the UP...

Page 4: ...PS is connected to an AC source and there is an acceptable AC voltage present 90 150VAC It is recommended that the UPS s batteries be charged for a minimum of 4 hours before use The UPS may be used im...

Page 5: ...seconds The alarm will stop once the UPS returns to the AC normal mode Low Battery Warning The UPS will sound two beeps every five seconds when the battery reserve runs low This condition will contin...

Page 6: ...he computer cable from the UPS and press the On button If UPS works normally the software has control of the UPS UPS does not provide expected runtime The batteries may be weak or at the end of useful...

Page 7: ...es and boots 4 Do not lay tools or other metal parts on top of the batteries 5 Disconnect the charging source prior to connecting or disconnecting the battery terminals 6 Determine if the battery is i...

Page 8: ...rload Capability 110 5 minutes 120 immediate shutdown Output Voltage Regulation 120VAC 12 5 to 8 4 Waveform Same as Input Boost Mode Voltage Buck mode voltage Nominal 16 Nominal 14 Line Mode Voltage R...

Page 9: ...nce C62 41 1991 Category B3 pulses 1kV 500 000 3 kV 10 000 6 kV 1000 General Specifications Warranty USA and Canada only 10 year limited warranty Battery Warranty 2 years Monitoring Software Includes...

Reviews: