The Inverter, charger and batteries are monitored continuously. Fault conditions are
presented on the display or via a variety of monitory devices available for purchase.
APPROVEMENT: IEC/EN 62040-1:2008+A1:2013. EMC; IEC/EN 62040, IEC/EN 61000
UPS2200-900: Online UPS with 2x9Ah AGM batteries and super stabilization for 230VAC
output even during heavy disturbance on the main input power. Internal bypass cutover if the
UPS is exposed to abnormal high load. The UPS is equipped with 10A breakers on both in- and
output.
UPS2200-1800: An off-line UPS 1-phase with 4x9Ah AGM batteries. The unit is given a
powerful UPS-relay to withstand high currents up to 16A. The UPS is equipped with 10A
breakers on both in- and output.
UPS2200 protection:
•
Short circuit protection
•
Over load protection
•
Deep discharge protection
•
Breakers on both in- and output.
•
Inverter and battery fuse
4. Connection
•
Mount the unit freely. Minimum 100mm space on each side.
•
Switch off all breakers, both in- and output.
•
Make sure that there is no power on the incoming cable.
•
First connect the main power, and then connect the load.
•
Make sure that the connections are tight and proper.
5.
Commissioning - Startup
.
•
Power up the main cable.
Switch on the breaker for in- and output.
Power up the UPS by holding the on button for 3 sec, indicated with a beep. After a short
time the UPS will power up. The UPS is now operating and status is shown on the
display.
•
Check the UPS operation:
Cut the main power by switching the input breaker off. The
display will toggle from LINE to BATT and will indicate an alarm beeping ever 4 sec. Load
and battery status is shown on the display. Switch the breaker on and the UPS should
return to normal operation after a 10 sec delay. The display toggles back from BATT to
LINE again.
•
Shutting down the UPS: Cut
the main power or switch the input breaker off. Press the
off button and hold for 3 sec, indicated with a beep. The UPS will now start to shut down
which will take 20 sec to complete.