background image

XU115 Manual                                                                                                                                            

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

XU115-510 

SPECIFICATIONS 

 

AC Input 
Number of Phases:

 Single (2W + G) 

Power Cord: 

6-ft. grounded, 3 wire, #14 line cord 

Input Voltage (Acceptable Input Voltage): 

120VAC (0 - 160VAC) 

Input Voltage Range (Normal mode): 

90 - 150VAC 

DC Start Capability: 

Yes, (defaults to 60Hz) 

Power Requirements (no load): 

35 watts (charging), 15 watts (charged) 

 
 
 
AC Output (Normal Mode) 
Load Rating:

 15 Amps @ 120 volts 

Load Power Factor: 

0.6 

Outlets:  

6 outlets (15 Amp) all with Advanced Series Mode surge elimination, 4 outlets with battery back-up 

Output Frequency: 

Same as Input 

Short Circuit Protection: 

Re-settable circuit breaker and electronically limited 

Overload Capability: 

110% - 5 minutes 

≥120% 

- immediate shutdown 

Output Voltage Regulation:

 120VAC: -12.5% to +8.4% 

Waveform: 

Same as Input 

Boost Mode Voltage (Buck mode voltage):

 N16% (Nominal -14%) 

Line Mode Voltage Range:

 105 - 130VAC

 

Efficiency:

 Normal mode > 90%

 

 
 
 
AC Output (Battery Mode) 
Capacity: 

1000VA/600W

 

Back-up Run Time: 

4 minutes 600W full load, 10.4 minutes 300W half load 

Output voltage:  

Nominal 120VAC

 

Waveform: 

Stepped sine wave (simulated sine wave) 

Topology: 

Single boost/buck line interactive, simulated sine wave 

Battery Mode Voltage Regulation: 

Nominal ± 6% until LBW 

Transfer Time: 

6-10 ms

 

Output Frequency & Regulation:

 50/60Hz ± 0.5Hz (Unless synchronized to utility) 

Short Circuit Protection: 

Active electronic (current limit)

 

 
 
 
Batteries 
Battery Rating:

 (2) 12V/7AH 

Replacement:

 Hot swappable

 

Recharge Time: 

8 hours to 90% after full load discharge 

 
 
 

Summary of Contents for XU115

Page 1: ...XU115 510 USER MANUAL SurgeX XU115 Line Interactive 1000VA UPS with Automatic Voltage Regulation Surge Eliminator Power Conditioner...

Page 2: ...ING YOUR EQUIPMENT 2 USB COMMUNICATIONS PORT CONNECTION 3 PHONE FAX MODEM NETWORK PROTECTION CONNECTION 3 OPERATION 3 CHARGING THE BATTERY 3 TURNING THE UNIT ON OFF 3 USB COMMUNICATIONS PORT 3 POWER M...

Page 3: ...tion To reduce the risk of fire connect only to a circuit provided with 20 amperes maximum branch circuit over current protection in accordance with the National Electric Code ANSI NFPA 70 Plug the UP...

Page 4: ...PS is connected to an AC source and there is an acceptable AC voltage present 90 150VAC It is recommended that the UPS s batteries be charged for a minimum of 4 hours before use The UPS may be used im...

Page 5: ...seconds The alarm will stop once the UPS returns to the AC normal mode Low Battery Warning The UPS will sound two beeps every five seconds when the battery reserve runs low This condition will contin...

Page 6: ...he computer cable from the UPS and press the On button If UPS works normally the software has control of the UPS UPS does not provide expected runtime The batteries may be weak or at the end of useful...

Page 7: ...es and boots 4 Do not lay tools or other metal parts on top of the batteries 5 Disconnect the charging source prior to connecting or disconnecting the battery terminals 6 Determine if the battery is i...

Page 8: ...rload Capability 110 5 minutes 120 immediate shutdown Output Voltage Regulation 120VAC 12 5 to 8 4 Waveform Same as Input Boost Mode Voltage Buck mode voltage Nominal 16 Nominal 14 Line Mode Voltage R...

Page 9: ...nce C62 41 1991 Category B3 pulses 1kV 500 000 3 kV 10 000 6 kV 1000 General Specifications Warranty USA and Canada only 10 year limited warranty Battery Warranty 2 years Monitoring Software Includes...

Reviews: