ADAPT

TM

 

Sphere b

Installation – Commissioning – Maintenance, ADAPT Sb

20120718  /  Art. No. 1545216

Installation

1. The commissioning box can be suspended from a 

ceiling and connected to a duct system. Use hanger 
system (A) or (B), see figure 2.

2. The front plate of ADAPT Sphere can be dismantled by 

pressing the fixing pins of the bottom plate outward, 
which will loosen it from the upper cone. The bottom 
plate is secured to the upper cone by a safety cord.  

3. Press the ADAPT Sphere air diffuser into the outlet of 

the commissioning box. Make sure that the orientation 
of the sensor module aligns with the extension of the 
room, see figure 1. Then fixate and secure the diffuser 
with screws or pop rivets. Readjust the hanger rods of 
the commissioning box if necessary, so that the air dif-
fuser is firmly positioned against the false ceiling. 

4. Connect the air diffuser connector into the top of the dif-

fuser (C, figure 2) and attach the safety cord. Press together 
the S-shaped hook to prevent it from coming loose.

5. Attach the diffuser section to the cone using the 3 pins.
6. The distance between the commissioning box and the 

diffuser section can be extended to up to 200 mm. If a 
greater distance is required, this is only possible if an order 
is placed for a special version with extra long cables. 

A

B

C

Figure 2. ADAPT Sphere, installation.

Figure 1. The orientation of the sensor module in a room or in 
an office module. The LED’s of the sensor should be aligned with 
the extension of the room in a straight line, facing the short sides 
of the room as shown by the arrow in the figure.