USER’S MANUAL

7. CONTROLS AND INDICATORS

FRONT PANEL EXPLANATIONS

a

Line LED 

Green LED remains standstill when Utility is normal.
Green LED flashes every 2 seconds when the UPS is in Battery charging mode.
Green LED remains standstill and simultaneously buzzer alarms continuously when the UPS is in
overload condition.

b

Inverter LED 

Yellow LED flashes every 2 seconds and simultaneously buzzer alarms continuously when Utility 
failure.

c

Overload LED 

Red LED remains standstill and simultaneously buzzer alarms continuously when the UPS is in over-
load condition.

d

Check Battery LED 

Red LED flashes every 0.5 seconds and buzzer alarms every 0.5 seconds when UPS is in battery low
condition.

e

Main Switch 

To Control on/off the UPS when Utility is normal.
To enable "DC-Start" Function when Utility fails. (To enable DC Start properly, you are recommen-
ded to connect <80% output load with the UPS only)
P.S. Make sure the computer connected to the UPS is switched on before enable the "DC-
Start" function. You are not recommended to add some other computer or peripherals after
DC-Start function is activated.

REAR PANEL EXPLANATIONS

a

AC Inlet

b

AC Fuse Holder  

c

Backup Outlets: 6 pcs IEC 320 

d

RJ11/RJ45 Jacks: MODEM /LAN Protection 

NOTE: 

This connection is not needed to use the UPS. The UPS works properly without a

connection

e

Computer Interface: 

USB communication port. (Not supplied, if the RS232 interface is

built)
Use of the software "UPSilon 2000" automatically saves files and shutdown PC.

NOTE: 

This connection is not needed to use the UPS. The UPS works properly without a

connection

8. TROUBLE SHOOTING

14

Situation

Check Items

Solution

Mains normal but Line LED is not on.

Is the power switch on? Is the fuse in
order? Is the power cord loose?

Press Main Switch on. Change fuse
w/same rating. Re'connect the power
cord properly.

'Inverter' LED flashes every 2 sec'
ond but no output.

Battery voltage is too low.

Recharge the UPS for 24 hours.

Alarm buzzer beeps continuously
when Utility is normal.

Check to see load status if it is in over'
load.

Remove some uncritical load.

Alarm buzzer beeps for 10 seconds,
then the UPS is turned off.

Remove some uncritical load and re'
switch on the UPS.

No LED`s display on the front panel.

Consult with your sales agent For help.

UPS dose not provide expected
back up time.

The UPS's battery is weak due to recent
outage. The UPS's battery is near the
end of its service life.

Charge the battery. If the battery is near
the end of its service lift, consider
replacing the battery.

UPS switch on then connect Utility,
but UPS is unable to work under
Utility mode.

Is the Utility normal?

If Utility is normal,connect Utility first
then restart UPS.

Summary of Contents for Power Pro+ 1000

Page 1: ...нтерактивный источник бесперебойного питания ÈÍÑÒÐÓÊÖÈß ÏÎ ýêñïëóàòàöèè PRO 1000 1500 Перед эксплуатацией системы внимательно ознакомьтесь с настоящей инструкцией и сохраните ее на весь период использования Рус ...

Page 2: ...òðóêöèè ТОРГОВЫЕ МАРКИ Âñå òîðãîâûå ìàðêè ÿâëÿþòñÿ ñîáñòâåííîñòüþ èõ çàêîííûõ âëàäåëüöåâ РАСПАКОВКА Àêêóðàòíî ðàñïàêóéòå ÈÁÏ Ïðîâåðüòå óñòðîéñòâî íà ïðåäìåò ïîâðåæäåíèé Åñëè ÈÁÏ ïîâðåæäåí ñðàçó æå îáðàòèòåñü ê äèëåðó Åñëè ÈÁÏ áûë ïîâðåæäåí ïðè òðàíñïîðòèðîâêå îáðàòèòåñü â ôèðìó îñóùåñòâëÿâøóþ äîñòàâêó Ðåêîìåíäóåì Âàì ñîõðàíèòü âåñü óïàêîâî íûé ìàòåðèàë äëÿ âîçìîæíîé òðàíñïîðòèðîâêè АВТОРСКОЕ ПРАВО...

