ADAPT

TM

 

Colibri d

Installation – Commissioning – Maintenance

20150225  /  Art. No. 1545215

Installation

All connections to the duct system should be done with a 
straight duct of the same dimension as the box inlet and 
with a length > 2 * ØD. If a flexible duct is used, it should be 
stretched so it remains as straight as possible, see figure 1.
1. The commissioning box can be suspended from a 

ceiling and connected to a duct system. Use hanger 
system (A) or (B), see figure 2.

2. Press the ADAPT Colibri air diffuser into the outlet of 

the commissioning box and secure it with screws or 
pop rivets. The diffuser should be turned so it’s hinges 
(C, figure 2) face the same direction as the inlet of the 
commissioning box. Readjust the hanger rods of the 
commissioning box if needed, so that the air diffuser is 
firmly positioned against the false ceiling, or the frame-
work of the modular suspended ceiling.

3. Remove the frontplate section of the air diffuser by 

applying the Quick Access principle, see figure 3. 

4. Connect the air diffuser connector to the appropriate 

contact in the upper surface of the diffuser face plate.

5. Flip the diffuser face plate up to close it.

Figure 1. Using a flexible duct.

A

B

C

Figure 2. ADAPT Colibri, installation, make sure the diffuser is 
turned with it’s hinges (C) facing the same direction as the inlet 
of the commissioning box.

Figure 3. Quick Access.

Summary of Contents for ADAPT Colibri d

Page 1: ...s The diffuser should be turned so it s hinges C figure 2 face the same direction as the inlet of the commissioning box Readjust the hanger rods of the commissioning box if needed so that the air diffuser is firmly positioned against the false ceiling or the frame work of the modular suspended ceiling 3 Remove the frontplate section of the air diffuser by applying the Quick Access principle see fi...

Page 2: ... orange The different LED indications Steady green LED Normal operation the air diffuser is operating normally Flashing green LED The air diffuser has just been powered on and calibration is in progress Steady red LED Function failure see separate docu mentation in the TUNE Adapt manual Steady orange LED The commissioning mode max airflow Flashing orange LED Other commissioning modes and all the f...

Page 3: ...f longer distances are required All cables and contacts are different so that they will not be confused or incorrectly connected Electrical data ADAPT is supplied with power via the connection box See the wiring diagram in figure 7 or relevant diagram from the Swegon Templates application containing details for the specific installation It is important that cables with appro priate cross sectional...

Page 4: ...m version without display Q0 1 VA Room version with display Q1 and duct version Q2 3 VA 7c DETECT RH humidity sensor 1 VA 8 ACTUATOR radiator control max 3 valves at 6 VA 9 ADAPT Relay relay for lighting 10 Connection to main control system Modbus RTU 11 SPLIT Link RJ45 12 SPLIT Modbus RJ12 max stab length 10 m Only one of the accessories in paragraph 7 can be connected at any one time in a room i...

Reviews: