TROUBLESHOOTING
This unit is equipped with safety sensors that may include
high and low pressure sensors for the refrigeration circuit
and also a flow switch to help prevent freezing if there
is a pump failure or other loss of flow. If any of these
sensors detect a problem, they will not allow the chiller to
function.
Some of the troubleshooting steps listed below can be
performed by the end user, and some of these steps must
be performed by a licensed HVAC technician. Retain this
guide should your chiller ever require servicing.
TEMPERATURE CONTROLLER HAS
NO POWER
1. Ensure switch is in the on position.
2. Check breaker for proper function.
3. Check flow meter for adequate water flow (2.5
GPM per ton). Insufficient flow will cause loss of
power.
4. Visually check for any loose wires.
THE FOLLOWING STEPS SHOULD BE PERFORMED BY
QUALIFIED SERVICE PERSONNEL ONLY
5. Check flow for proper voltage at the unit with an
electric volt-meter.
6. Remove the front cover of the temperature
sensor and check voltage. If 24 VAC is presen
and all wires are installed and tight, the controller
may need to be replaced. If no
voltage is present, see step 7.
7. The controller is wired so that it will not come on
if there is not sufficient water flow to the unit. If
there is no voltage at the controller, check the
flow and verify that the chiller is receiving at least
2.5 GPM for each ton of cooling required. If there
is sufficient flow, see step 8.
8. Check connections of the flow sensor (the flow
sensor is installed in the water line) to verify there
is 24VAC across the sensor while
sufficient water is flowing. If there is no voltage
across the sensor leads with a proper flow-rate,
then the sensor needs to be replaced.
9. Check the direction of flow in the water circuit. If
water is flowing backwards, the flow switch will
not allow power to the temperature controller,
and the unit will not function properly.
TEMPERATURE CONTROLLER IS ON
BUT CHILLER WILL NOT START
1. The unit has a 5-minute delay on start-up
before beginning normal operation. Before
troubleshooting, ensure that 5 minutes have
passed.
2. Check the temperature set-points of the
controller to verify the desired settings are
still in place. The factory differential temperature
should be 3 degrees, and shouldn’t be changed.
For example, with the factory set differential
temperature setting of 3 degrees, and a desired
temperature setting of 45°F (8°C), the unit will
not start until the water reaches 48°F (9°C).
3. Check to make sure the controller is set to C1.
1 8
Summary of Contents for 1-18-01
Page 2: ......
Page 5: ...5...
Page 14: ...1 5 TO 4 TON WIRING DIAGRAM 1 4...
Page 15: ...8 TON WIRING DIAGRAM 1 5...
Page 20: ...s urn a c om 1780 55th Street Suite A Boulder CO 80301 303 993 5271 info surna com A P E...