3.3 Integer Value (RO): IV R
O b j e c t
Instance
Object Name
Min/Max
17
Changeover Status
0-1
Automatic changeover between heating and cooling (0=inactive, 1=heating, 2=cooling)
18
Defrost Status
0-2
0=IDLE, 1=ACTIVE, 2=STOP to drain water
19
Digital Outputs Status
0-65536
Contains a bit for each of the digital outputs:
bit0="AL1 (alarm)"
bit1="BYPASS 1 (For on/off bypass: 0=closed/off 1=open/on. For prop_bypass: 0=down
1=up"
bit2="BYPASS 2 (For on/off bypass: always on. For prop_bypass: 0=stop 1=run)"
bit3="CT"
bit4="KWin"
bit5="KWout"
bit6="OR1 SAT “pressure alarm””
bit7="OR2 SAT “fan on”"
bit8="OR3 SAT “water pump NV”"
bit9="OR4 SAT “bypass on”"
bit10="SATBA WP"
bit11="SATBA OUT9 KWext"
20
OUT INT ELECT PREHEAT
0-100
Output percentage for the power control of the electrical preheater
21
OUT INT ELECT POSTHEAT
0-100
Output percentage for the power control of the electrical postheater inside the unit
22
OUT EXT ELECT POSTHEAT
0-100
Output percentage for the power control of the electrical postheater external to the unit
23
CP SENSOR MODBUS SUPPLY
0-9999 [Pa]
Pressure measured by the Modbus sensor located on the supply duct
24
CP SENSOR MODBUS EXHAUST
0-9999 [Pa]
Pressure measured by the Modbus sensor located on the exhaust duct