www.swegon.se     1

GB.BCHA455.050101

Specifications are subject to alteration without notice.

2.1 General

The humidifier should be installed in wet areas with floor 

gulley and should preferably be located upstream of the air 

cooler, if there is one.

2.1.1 Humidifier selection

The following recommendations apply to the water quality, 

type of installation and control equipment in conjunction with 

selecting a humidifier (see also Sections 2.2-2.5):

2.1.2 Symbols used and technical correlation

The  chart  (right)  shows  the  humidification  process  with 

water having the same temperature as the wet-bulb  tem-

perature t

v

.

The humidifiers should be connected to a cold water supply. 

Any change of enthalpy will then be negigible, even though 

the water supplied has a slightly lower temperature than the 

wet-bulb air temperature.

Degree of humidification b

x

 =

 

 

 

 

 

 

BCHA

Instructions for the BASIC
BCHA Humidifier, Sizes 004–055

1. General

The BCHA is an evaporative humidifier designed for once-
through  water  or  circulated  water.  The  water  evaporates 
from an unheated contact fill, consisting of an inorganically 
impregnated, woven glass fibre of cross-block design. 

The  contact  fill  is  incombustible  and  thus  is  not  affected 
by high air temperatures or high water temperatures. The 
woven glass fibre is also highly water absorbent that allows 
complete wetting of the surfaces.

The air flow through the humidifier must be horizontal.
The water distribution system for circulated water consists 
of  water  spray  tubes,  pump,  drain  valve,  float  valve  and 
internal pipework.

The components of the BCHA are easy to reach for cleaning. 
They can easily be withdrawn from the inspection door. The 
water tray is made of stainless steel; has its drainage line on 
the inspection side. If the drain connection at the side of the 
unit is left open, it must be fitted with a type BCXZ-1-71-5 
water trap.

WARNING! 

Do not open the inspection doors on the pressurized 

side downstream of the fan. The door may otherwise 
fly open and cause personal injury.

1.1 Specification

The version, size, etc. are specified in the delivery documents.

2. Installation

Water consumption due to evaporation, E, can be calculated 

as follows:
E= q · 60 · 1.2 · (x

– x

1

) l/min, where q = air flow, m

3

/s

X

max

–X

1

X

2

–X

1

Symbols

x

1

      =  inlet air moisture 

 

 

  content   

x

2

 

=  outlet air moisture  

 

 

  content

x

max

  =  moisture content at    

 

  saturation point

 

=  relative humidity

=  dry-bulb temperature

t

v

 

=  wet-bulb temperature

Summary of Contents for BASIC BCHA

Page 1: ...d woven glass fibre of cross block design The contact fill is incombustible and thus is not affected by high air temperatures or high water temperatures The woven glass fibre is also highly water absorbent that allows complete wetting of the surfaces The air flow through the humidifier must be horizontal The water distribution system for circulated water consists of water spray tubes pump drain valve fl...

Page 2: ...table level 2 3 Electrical connections Before wiring the humidifer remove the humidifier casettes and run the power supply cables through the casing to the humidifier pump and the solenoid valve The cables must not be run above or through the inspection door A safety isolating switch for the appropriate rated output and cur rent tabulated on page 6 Section 4 1 Electrical data must precede the electr...

Page 3: ... fitted with a cleanable type BCXZ 1 71 water trap 6 and must be run without any reduction in diameter to a floor gulley 2 7 Humidification by once through water 2 7 1 Connecting the humidifier to the mains water system Fit a constant flow valve 3 to the inlet of the distribution tube size 15 conn Then connect the supply pipe 1 to the constant flow valve Fit a solenoid type or motor driven shut off valv...

Page 4: ...ere is a high concentration of calcium and bicarbonate in thewaterorifthedustconcentrationintheairishigh inspect the humidifier more often If circulated water is used the bleed off flow can be increased see page 2 The frequency of inspection and the bleed off rate are conditional on the installation and should be based on experience 3 3 When servicing check the following 1 The humidifying surface sh...

Page 5: ...assettes have been withdrawnfromthehumidifier Openthehoseclamp 2 and lift the cover plate with spray pipe 3 Pull the spray pipe 4 out of the cover plate Remove the end plugs 5 from the spray pipe Use an awl or a similar tool to clean the holes in the spray pipe and flush the pipe clean with water 3 6 To clean the water tray Remove the overfilling protection 1 and clean the bottom of the water tray ...

Page 6: ...lation class B 4 1 Electrical data 4 Technical data Weight std Weight EI 30 W o water With water W o water With water 65 85 Weight std Weight EI 30 W o water With water W o water With water 60 66 68 74 70 80 80 90 94 142 110 158 117 180 137 200 130 211 152 233 163 269 189 295 195 325 225 355 242 417 277 452 004 1039 546 453 006 1259 656 453 009 1459 756 653 014 1759 906 653 020 1946 1026 653 027 2...

Reviews: