ThermShield Standard Square/Rectangular Installation Guide
14
Swegon reserves the right to alter specifications. 20210615 - L00010
6
1
3
7
Suspension for
mortarless installation
close to ceiling
Damper blade must be closed during installation!
Suspension systems are required for the dry mortarless
installation of the fire damper with mineral wool in solid
walls and flexible walls. Fire dampers can be suspended
from solid ceiling slabs using adequately sized threaded
rods. Load the suspension system only with the weight of
the fire damper. Ducts must be suspended separately.
1. Prepare opening in the wall according to H + 130mm
and B + 200mm or more and install threaded rods (8 mm)
to the ceiling above.
2. Insert fire damper into wall to the wall limit mark (7)
on the damper and bend the fixing bracket (1) 90°. (screw
hole is 6mm in diameter). Fix the C profile on the drop
rods using M8 screws.
3. Close the space between casing and wall with mineral
wool (
≥
140 kg/m³) (3). Connections of mineral wool
should be sealed with intumescent fire resistant sealant
(6). Mineral wool and damper casing must be coated
with 2mm.
Test the operation of the damper blade!
Ensure that the damper is sufficiently supported!
18mm
27mm
1
2
3