background image

XU115 Manual                                                                                                                                            

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

XU115-510 

REPLACING THE BATTERY (Qualified Service Personnel Only) 
 

Please read all warnings and cautions before attempting to service the batteries. 
 

WARNING! 

This UPS contains potentially hazardous voltages. Do not attempt to disassemble the UPS beyond 

the battery replacement procedure. This UPS contains no user serviceable parts. Repairs and battery 
replacement must be performed by Qualified Service Personnel Only. 

CAUTION: 

Do not open or mutilate batteries. Released electrolyte is harmful to the skin and eyes and may be 

toxic. 

CAUTION: 

Do not dispose of batteries in a fire. The batteries may explode. The batteries in this UPS are 

recyclable. Dispose of the batteries properly. The batteries contain lead and pose a hazard to the environment 
and human health if not disposed of properly. Refer to local codes for proper disposal requirements or return the 
battery to the supplier. 

CAUTION: 

Although the battery system voltage is only 12VDC and 24VDC the battery system can still 

present a risk of electric shock. These batteries produce sufficient current to burn wire or tools very rapidly, 
producing molten metal. Observe these precautions when replacing the batteries: 

1.

 

Remove watches, rings, or other metal objects. 

2.

 

Use hand tools with insulated handles. 

3.

 

Wear protective eye gear, rubber gloves, and boots. 

4.

 

Do not lay tools or other metal parts on top of the batteries. 

5.

 

Disconnect the charging source prior to connecting or disconnecting the battery terminals. 

6.

 

Determine if the battery is inadvertently grounded. If the battery is, remove the source of the 
grounding. Contact with any part of a grounded battery can result in an electrical shock. The 
likelihood of such shock will be reduced, if such grounds are removed during installation and 
maintenance. 
 

Battery Replacement Procedure 
 
PLEASE READ THE CAUTIONS AND WARNING BEFORE ATTEMPTING TO REPLACE THE 
BATTERIES 
 
BATTERY INFO:   

Battery Qty/Rating: 2 units-12V7Ah

 

First Power Part #: FP1270

 

CSB Part #: GP1272

 

 

1.

 

Turn off the equipment that is plugged into the output receptacles of the UPS.

 

2.

 

Press and release the On/Off Button to turn the UPS off.

 

3.

 

Unplug the UPS’s power cord from the AC wall outlet

4.

 

Unplug the equipment from the output receptacles of the UPS.

 

5.

 

Unplug the computer interface cable from the UPS

 

6.

 

Remove the screws from the Battery Access panel and carefully slide batteries out.

 

7.

 

Disconnect all connections (red and black) noting attachment points and wire colors/connections

 

8.

 

Do not short the battery wires together – Remove batteries and set aside.

 

9.

 

Orient new batteries in the same direction as original batteries.

 

10.

 

Connect black wires first, followed by red wire connections – Some sparking may occur, this is normal.

 

11.

 

Carefully slide the batteries back into the UPS.

 

12.

 

Re-install battery compartment cover and retaining screws.

 

Summary of Contents for XU115

Page 1: ...XU115 510 USER MANUAL SurgeX XU115 Line Interactive 1000VA UPS with Automatic Voltage Regulation Surge Eliminator Power Conditioner...

Page 2: ...ING YOUR EQUIPMENT 2 USB COMMUNICATIONS PORT CONNECTION 3 PHONE FAX MODEM NETWORK PROTECTION CONNECTION 3 OPERATION 3 CHARGING THE BATTERY 3 TURNING THE UNIT ON OFF 3 USB COMMUNICATIONS PORT 3 POWER M...

Page 3: ...tion To reduce the risk of fire connect only to a circuit provided with 20 amperes maximum branch circuit over current protection in accordance with the National Electric Code ANSI NFPA 70 Plug the UP...

Page 4: ...PS is connected to an AC source and there is an acceptable AC voltage present 90 150VAC It is recommended that the UPS s batteries be charged for a minimum of 4 hours before use The UPS may be used im...

Page 5: ...seconds The alarm will stop once the UPS returns to the AC normal mode Low Battery Warning The UPS will sound two beeps every five seconds when the battery reserve runs low This condition will contin...

Page 6: ...he computer cable from the UPS and press the On button If UPS works normally the software has control of the UPS UPS does not provide expected runtime The batteries may be weak or at the end of useful...

Page 7: ...es and boots 4 Do not lay tools or other metal parts on top of the batteries 5 Disconnect the charging source prior to connecting or disconnecting the battery terminals 6 Determine if the battery is i...

Page 8: ...rload Capability 110 5 minutes 120 immediate shutdown Output Voltage Regulation 120VAC 12 5 to 8 4 Waveform Same as Input Boost Mode Voltage Buck mode voltage Nominal 16 Nominal 14 Line Mode Voltage R...

Page 9: ...nce C62 41 1991 Category B3 pulses 1kV 500 000 3 kV 10 000 6 kV 1000 General Specifications Warranty USA and Canada only 10 year limited warranty Battery Warranty 2 years Monitoring Software Includes...

Reviews: