24
UPS fails to provide
battery backup or its
backup time is shorter
than its intended
performance.
If the backup time remains
unsatisfactory after 8 hours of
charging please contact your
local dealer for battery
replacement.
UPS is normal, but
there is no output to
the load.
Check that all power
cords are properly
connected.
If the problem persists consult
your local dealer for technical
assistance.
The UPS switches into
battery mode and then
back into utility mode
when a connected
device is turned on, or
the UPS
switches back and
forth between battery
and utility modes.
1. A power strip is
connected to the
UPS.
See if there is any
damage to the utility
wall receptacle or if
the cord plug is faulty.
1. Do not use the power strip.
2. Replace the wall
receptacle/cord plug.
Strange noise or smell
Immediately shut down the whole
system. Disconnect the power
from the UPS and call for
service.
UPS is unable to
provide backup power.
Check that the battery
connectors are fully engaged.
Allow the batteries to recharge if
they are weak. If the problem
persists after recharging replace
the batteries. If the problem still
persists consult your local dealer
for technical assistance.
25
Error Codes
When the Fault LED
is lit press the ON button ‘
’ briefly to check the
error code. The error codes 1, 2, 4, 8, and 16 are represented by the four
bar LEDs 25%, 50%, 75%, and 100%, and the Overload LED
. Each
LED represents a number as shown in the figure below. For example, the
figure below shows the 25%, 50%, and 100% bar LEDs lit. The error code
is therefore 8 + 2 + 1 = 11, or Er11, which indicates that the UPS is over-
temperature.
1
2
4
8
16