Page 3: ... 5 6 1 Ïîäêëþ åíèå 5 6 2 Ïîäçàðÿäêà àêêóìóëÿòîðíîé áàòàðåè 5 6 3 Ïîäêëþ åíèå îáîðóäîâàíèÿ ê ÈÁÏ 5 6 4 Ïåðåãðóçêè è êîðîòêîå çàìûêàíèå íà âûõîäå 6 6 5 Ïîäêëþ åíèå óñòðîéñòâà çàùèòû îò âûáðîñîâ â òåëåôîííîì ñåòåâîì êàáåëå 6 6 6 Çàìåíà àêêóìóëÿòîðíîé áàòàðåè 6 7 Ýëåìåíòû óïðàâëåíèÿ è èíäèêàòîðû 7 8 Ðåøåíèå âîçìîæíûõ ïðîáëåì 8 9 Òåõíè åñêèå õàðàêòåðèñòèêè 9 3 Рус SVEN Power Pro 1000 1500 ...

Page 4: ...КТАЦИЯ 1 Ëèíåéíî èíòåðàêòèâíûé èñòî íèê áåñïåðåáîéíîãî ïèòàíèÿ 1 øò 2 Ñèëîâîé êàáåëü 2 øò 3 Èíòåðôåéñíûé êàáåëü 1 øò 4 Ñîåäèíèòåëüíûé êàáåëü RJ 11 1øò 5 Ïðîãðàììíîå îáåñïå åíèå 1 äèñê 6 Èíñòðóêöèÿ ïî ýêñïëóàòàöèè 1 øò Ïðèìå àíèå Äîïîëíèòåëüíî ïðîãðàììíîå îáåñïå åíèå ðàçìåùåíî íà ñàéòå äåéñòâóþùàÿ èëè îáíîâëåííàÿ âåðñèÿ http www sven ru 4 ОСОБЕННОСТИ ЛИНЕЙНО ИНТЕРАКТИВНЫХ ИСТОЧНИКОВ БЕСПЕРЕБОЙНОГО ...

Page 5: ...ðàáîòû îáåñïå åíî íåîáõîäèìî îöåíèòü ñóììàðíóþ ìîùíîñòü ïîäêëþ åííîãî ê ÈÁÏ îáîðóäîâàíèÿ Òðåáóåìàÿ ñóììàðíàÿ ìîùíîñòü äîëæíà áûòü ìåíüøå èëè ðàâíÿòüñÿ íàãðóçî íîé ñïîñîáíîñòè ÈÁÏ â ïðîòèâíîì ñëó àå ÈÁÏ áóäåò èçäàâàòü íåïðå ðûâíûé çâóêîâîé ñèãíàë è çàãîðèòñÿ êðàñíûé ñâåòîäèîä Ïðèìå àíèå Äëÿ òîãî òîáû ÈÁÏ ðàáîòàë íàäåæíî â òå åíèå äëèòåëüíîãî âðåìåíè íåîáõîäèìî ïðàâèëüíî âûáðàòü ìîùíîñòü íàãðóçêè èñ...

Page 6: ...ì êàáåëå Ïîäêëþ èòå òåëåôîííûé êàáåëü â ìîäóëü ðàçúåìîâ çàùèòû ìîäåìà òåëåôîííîé ëèíèè îò âûáðîñîâ íà çàäíåé ïàíåëè ÈÁÏ Êîì áèíèðîâàííûé ìîäóëü ãíåçä RJ 11 RJ 45 äîïóñêàåò ïîäêëþ åíèå âñåõ ñòàíäàðòíûõ ðàçúåìîâ òåëåôîííîé ëèíèè è 10 Base T ñå òåâûõ êàáåëåé Êàáåëü îò ÀÒÑ èëè îò ëîêàëüíîé êîìïüþòåðíîé ñåòè ïîäñîåäèíèòå ê ðàçúåìó ñ îáîçíà åíèåì IN Ê ðàçúåìó ñ îáîç íà åíèåì OUT ïîäêëþ èòå çàùèùàåìîå îá...

