Surge Protection Specifications 
 
Surge Protection: 

Advanced Series Mode® surge elimination 

 

Surge Energy Rating: 

6,000 volts/3,000 amps 

 
Let through Voltage (6,000 volt surge): 

0 volts 

 

UL 1449 Adjunct Classification Test Results:

 1000 surges, 6000 volts, 3000 amps, B3 pulse; Measured 

suppressed voltage: 170 volts; no failures. 

 
Federal Guidelines:

 Grade A, Class 1, Mode 1 (CID A-A-55818) 

 

EMI/RFI Filter, Normal Mode (50-ohm load): 

40 dB @ 100 kHz; 50 dB @ 300 kHz; 50 dB @ 3 MHz; 50 

dB @ 30 MHz 

EMI/RFI Filter, Common Mode (50-ohm load):

 18 dB @ 300 kHz; 30 dB @ 1 MHz; 50 dB @ 5 MHz; 50 

dB @ 20 MHz 
 

Maximum Applied Surge Voltage: 

6000 volts* 

Maximum Applied Surge Current:

 Unlimited, due to current limiting* 

Maximum Applied Surge Energy: 

Unlimited, due to current limiting* 

Endurance (C62.41-1991 Category B3 pulses): 

1kV>500,000; 3 kV>10,000; 6 kV>1000 

 

General Specifications 
 
Warranty: 

(USA and Canada only) 10-year limited warranty 

Battery Warranty:

 2 years  

Monitoring Software:

 Includes SentryPlus software 

Communications: 

USB 

Rack Size: 

2U 

Unit Dimensions (H x W x D): 

3.5” x 19.0” x 10.5” 

Unit Weight (lbs.):

 32.0 lbs. 

Operating Temperature: 

32°F to 104°F (up to 5,000 ft above sea level (0°C to +40°C (up to 1,500 meters 

above sea level) 

Operating Elevation:

 32°F to 95°F (5,001-10,000 ft above sea level (0°C to +35°C (1,501 to 3,000 meters 

above sea level) 

Storage Temperature/Relative Humidity: 

5°F to 113°F (-15°C to +45°C) / 0 - 95% non-condensing 

Humidity Range:

 5% to 95% R.H., non-condensing 

 

* 1.2 x 50 μs pulse, industry standard combination wave surge, as per IEEE C62.41.

 

 
** Specifications subject to change without notice. 
 

*CAUTION:  Do not install this device if there is not at least 10 meters (30 feet) or more between the 
electrical outlet and the electrical service panel. 

 

Summary of Contents for XU115

Page 1: ...XU115 510 USER MANUAL SurgeX XU115 Line Interactive 1000VA UPS with Automatic Voltage Regulation Surge Eliminator Power Conditioner...

Page 2: ...ING YOUR EQUIPMENT 2 USB COMMUNICATIONS PORT CONNECTION 3 PHONE FAX MODEM NETWORK PROTECTION CONNECTION 3 OPERATION 3 CHARGING THE BATTERY 3 TURNING THE UNIT ON OFF 3 USB COMMUNICATIONS PORT 3 POWER M...

Page 3: ...tion To reduce the risk of fire connect only to a circuit provided with 20 amperes maximum branch circuit over current protection in accordance with the National Electric Code ANSI NFPA 70 Plug the UP...

Page 4: ...PS is connected to an AC source and there is an acceptable AC voltage present 90 150VAC It is recommended that the UPS s batteries be charged for a minimum of 4 hours before use The UPS may be used im...

Page 5: ...seconds The alarm will stop once the UPS returns to the AC normal mode Low Battery Warning The UPS will sound two beeps every five seconds when the battery reserve runs low This condition will contin...

Page 6: ...he computer cable from the UPS and press the On button If UPS works normally the software has control of the UPS UPS does not provide expected runtime The batteries may be weak or at the end of useful...

Page 7: ...es and boots 4 Do not lay tools or other metal parts on top of the batteries 5 Disconnect the charging source prior to connecting or disconnecting the battery terminals 6 Determine if the battery is i...

Page 8: ...rload Capability 110 5 minutes 120 immediate shutdown Output Voltage Regulation 120VAC 12 5 to 8 4 Waveform Same as Input Boost Mode Voltage Buck mode voltage Nominal 16 Nominal 14 Line Mode Voltage R...

Page 9: ...nce C62 41 1991 Category B3 pulses 1kV 500 000 3 kV 10 000 6 kV 1000 General Specifications Warranty USA and Canada only 10 year limited warranty Battery Warranty 2 years Monitoring Software Includes...