Actionair DWFX-C Installation Guide

14

Swegon reserves the right to alter specifications.           20220503 - LNNN00353 (5.0)                                                                               

Inspection and handover check sheet

This certificate applies only to Swegon Fire Dampers. The installer must complete this installation certificate when instal

-

ling fire and smoke dampers. A separate certificate must be completed for each individual fire and smoke damper.

Damper Unique System I.D: ..........................................................................................................................................................
Name of installation location:......................................................................................................................................................... 
Address:............................................................................................................................................................................................ 

Installation location identification section/floor/room: ................................................................................................................

 

Damper product type: .................................................................................................................................................................... 
Release fuse temperature: .............................................................................................................................................................. 
Notes/Considerations: ....................................................................................................................................................................
Installed by: ..................................................................................................................................................................................... 
Company Name: ............................................................................................................................................................................ 
Address: .......................................................................................................................................................................................... 
Company Telephone No: ............................................................................................................................................................... 
Installers Name: .............................................................................................................................................................................. 
Installers Telephone No: ................................................................................................................................................................. 
Date of installation: ........................................................................................................................................................................

It is hereby verified that the damper detailed above has been installed and tested according to the manufactures recom

-

mendations:
Installers signature: ................................................................................................ 

Date: ................................................

Question

Action

1

Are the dampers the correct type?

Confirm damper is correct type for the application

2

Are the dampers located correctly?

The damper location is to be checked against the installation 

drawings/details

3

Are the dampers correctly identified?

Unique system ID to be clearly indicated on the damper or 

other agreed location.

4

Have supports for both the damper and the adjacent 

ductwork been installed in accordance with the appro-

ved manner?

5

Are the dampers fitted in the correct orientation?

Confirm the damper is installed with any actuators (if applica

-

ble) on the left or right hand side. Not on the top or the bot-

tom (i.e. blade pivot running vertically) unless permitted under 

the respective DoP.

6

Is access through the ductwork, to the damper unob-

structed?

Unobstructed space should be provided for safe access to the 

damper. This must include access through ceiling voids and ad-

jacent services. Damper installer to advise the system designer 

if problems are foreseen.

7

Has the space around the damper and within the 

opening been left clear and not been used for other 

services?

Other services within the installation opening will invalidate 

the installation method. Damper installer to advise the lead 

contractor if problems are foreseen.

8

Using the access opening provided, check that blades 

open and close.

Check position of damper blades.

9

Has the damper been checked for internal cleanliness, 

free from damage and that vertical casings in particular 

are free from debris?

With the damper in the closed position, inspect for damage.

10

Has the damper been released to simulate operation of 

the thermal release? (Damper drop test)

Ensure damper operation is free from interference.

11

Have the damper blades been re-set following drop 

test and the access panel replaced?

After re-setting the damper, check the position shown on the 

blade position indicator is correct.

12

At the time of damper handover, is the fire barrier and 

penetration seal complete?

Damper installer to record on the handover register if  

any following trades are still to complete their activities.

13

Is the damper installation complete and available for 

handover prior to system commissioning?

Obtain the relevant acceptance of the damper installation from 

the CDM coordinator.

14

Is the completed handover register cross-referenced 

back to the identification codes listed in the system 

designers damper schedule?

Summary of Contents for actionair DWFX-C

Page 1: ...y a competent person Care must be taken when installing and inspecting dampers as they are likely to close without warning due to loss of electrical power or a temperature rise in the ductwork This is their prime function Do not insert any items fingers or limbs between the blades Larger dampers must be handled in accordance with current regula tions and good practice due to weight Drawings Please...

Page 2: ...s as early as possible in the project to get important stakeholders engaged and ensure an instal lation solution can be found The instructions are based on the tested method using Actionair SmokeShield PTC and FireShield products Our SmokeShield dampers are designed to be used with fire separating elements to maintain fire compart ments The SmokeShield is an actuated failsafe close damper with low...

Page 3: ... 1227 Email actionair sw www swegon c Plea for la co Inst and SC G ECN2227 Vertical Damper Installation in a Plasterboard Wall with Pattress Actionair SmokeShield PTC AA F 10708 Illustrated above Actionair FireShield AA F 10709 Installation Method 1 Fit track of partition to the ceiling 2 Suspend the damper from the ceiling through the centre of the partition ceiling track using 10mm stud ding dro...