Page 7: ... èñïîëüçîâàíèÿ ñåòåâîãî èñòî íèêà ïèòàíèÿ ïå ðåìåííîãî òîêà íàæìèòå êíîïêó ÂÊË ÂÛÊË Ñâå åíèå æåëòîãî ñâåòîäèîäà óêàæåò íà òî òî ÈÁÏ âîøåë â àâòîíîìíûé ðåæèì ðàáîòû Âûêëþ åíèå ÈÁÏ Äëÿ òîãî òîáû âûêëþ èòü ÈÁÏ íàæìèòå êíîïêó ÂÊË ÂÛÊË íà ëèöåâîé ïàíåëè ïðè áîðà Çàäíÿÿ ïàíåëü a Âõîäíîé ðàçúåì Òèï âõîäíîãî ðàçúåìà IEC 320 âèëêà Èñïîëüçóéòå âõîäíîé ñèëîâîé êàáåëü òî áû ñîåäèíèòü ÈÁÏ ñ ñåòüþ ýëåêòðîñíàáæå...

Page 8: ... пре дохранитель 3 Плохой контакт в цепях подключе ния ИБП к сети 1 Явление нормальное ИБП защища ет компьютерное оборудование от сбоев напряжения в сети электро снабжения 2 Уменьшите нагрузку и замените предохранитель при отключенном ИБП 3 Проверьте качество подключения ИБП к сети ИБП не обеспечивает ожидаемое время работы в автономном ре жиме Включается индикация о низком уровне заряда аккуму ля...

Page 9: ...дупредительные сигналы Звуковые сигналы 45 дБ на расстоянии 1 метра Входной разъем IEC 320 вилка Выходные разъемы 6 шт IEC 320 от инвертора Рабочие условия окружающей среды Высота над уровнем моря 5000 м 0 50 C при влажности 0 90 без конденсации Сертификаты UL cUL FCC CE TUV РосТест Входные параметры без перехода на работу от батарей Уровень входного напряжения 172 272 В Частота 50 Гц определяется...

Page 10: ...USER S MANUAL 10 Uninterruptible Power System Please read this operation manual before using the unit and retain this operation manual in safe place for future reference ...

Page 11: ...arks and registered trademarks are the property of their respective owners INFORMATION TO USER Changes or modifications to this equipment not expressly approved by the party responsible for compliance could void the user s author ity to operate the equipment UL WARNING STATEMENT See the INSTALLATION SAFETY INSTRUCTIONS section in page 12 Technical support http www sven ru TABLE OF CONTENTS 1 Intro...

Page 12: ... unstable cart stand or table Do not place UPS under direct sunlight or close to heat emitting source Do not place UPS power cord in any area where it may get damaged by heavy objects Do not connect UPS to home appliance e g hairdryer fan etc Do not connect UPS to Laser printer If you store the UPS or UPS does not operate for a long period recharge the battery every month by starting the UPS for 8...

Page 13: ... UPS outlets provide battery power and surge protection to the equipment when utility voltage is outside acceptable limits 6 1 REPLACING THE BATTERY Note Once the battery is disconnected the loads are not protected from power outages Use a cross type screwdriver to remove the two front panel screws and slide down the panel Gently Pull the battery out of the UPS Loosen the black wire from the negat...

Page 14: ... This connection is not needed to use the UPS The UPS works properly without a connection e Computer Interface USB communication port Not supplied if the RS232 interface is built Use of the software UPSilon 2000 automatically saves files and shutdown PC NOTE This connection is not needed to use the UPS The UPS works properly without a connection 8 TROUBLE SHOOTING 14 Situation Check Items Solution...

Page 15: ...ace connection support USB Intelligent software support Win9X Me NT 2000 XP Indicators LED s indicating online on battery overload bad battery Alarm signals Audible signals 45 dB at 1 meter Input socket IEC 320 male socket Output socket 6 x IEC 320 Operating environment Altitude 5 000 m 0 50 C 32 104 F 0 90 RH non condensing Agency Approval UL cUL FCC CE TUV RusTest Input Non Battery Operation Inp...

Page 16: ......

Reviews: