User Manual Description of Function Codes
- 195 -
Function Code Parameter Name
Setting Range
Default Unit
Property
Fd-09
HCB:JP1 output
0: Invalid
1: Up arrival indicator
2: Down arrival indicator
3: Fault output
4: Non-door zone stop output
5: Non-service state output
6: Door close button indicator
output
1
-
★
Fd-10
HCB:JP2 output
2
-
★
These parameters are used to set the functions of pins 1 and 4 of JP1 and JP2 on the HCB. The
setting is effective to the HCBs for all floors.
Note
The output load capacity of the HCB is limited, with the output voltage of 24 V and the load power
not larger than 1 W.
Function Code
Parameter Name
Setting Range
Default
Unit
Property
Fd-11
HCB-B:JP1 input
0: Reserved
NO/NC input:
1/33: Light-load signal
2/34: Half-load signal
3/35: Door 2 selection
4/36: Door 2 restricted
(back door forbidden)
5/37: Door 1 safety edge
6/38: Door 2 safety edge
7/39: Single/double door
selection
0
-
★
Fd-12
HCB-B:JP2 input
0
-
★
Fd-13
HCB-B:JP3 input
0
-
★
Fd-14
HCB-B:JP4 input
0
-
★
Fd-15
HCB-B:JP5 input
0
-
★
Fd-16
HCB-B:JP6 input
0
-
★
These parameters are used to set the functions of pins 2 and 3 of JP1 to JP6 on the HCB-B
no-display parallel-serial conversion board. The setting is effective to all HCB-Bs connected
to the system.
Summary of Contents for NICE3000 New
Page 1: ......
Page 13: ......
Page 14: ...1 Safety Information and Precautions ...
Page 21: ...Safety Information and Precautions NICE3000new User Manual 20 ...
Page 22: ...2 Product Information ...
Page 33: ...Product Information NICE3000new User Manual 32 ...
Page 34: ...3 Mechanical and Electrical Installation ...
Page 67: ...4 Use of the NICE3000new ...
Page 79: ...5 System Commissioning and Application Example ...
Page 105: ...6 Function Code Table ...
Page 136: ...Function Code Table NICE3000new User Manual 134 ...
Page 137: ...7 Description of Function Codes ...
Page 205: ...8 EMC ...
Page 214: ...EMC NICE3000new User Manual 212 ...
Page 215: ...9 Troubleshooting ...
Page 230: ......
Page 233: ......