P Line Touch Panel
Installation and Commissioning
9
2 Installation and Commissioning
2.1
Unpacking the Device
Unpack all parts carefully and check the contents for any visible damage in transit.
Also check whether the shipment matches the specifications on your delivery
note.
If you notice damages in transit or discrepancies, please contact us immediately.
2.2
Mounting the Device
The device can be easily and quickly mounted from the rear of the device. A panel
thickness of 1 mm to 6 mm (0.039" to 0.236") is permitted for proper mounting.
1. Insert the device in the mounting cutout from the front.
Figure 2-1 Mounting the device using a mounting bracket
2. Insert the mounting brackets into the appropriate openings (figure 1) and pull
the brackets downwards until they lock in place (2).
3. Fasten the device into position using the threaded pins (3).
NOTICE: Damage
When installing the device, leave a gap of at least 30 mm (1.181") around the
device to ensure sufficient air circulation.
NOTICE: Damage
When the operating device is installed horizontally, please note that additional
sources of heat beneath the operating device may result in heat accumulation.
Make sure to allow sufficient heat dissipation!
Please observe the permissible temperature range specified in the technical
data of the user manual when operating the device.
NOTICE: Damage
In order to ensure the degree of protection specified in the technical data, al-
ways make sure that the seal lies flat against the mounting surface and the
threaded pins of the mounting brackets are tightened uniformly to a maximum
torque of 1 Nm.
Summary of Contents for P Line
Page 6: ...Overall Table of Contents P Line Touch Panel 6...
Page 42: ...Installation and Commissioning P Line Touch Panel 42...
Page 44: ...Control and Display Elements P Line Touch Panel 44...
Page 58: ...Interfaces of the Device P Line Touch Panel 58...
Page 62: ...Maintenance and Servicing P Line Touch Panel 62...
Page 98: ...Ordering Data P Line Touch Panel 98...
Page 100: ...100...
Page 101: ......