ADAPT
Parasol EXb
6
Swegon reserves the right to alter specifications. 01/09/2020
Side 1-4, (left-hand connection on side 4)
Type
Primary air
volume
Side
Nozzle
setting
k-factor /
side
690
Low
1,2,3,4
L
0.253
690
Average
1,2,3,4
M
0.44
690
High
1,2,3,4
H
0.693
690
None
1,2,3,4
C
0
1290 MF
Low
1&3
L
0.176
1290 MF
Average
1&3
M
0.253
1290 MF
High
1&3
H
0.429
1290 MF
None
1&3
C
0
1290 MF
Low
2&4
L
0.464
1290 MF
Average
2&4
M
0.667
1290 MF
High
2&4
H
1.131
1290 MF
None
2&4
C
0
1290 HF
Low
1&3
L
0.253
1290 HF
Average
1&3
M
0.44
1290 HF
High
1&3
H
0.693
1290 HF
None
1&3
C
0
1290 HF
Low
2&4
L
0.667
1290 HF
Average
2&4
M
1.16
1290 HF
High
2&4
H
1.827
1290 HF
None
2&4
C
0
1290 PF
Low
1&3
L
0.85
1290 PF
Average
1&3
M
0.99
1290 PF
High
1&3
H
1.21
1290 PF
None
1&3
C
0
1290 PF
Low
2&4
L
2.22
1290 PF
Average
2&4
M
2.62
1290 PF
High
2&4
H
3.2
1290 PF
None
2&4
C
0
1
k (1+3) + p
i
(1.3) => q (1+3)
K-factor of the short sides together with the
commissioning pressure reading of these equals
the flow of the short sides, 1&3.
2
k (2+4) + p
i
(2.4) => q (2+4)
K-factor of the long sides together with the
commissioning pressure reading of these equals
the flow of the long sides, 2 & 4.
3
q tot =q (1+3) + q (2+4)
The total flow of the product is the sum of the above.
NB! p
i
(1.3) = p
i
(2.4)
NOTE: The commissioning pressure is different
for the long sides (2 & 4) and the short sides
(1 & 3).
/
Water
Air
2
4
3
Side 1-4, (standard connection on side 2)
Water
Air
1
2
4
1
3
P
i
(2.4)
P
i
(1.3)
k-factor guide per side