NICE3000
new
User Manual Mechanical and Electrical Installation
- 51 -
The following table describes the input and output terminals of HCB-U1.
Table 3-9 Input and output terminals of HCB-U1
Terminal
Name
Function
Terminal Wiring
J1
Interface for the up call button and indicator
Pins 2 and 3 are for up call input.
Pins 1 and 4 are power supply for the up call
indicator (24 VDC output, load capacity: 40
mA).
1 2 3 4
Up call indicator
Up call
button
J2
Interface for the down call button and indicator
Pins 2 and 3 are for down call input.
Pins 1 and 4 are power supply for the down
call indicator (24 VDC output, load capacity: 40
mA).
1 2 3 4
Down call indicator
Down call
button
J3
Interface for the fire emergency and elevator
lock switches
Pins 1 and 2 are for fire emergency input.
Pins 3 and 4 are for elevator lock input.
1 2 3 4
Fire
emergency
input
Elevator
lock input
S1
Button for setting the floor address.
Hold down the button to adjust the floor
address (range: 0−56). After you stop pressing,
the address number blinks three times, and
therefore the setting is successful.
S1
CN1
Modbus communication and power supply
terminal
Pins 2 and 3 are for Modbus communication.
Pins 1 and 4 are for DC power supply.
1 2 3 4
MOD
-
MOD
+
24
V
COM
Summary of Contents for NICE3000 New
Page 1: ......
Page 13: ......
Page 14: ...1 Safety Information and Precautions ...
Page 21: ...Safety Information and Precautions NICE3000new User Manual 20 ...
Page 22: ...2 Product Information ...
Page 33: ...Product Information NICE3000new User Manual 32 ...
Page 34: ...3 Mechanical and Electrical Installation ...
Page 67: ...4 Use of the NICE3000new ...
Page 79: ...5 System Commissioning and Application Example ...
Page 105: ...6 Function Code Table ...
Page 136: ...Function Code Table NICE3000new User Manual 134 ...
Page 137: ...7 Description of Function Codes ...
Page 205: ...8 EMC ...
Page 214: ...EMC NICE3000new User Manual 212 ...
Page 215: ...9 Troubleshooting ...
Page 230: ......
Page 233: ......