Actionair DWFX-C Installation Guide
2
Swegon reserves the right to alter specifications. 20220503 - LNNN00353 (5.0)
Application
Installation Method
Actionair SmokeShield
Actionair FireShield
Vertical Damper Installation in a
Plasterboard Wall with Patress
Page 3, [AA/F 10708]
Page 3, [AA/F 10709]
Vertical Damper Installation in a
Plasterboard Wall without Patress
N/A
Page 4, [AA/F 10723]
Vertical Damper Installation in a
Plasterboard Wall against a Slab
Page 5, [AA/F 10730]
Page 5, [AA/F 11682]
• The methods in this manual should be followed to
ensure a CE-marked installation. This CE installation
document covers single dampers only. If a multiple
damper assembly or, if a non-standard install is requi-
red, talk to us as early as possible in the project to get
important stakeholders engaged and ensure an instal-
lation solution can be found.
• The instructions are based on the tested method using
Actionair SmokeShield PTC and FireShield products.
• Our SmokeShield dampers are designed to be used
with fire separating elements to maintain fire compart
-
ments. The SmokeShield is an actuated failsafe close
damper with low smoke leakage, often referred to in
the industry as a Fire/Smoke damper.
• Under the Fire Damper Product standard BS EN 15650
our Fire Damper products are tested to BS EN 1366-2
and classified under BS EN 13501-3.
• For smoke control, the product you use should be
tested to BS EN 12101-8 and drive open, drive closed
without failsafe position, see our website for informa-
tion on the Actionair SmokeCommand smoke con-
trol damper documentation and suitable installation
methods.
CE Installation Method Overview