Description of Function Codes NICE3000
new
User Manual
- 162 -
Table 7-7 Functions indicated by bits of F6-09
Bit
Function
Description
Default
Bit1
Disabling returning
to base floor for
verification
The function of returning to base floor for verification
due to large deviation of the car position is disabled.
0
Bit2
Cancelling auto
sequential arrange
of hall call floor
addresses to be
displayed
If the display of a floor in group FE is set to 1, the
following floors to be displayed are automatically
arranged in the ascending order.
0
Bit5
Current detection
valid at startup for
synchronous motor
The controller performs output current detection when
the synchronous motor is started up. If the current is
abnormal, the output will be locked and the running will
be forbidden.
0
Bit6 Reversing MCB
lamp output
After this function is enabled, the MCB lamp output logic
is reversed.
0
Bit7
Door open valid at
non-door zone in
the inspection state
In the inspection state, you can open/close the door by
pressing the door open/close button at the non-door
zone.
0
Bit8
Door open and
close once after
inspection turned to
normal
The elevator door opens and closes once after the
system turns from first-time inspection to normal
running.
1
Bit10 Buzzer not tweet
upon re-leveling
The buzzer inside the car does not tweet upon re-
leveling.
0
Bit11
Super short floor
function
The controller cannot perform shaft-tuning if the floor
height is less than 500 mm. After this function is
enabled, shaft-tuning can be performed normally.
0
Bit12 Fault auto reset
The controller automatically resets the faults once every
hour.
0
Bit13 Err53 fault auto
reset
When Err53 is reported, if the conditions of door open
limit valid and door lock release are satisfied, the
controller resets Err53 automatically. A maximum of
three times of auto reset is allowed.
1
Bit14
Up slow-down not
reset for super short
floor
If this function is enabled, the up slow-down 1 signal
does not reset floor display. The down slow-down 1
signal still resets floor display. This is valid only when
the customized super short floor function is enabled.
0
Bit15
Down slow-down
not reset for super
short floor
If this function is enabled, the down slow-down 1 signal
does not reset floor display. The up slow-down 1 signal
still resets floor display. This is valid only when the
customized super short floor function is enabled.
0
Function Code
Parameter Name
Setting Range
Default
Unit
Property
F6-12
VIP floor
0 to F6-00
0
-
★
It is used to set the VIP floor. For details, see section 5.2.4.
Summary of Contents for NICE3000 New
Page 1: ......
Page 13: ......
Page 14: ...1 Safety Information and Precautions ...
Page 21: ...Safety Information and Precautions NICE3000new User Manual 20 ...
Page 22: ...2 Product Information ...
Page 33: ...Product Information NICE3000new User Manual 32 ...
Page 34: ...3 Mechanical and Electrical Installation ...
Page 67: ...4 Use of the NICE3000new ...
Page 79: ...5 System Commissioning and Application Example ...
Page 105: ...6 Function Code Table ...
Page 136: ...Function Code Table NICE3000new User Manual 134 ...
Page 137: ...7 Description of Function Codes ...
Page 205: ...8 EMC ...
Page 214: ...EMC NICE3000new User Manual 212 ...
Page 215: ...9 Troubleshooting ...
Page 230: ......
Page 233: ......