ThermShield Standard Square/Rectangular Installation Guide
(1) Accessories
(2) Type
(3) Length
FD-A
-
CF60
800
(1)
(2)
Fire damper accessories
FD-A
Type
CF60 - Connecting frame 60mm
CF100 - Connecting frame 100mm
CP60- Connecting plate 60mm
CP100- Connecting plate 100mm
(3)
Connecting frame length
200 ... 1200[mm]
Battery assembly
installation 2x2 & 2X1
Damper blade must be closed during installation!
The wall is composed of concrete blocks (minimum
density of 550 kg/m³) or reinforced concrete (minimum
density of 2200 kg/m³) and with a minimum thickness of
100mm.
Maximum dimension of a single unit in a 2 X 2 battery
installation:
2X2 grid: 1200x800mm
*For battery installation 2x2 use 8x connecting frames
and 2x connecting plate.
1. Prepare a hole of dimensions 2B + 140 mm and 2H
+ 140mm fill the bottom with mortar/gypsum in 50mm
height.
2. Place two lower dampers in the opening, and fix
dampers to the wall using screws (only 2 sides facing
aerated concrete). Place the vertical part from the
installation kit to the dampers on both sides, and attach it
using the self-tapping screws.
3. Fill the space between the dampers and the wall with
mortar/gypsum, and fill the space between the dampers
with mineral wool (100 kg/m³ of density or higher). Place
two upper dampers and fix the dampers to the wall using
the screws (only 2 sides facing aerated concrete).
4. Place the vertical part and two horizontal parts from
the installation kit to the dampers on both sides, and
attach it using the self-tapping screws every 150mm.
Fill the gap between dampers and wall on upper side
with mortar/gypsum and the installation is complete.
Test the operation of the damper blade!
Ensure that the damper is sufficiently supported!
1
2
3
4