Page 4: ...99 MJB 04 11 20 Swegon Air Management Limited South Street Whitstable Kent CT5 3DU Tel 44 0 1227 276100 Email actionair swegon com www swegon com uk Please refer to the DoP for latest classifications for CE UKCA compliance and the Installation Operation and Maintenance Guide SCAN ME D ECN2227 JPM 13 04 22 Vertical Damper Installation in a Plasterboard Wall without Pattress Actionair FireShield AA ...

Page 5: ... Manag South Street Whitstable Tel 44 0 1227 Email actionair s www swegon Plea for l co Inst and SC H ECN2227 Vertical Damper Installation in a Plasterboard Wall against a Floor Slab Actionair SmokeShield PTC AA F 10730 Actionair FireShield AA F 11682 Installation Method 1 Apply a bead of low pressure intumescent mastic along top edge of damper as a gap filler and Install the damper against the fl...

Page 6: ... are only available for 72 C For Dampers where alternative thermal link temperatures are required a chain link can be offered in place of a cassette Electrical release is only available with a cassette i e 72 C Please refer to Actionair Sales Office Please note For dampers with dimensions of 150mm and below ensure that there is adequate access to enable re setting Self Latching Removable Release M...

Page 7: ...ion Both screws should be tightened fully to ensure that both sections of the ETR are closed together It is a safety feature if both sections are not closed the unit will not operate For ductless installations the ETR should be fitted onto the damper spigot not casing above the damper interface shroud and in accordance with the fitting instructions If the ETR is not fitted in the exact manner desc...

Page 8: ...nths A comprehensive example of the maintenance pro cedure is given in Annex D of the standard Some automatic systems may allow more frequent testing 48hr or less and this may be required by a national standard Approved Document B Volume 2 Clause 10 12 states adequate means of access must be provided to allow inspection testing and maintenance of both fire damper and its actuating mechanism BS 999...

Page 9: ... CONTACT WHEN DAMPER MADE BETWEEN 1 2 FULLY RELEASED VOLT FREE CONTACT MADE BETWEEN 4 6 WHEN DAMPER FULLY RESET TF 72 C AC 250V 6 3 A CONTINUITY WITH COMMON ELECTRICAL THERMAL RELEASE ETR MUST BE FITTED TO DUCTING FOR DAMPER OPERATION SPRING BIASED TEST SWITCH WHEN DAMPER CLOSED CONTINUITY WITH COMMON WHEN DAMPER OPEN CONTINUITY WITH COMMON WHEN DAMPER CLOSED CONTINUITY WITH COMMON WHEN DAMPER OPE...

Page 10: ...OR S AND HEIGHTS OF 100 150MM FOR DUCT WITH WIDTHS AND HEIGHTS OF 200 1000MM FOR DUCT WIDTHS AND HEIGHTS OF 151 199MM FOR DUCT WIDTHS 200MM 1000MM WITH HEIGHTS OF 100 199MM Base Dampers Circular Dampers Series 601 For Circular and Flat Oval Dampers spigots are 3mm under duct size Diameters and flat oval diameters in 1mm increments Circular Dampers Series 601 FOR DAMPERS 100 150MM D FOR CIRCULAR AM...

Page 11: ...es partly in airstream Damper spigots stream OVERALL WIDTH OF INSTALLATION FRAME IS DUCT WIDTH 114 Series 301 spigots 5mm under duct size 100 249 high use Series 101 Damper as OVERALL WIDTH OF INSTALLATION FRAME IS DUCT WIDTH 114 spigots 3mm under duct size OVERALL WIDTH OF INSTALLATION FRAME IS DUCT WIDTH 114 OVERALL WIDTH OF INSTALLATION FRAME IS DUCT WIDTH 114 FireShield ...

Page 12: ...Actionair DWFX C Installation Guide 12 Swegon reserves the right to alter specifications 20220503 LNNN00353 5 0 Cleat dimensions FireShield SmokeShield PTC ...

Page 13: ...y wired Check wiring in accordance with procedures The ETR cables have been damaged or tampered with Replace with new mode Control Mode operates but limited or no movement of damper blades is observed The mode is not correctly synchronised with the interface Remove motor from interface Check motor in fully released state Set position of interface and refit motor with label upmost include motor loc...

Page 14: ...ess permitted under the respective DoP 6 Is access through the ductwork to the damper unob structed Unobstructed space should be provided for safe access to the damper This must include access through ceiling voids and ad jacent services Damper installer to advise the system designer if problems are foreseen 7 Has the space around the damper and within the opening been left clear and not been used...