20210615 - L00010 Swegon reserves the right to alter specifications.
ThermShield Standard Square/Rectangular Installation Guide
150
150
150
150
150
150
150
150
150
Battery assembly
installation 1x2
Damper blade must be closed during installation!
The wall is composed of blocks of aerated concrete
(minimum density 550 kg/m³) and with a minimum
thickness of 100mm.
Maximum dimension of fire dampers:
1X2 grid: 1500x800mm
*For battery installation 1x2 use 2x connecting frame.
1. Prepare a hole of dimensions B + 80mm and 2H + 140
mm. Fix the dampers to the wall using the screws and fill
the space between the dampers and the wall with mortar.
2. Place the installation kit to the dampers.
3. Attach the installation kit to the dampers using the self-
tapping screws every 150mm.
4. Fill the space between the dampers with mineral wool
(100 kg/m³ of density).
Ensure that the damper is sufficiently supported!
(1) Accessories
(2) Type
(3) Length
FD-A
-
CF60
-
800
(1)
(2)
Fire damper accessories
FD-A
Type
CF60 - Connecting frame 60mm
CF100 - Connecting frame 100mm
CP60- Connecting plate 60mm
CP100- Connecting plate 100mm
Connecting frame length
200 ... 1200[mm]
150
150
150
1
2
3
4