Installation – Commissioning – Maintenance, ADAPT Fb

20120718  /  Art. No. 1545217  

Montering

1. The commissioning box can be suspended from a ceiling 

and connected to a duct system.The diffuser is secured 
to the ceiling by connecting the M8 threaded rod (A) 
into the popnut on the top of the diffuser, see figure 2. 

2. Make sure that the orientation of the sensor module 

aligns with the extension of the room, see figure 1. If 
the connecting duct does not enter the room as in the 
example in figure 3, the frontplate of the diffuser must 
be dismantled and rotated in a direction with the sensor 
module directed as shown in figure 1. Then fixate and 
secure the diffuser with screws or pop rivets. Readjust 
the hanger rods of the commissioning box if necessary

3. The front plate is dismantled by pressing the fixing pins 

of the bottom plate outward, which will loosen it from 
the upper cone. Detach the safety cord that secures front 
plate to the upper cone and disconnect the connector 
(C, figure 2) from the top of the front plate. When reas-
sembling, press together the S-hook to prevent it from 
coming loose. 

A

B

C

Figure 2. ADAPT Free, installation.

Figure 1. The orientation of the sensor module in a room or in 
an office module. The LED’s of the sensor should be aligned with 
the extension of the room in a straight line, facing the short sides 
of the room as shown by the arrow in the figure.