ThermShield MF(1 & 2) Installation Guide
12
Swegon reserves the right to alter specifications. 20210615 - L00014
Minimal seperation
damper installation
(circular)
Damper blade must be closed during installation!
Firebatt- Mineral wool
1*. Prepare opening in the wall according to the
installation type.
(Firebatt installation- build the subframe according to the
drawing see page 13.
Mortar- Gypsum blocks
1. Prepare opening in the wall according to page 4.
Fire damper can be installed with minimal distance of
30 mm between wall/ceiling and 30 mm from other
dampers.
2. Insert the fire dampers into the wall and fill the space
between the casings with mineral wool (140kg/m³) up to
flanges.
30
30
30
30
Ød/2
30
1*
Fill the space between the wall/ceiling with mineral wool
(140kg/m³) up to flanges.
3. Fill the rest of the wall openings in accordance to the
relevant installation method.
Material compliant with the
classification from DOP
Mineral wool 250mm wide
(140 kg/m³)
*Minimal distances from another damper or wall/ceiling.
1
2
3
4