ThermShield MF(1 & 2) Installation Guide
Rigid wall installation
MF1/MF2 installation
frame
Damper blade must be closed during installation!
The wall is composed of concrete blocks (minimum
density of 550 kg/m³) or reinforced concrete (minimum
density of 2200 kg/m³) and with a minimum thickness of
100 mm.
1. Create an opening in the wall
(FDC25- Ød +10 mm, FDC40-Ød + 25 mm).
2. Place the damper in the opening.
3. Fasten the fire damper with screws
FDC25- 4pcs, 6x160 mm,
FDC40- 12pcs, 6x160 mm.
Ensure that the damper is sufficiently supported.
Test the operation of the damper blade!
1
2
3